Desa VP600BA, VN600BA, VN1000BTA, VP1000BTA, VN10A, VP10A, VN6D, VP5D Connecting to GAS Supply

Page 8

8

INSTALLATION

Installing Heater To Wall (Cont.) Connecting To Gas Supply

INSTALLATION

Continued

Installing Bottom Mounting Screw

1.Locate bottom mounting hole. This hole is near bottom on back panel of heater (see Figure 11).

2.Mark screw location on wall.

3.Remove heater from wall.

4.If installing bottom mounting screw into hollow or solid wall, install wall anchor. Follow steps 1 through 5 under Attaching To Wall Anchor Method, page 7. If installing bottom mounting screw into wall stud, drill hole at marked location using 9/64" drill bit.

5.Replace heater on wall.

6.Insert bottom anchor screw through back panel into bottom anchor or drilled hole (see Figure 11).

7.Tighten screw until heater is firmly secured to wall. Do not over tighten.

Note: Do not replace front panel at this time. Replace front panel after making gas connections and checking for leaks (see pages 8 through 10).

Figure 11 - Installing Bottom Mounting Screw

CONNECTING TO GAS SUPPLY

WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pres- sure regulator.

WARNING: A qualified service person must con- nect heater to gas supply. Follow all local codes.

WARNING: For natural gas, never connect heater to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

IMPORTANT: For natural gas, check gas line pressure before connecting heater to gas line. Gas line pressure must be no greater than 14 inches of water. If gas line pressure is higher, heater regulator damage could occur.

For more

CAUTION: For propane/LP gas, never connect heater directly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and pro- pane/LP supply.

For propane/LP gas, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 12. Pointing the vent down protects it from freezing rain or sleet.

CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in cer- tain areas. Check your local codes. Use pipe of large enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.

Installation must include equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 13, page 9).

IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

Propane/LP

 

Supply Tank

External Regulator

 

Vent Pointing Down

Figure 12 - External Regulator With Vent Pointing Down (propane/LP systems only)

visit www..com

110720-01A

Image 8
Contents VENT-FREE GAS Heater What to do if YOU Smell GASTable of Contents Safety InformationProduct Features UnpackingProduct Identification Local CodesAIR for Combustion and Ventilation Providing Adequate VentilationDetermining FRESH-AIR Flow for Heater Location Confined and Unconfined SpaceAIR for Combustion VentilationVentilation AIR Ventilation Air From Inside BuildingInstallation Installation ItemsCheck GAS Type Locating HeaterInstalling Heater to Wall Installing Two Mounting ScrewsMarking Screw Locations Placing Heater On Mounting ScrewsConnecting to GAS Supply Installing Bottom Mounting ScrewPressure Testing Gas Supply Piping System Checking GAS ConnectionsLighting Instructions Pressure Testing Heater Gas ConnectionsOperating Heater Manual Lighting Procedure To Turn OFF GAS To ApplianceShutting Off Heater Shutting Off Burner Only pilot stays litTo Select Heating Level Burner PatternsOFF Position Shown Inspecting Burner Thermostat Control OperationPilot Flame Pattern Burner Flame Pattern Blue Flame ModelsCleaning Maintenance Cleaning Burner Pilot AIR Inlet HoleBurner Flame Pattern Infrared Models ODS/PILOT and Burner OrificeTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Gas leak. See Warning statement at Specifications VP600BA VP5D VP10A VP1000BTAIllustrated Parts Breakdown VN600BA VP600BA PilotParts List KEY Part Number for VP600BA VN600BA Description QTYVP10A VN10A KEY Part Number VP10A VN10A Description QTY VP5D VN6D ODS/PILOT KEY Part Number VP5D VN6D Description QTY VP1000BTA VN1000BTA Pilot KEY Part Number VP1000BTA VN1000BTA Description QTY Replacement Parts Technical ServiceService Publications AccessoryOwners Registration Form Postage Required Parts Centrals Baltimore ElectricWarranty Information

VP600BA, VN600BA, VN1000BTA, VP1000BTA, VN10A, VP10A, VN6D, VP5D, VP1000BTA VN10A, VP10A specifications

The Desa VP600BA, VN600BA, VN1000BTA, VP1000BTA, VN10A, VP10A, VN6D, and VP5D models represent a remarkable lineup in the realm of ventilation and heating solutions. Each of these models is designed with specific features and technologies that cater to diverse needs, enhancing comfort and efficiency in residential and commercial environments.

Starting with the VP600BA and VN600BA, these models provide robust heating capabilities paired with user-friendly interfaces. Highlighting energy efficiency, both units are engineered to minimize energy consumption while maximizing output. The VN1000BTA and VP1000BTA step up the game with advanced thermostatic controls. These models not only provide reliable heating but also enable precise temperature regulation, ensuring optimal comfort levels.

The VN10A and VP10A models are tailored for versatility, accommodating various space sizes without compromising performance. Equipped with high-efficiency burners, they deliver consistent warmth even in colder climates. The VN6D and VP5D models are compact yet powerful, making them perfect for smaller spaces or areas where installation flexibility is essential. Their lightweight design allows for easy maneuverability while maintaining high-temperature output.

Innovative technologies define these models, with features like electronic ignition systems that provide a hassle-free start-up experience. Many bear smart technology integration, allowing users to control settings remotely via smartphone applications. This level of interactivity signifies a growing trend in home automation, where convenience is key.

The aesthetics of these models cannot be overlooked. With sleek designs and customizable options, they seamlessly blend into a variety of interior decors, enhancing the overall ambiance of any space. The builds are also designed for durability, featuring corrosion-resistant materials that assure longevity.

In terms of safety, these models incorporate multiple redundancies, including automatic shut-off features and robust flame management systems. Hence, user peace of mind is guaranteed alongside effective heating solutions.

Overall, the Desa VP600BA, VN600BA, VN1000BTA, VP1000BTA, VN10A, VP10A, VN6D, and VP5D models exemplify a harmonious balance of function, technology, and design, making them ideal choices for heating and ventilation in contemporary settings. Their array of features ensures each unit meets the specific demands of users, providing an energy-efficient and comfortable environment regardless of the application.