Desa GWP6 Ventilation AIR, Ventilation Air From Inside Building, Ventilation Air From Outdoors

Page 5

AIR FOR COMBUSTION AND VENTILATION

Continued

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

 

 

Gas water heater

 

40,000

 

_____________ Btu/Hr

Vent-free heater

+

10,000

_____________ Btu/Hr

Total

=

50,000

_____________ Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

AIR FOR COMBUSTION AND VENTILATION

5

Determining Fresh-Air Flow For Heater Location

Ventilation Air

 

 

 

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Example: 51,200 Btu/Hr (maximum the space can support) 50,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.

Rework worksheet, adding the space of an adjoining room. If the

 

extra space provides an unconfined space, remove door to adjoining

 

room or add ventilation grills between rooms. See Ventilation Air From

 

Inside Building.

B.

Vent room directly to the outdoors. See Ventilation Air From Outdoors.

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Sec- tion 5.3 or applicable local codes.

12"

Figure 2 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

For more information, visit www.desatech.com

107902-01D

Image 5
Contents What to do if YOU Smell GAS GWN6, GWP6GWN10T, GWP10T GWRN10 and GWRP10 Safety Information Table of ContentsUnpacking Product FeaturesProduct Identification Local CodesDetermining FRESH-AIR Flow for Heater Location AIR for Combustion and VentilationProviding Adequate Ventilation Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Items InstallationCheck GAS Type Locating HeaterInstalling Two Mounting Screws Installing Heater to WallMarking Screw Locations Placing Heater On Mounting ScrewsRemoving Front Panel Of Heater Connecting to GAS SupplyInstalling Bottom Mounting Screw Checking GAS Connections Pressure Testing Gas Supply Piping SystemReplace front panel Pressure Testing Heater Gas ConnectionsLighting Instructions Operating HeaterTo Turn OFF GAS To Appliance Manual Lighting ProcedureShutting Off Heater Shutting Off Burner Only pilot stays litBurner Patterns To Select Heating LevelThermostat Control Operation Pilot Flame Pattern Inspecting BurnerBurner Flame Pattern Blue Flame Models Burner Flame Pattern Infrared ModelsCleaning Burner Pilot AIR Inlet Hole Cleaning MaintenanceODS/PILOT and Burner Orifice CabinetObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at GWP6 GWN6 GWP10 GWN10 Pilot Illustrated Parts BreakdownKEY Part Number for GWP6 GWN6 GWP10 GWN10 Description QTY Parts ListGWRP10 GWRN10 KEY Part Number GWRP10 GWRN10 Description QTY GWP10T GWN10T Pilot KEY Part Number GWP10T GWN10T Description QTY GWP6 GWP10 GWRP10 GWP10T SpecificationsService Hints Replacement PartsTechnical Service Service Publications AccessoryBaltimore Electric Parts CentralsOwners Registration Form Postage Required 107902-01D Warranty Information

GWN10T, GWP10T, GWRN10, GWN6, GWP6 specifications

Desa GWN10, GWP10, GWRP10, GWP6, and GWN6 are innovative products designed to meet diverse demands in various sectors. Each model brings unique features and characteristics, tailored for specific applications in the world of technology and daily use.

Desa GWN10 is recognized for its robust design and energy efficiency. It employs advanced wireless communication technology, enabling seamless integration with smart home systems. The GWN10 stands out with its high performance in terms of connectivity range and reliability. It offers users the convenience of remote monitoring and control, making it ideal for residential and commercial use, especially in areas that require a secure and efficient energy solution.

GWP10, on the other hand, is engineered for flexibility and versatility. Its modular design allows users to configure the system according to their specific needs. The GWP10 utilizes cutting-edge battery technology, providing longer usage times and faster charging capabilities. With its user-friendly interface and cloud connectivity, users can easily track energy consumption and optimize settings for enhanced performance.

The GWRP10 is a game-changer in renewable energy applications. Equipped with advanced solar integration technologies, it can harness solar power effectively, making it an eco-friendly choice. The GWRP10 features intelligent energy management systems that optimize power distribution, ensuring that energy is used efficiently. This model is perfect for users looking to reduce their carbon footprint while enjoying reliable power supply.

GWP6, a compact powerhouse, offers exceptional performance in a smaller footprint. Its lightweight construction and easy installation make it suitable for urban environments where space is a premium. The GWP6 leverages latest communication standards, such as IoT connectivity, providing real-time data insights for users. This makes it ideal for mobile applications and temporary installations.

Finally, the GWN6 emphasizes portability and ease of use. With its rugged design, it is perfect for outdoor activities and off-grid solutions. The GWN6 includes battery backup options, ensuring uninterrupted power during outdoor adventures. Its durable build and waterproof features make it reliable for challenging environments.

Together, these models showcase Desa’s commitment to innovation, sustainability, and user-centric design. Whether for energy management, renewable energy integration, or portable power, Desa GWN10, GWP10, GWRP10, GWP6, and GWN6 provide advanced solutions for contemporary needs. Their groundbreaking technologies and features are setting new standards in their respective categories, making them valuable assets for both everyday consumers and businesses alike.