Quadra-Fire SAPPHIRE-D-MBK, SAPPHIRE-MBK, SAPPHIRE-D-PMH Twist-lock the vent cap and seal

Page 17

Step 8.

Slip the storm collar over the pipe, and push it down to the top of the flashing Figure 5.16. Use non-hardening sealant above and below the joint between the storm collar and the pipe.

Optional High Wind Termination Cap

Secure Flashing with Non-Hardening

Sealant and Roofing Nails

Figure 5.16

Step 9.

Twist-lock the vent cap and seal.

Note: For multi-story vertical installations, a ceiling firestop is required at the second floor, and any subsequent floors Figure 5.17. The opening should be framed to 10 in. x 10 in. (254mm x 254mm) inside dimensions, in the same manner as shown in Figure 5.14 on page 16.

Nails

Ceiling Firestop

Minimum 1 in.

(25mm) Clearance

Minimum 1 in.

(25mm) Clearance

Minimum 1 in.

(25mm) Clearance

Minimum 1 in.

(25mm) Clearance

Figure 5.17

WARNING

Fire Risk.

Explosion Risk.

Any occupied areas above the first floor, including closets and storage spaces, which the vertical vent passed through must be enclosed. The enclosure may be framed and sheetrocked with standard construction materials; however, refer to these installation instructions for the minimum allowable clearance between the outside of the vent pipe and the combustible surfaces of the enclosure. Do not fill any of the required air space with insulation.

Quadra-Fire • Sapphire • 7055-116 Rev. D • 6/11

17

Image 17
Contents Do Discardnot What to do if you smell gasDo not Discard this Manual Mfg Date Serial Number Model NameTable of Contents 1Listing and Code Approvals Manufacturer Requirements Requirements for the Commonwealth of MassachusettsBELOW. Keep Clear of ALL Obstructions Getting Started Design & Installation ConsiderationsTools and Supplies Needed Inspect Appliance & ComponentsDesign Purposes only Selecting Appliance LocationClearances to Combustibles Vent Termination Minimum Clearances 4Termination LocationsAlcove Applications Venting Components Vent InformationUse of Elbows Measuring StandardsVenting Guidelines for Horizontal Runs How to Use the Vent GraphType B Straight Out Installation Type a Up and Out InstallationType C 45 Elbow in Corner Installation Horizontal Termination203mm Step Direct Vent Pipe Vertical TerminationStep Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Existing Masonry Chimney Type a Type C Up & Out Installation Type D Hearth MountType a & B Co-Axial to Co-Linear Fire Risk Explosion Risk Retro Connector Gas Information Installation Propane LP Natural GasFuel Conversions Converting to LP GasScrews Rubber Gasket Identification Label F Valve Regulator ReplacementPressure Gas Pressures Gas ConnectionCheck for GAS Leaks High Altitude InstallationsConnecting to the Appliance Recommendation for WireWire Size Max. Length Electrical InformationStanding Pilot Ignition System Wiring SwitchIgnitor ValveAccessories Appliance SetupRemove Shipping Materials Top to Rear Vent ConversionLeg Leveling System Baffle Installation/AdjustmentBrick Installation Embers Positioning the LogsMineral Wool Do not use substitute material Glass Door Assembly Optional Blower InstallationBlower Shutter Adjustment Controls Operating InstructionsBefore Lighting Appliance Lighting Appliance For Your Safety Read Before LightingAfter Appliance is Lit Frequently Asked QuestionsInitial Break-in Procedure Symptom Possible Cause Corrective Action TroubleshootingBe Placed in this Opening After servicing Maintaining and Servicing Your ApplianceNecessary. USE Caution When CLEANING/HANDLING Ceramic Burner Maintenance Tasks InspectReference Materials Appliance Dimension DiagramMm inner pipe 6-5/8 in mm outer pipe Vent Components DiagramDescription Vent Components ListSimpson Dura-VentSimpson HHT SLPDescription Dura-Vent Termination Caps & KitsService Parts Log Set AssemblyPart number list on following 19 18Stocked At DepotBK-GAS Description Comments Part NumberLPK-30K StockedNGK-30K Limited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Contact Information