Desa CGB3930NRA, CGD3924NRA, CGB3924NRA Unvented Natural GAS LOG Heater Installation

Page 8

UNVENTED NATURAL GAS LOG HEATER

INSTALLATION

Continued

NOTICE: Manual control heaters may be used as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open, noncombustible material above fireplace opening is not needed. Go to Installing Damper Clamp Accessory for Vented

If Using Mantel

You must have noncombustible material(s) above the fireplace opening. Noncombus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible mate- rial must extend at least 8 inches up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). Even

if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and Figures 6 and 7 on page 9 for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.

Operation, page 10.

Minimum Noncombustible Material Clearances

If Not Using Mantel

Note: If using a mantel, go to If Using Mantel. If not using a mantel, follow the information below.

You must have noncombustible material(s) above the fireplace opening. Noncombus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible mate- rial must extend at least 8" up (for all mod- els). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). See Figure 5 for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.

Noncombustible

Requirements for

Material Distance (A)

Safe Installation

 

 

12" or more

Noncombustible material okay.

Between 8" and 12"

Install fireplace hood accessory (GA6050, GA6052,

 

or GA6053, see Accessories, page 27).

Less than 8"

Noncombustible material must be extended to at

 

least 8". See Between 8" and 12", above. If you

 

cannot extend material, you must operate heater

 

with flue damper open.

Heat Resistant

Material

(A)

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace

8

105677

Image 8
Contents Remote Ready What to do if YOU Smell GASUnvented Natural GAS LOG Heater Safety Information Product Features Remote Control AccessoriesProduct Identification Local CodesConfined Space and Unconfined Space Providing Adequate VentilationUnusually Tight Construction Determining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Check GAS TypeMinimum Fireplace Clearance to Combustible Materials LOG Sizing RequirementsUnvented Natural GAS LOG Heater Installation Minimum Noncombustible Material ClearancesDetermining Minimum Mantel Clearances When Using a Hood Mantel ClearancesFloor Clearances Determining Minimum Mantel ClearancesInstallation Items Needed Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Connecting to GAS Supply Attaching Flexible Gas Hose to HeaterInstalling Remote RE- Ceiver Unit Checking GAS ConnectionsInstalling 9-Volt Battery in Receiver Installing Wireless Remote Control AccessoryInstalling Logs CGD3924NRA Installing Logs on Models CGB3924PRA and CGB3930PRA Tered over the burner U bendLighting Instructions For Your Safety Read Before LightingOperating Heater Manual Lighting Procedure Unvented Natural GAS LOG Heater OperatingTo Turn OFF GAS To Appliance Optional Remote OperationMain Burner Inspecting BurnersPilot Flame Pattern Unvented Natural GAS LOG Heater Cleaning and Maintenance Service HintsTechnical Service Cleaning Burner Injector Holder and Pilot AIR Inlet HoleTroubleshooting Observed Problem Possible Cause RemedyUnvented Natural GAS LOG Heater Troubleshooting Maintenance,Gas leak. See Warning statement at Unvented Natural GAS LOG Heater Illustrated Parts Breakdown CGD3924NRAParts List KEY Part Number Description QTYCGB3924NRA CGB3930NRA KEY CGB3924NRA CGB3930NRA Part Number Description QTY Unvented Natural GAS LOG Heater Replacement Parts Parts Under WarrantyParts not Under Warranty Parts CentralWiring Diagram AccessoriesSpecifications Warranty Information