Quadra-Fire SAPPHIRE-D-MBK, SAPPHIRE-MBK, SAPPHIRE-D-PMH owner manual Gas Pressures Gas Connection

Page 25

B. Gas Pressures

C. Gas Connection

Proper input pressures required for optimum appliance per- formance, gas line sizing requirements need to be followed from NFPA51.

WARNING

Fire Risk.

Explosion Hazard.

High pressure will damage valve.

Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

NOTE: Have the gas supply line installed in accordance with local building codes, if any. If not, follow ANSI Z223.1. Instal- lation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter.)

NOTE: A listed (and Commonwealth of Massachusetts approved) 1/2 inch (13mm) T-handle manual shut-off valve and flexible gas connector are connected to the 1/2 inch (13mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

WARNING

Verify inlet pressures.

High pressure may cause overfire condition.

Low pressure may cause explosion.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Pressure requirements for appliance are shown in the table below.

PRESSURE

NG

LP

Minimum Inlet Pressure

5 inches w.c.

11 inches w.c.

Maximum Inlet Pressure

10 inches w.c.

13 inches w.c.

Manifold Pressure on “HI”

3.5 inches w.c.

10 inches w.c.

If the pressure is not sufficient, ensure:

1)The piping used is large enough.

2)The supply regulator is adequately adjusted.

3)That the total gas load for the residence does not exceed the amount supplied.

The regulator that attaches directly to the residence inlet or to the propane tank is the supply regulator. It should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.

WARNING

Gas Leak Risk.

Support control when attaching pipe to prevent bending gas line.

NOTE: The gap between the supply piping and gas access hole may be plugged with non-combustible insulation to prevent cold air infiltration.

Leak test all gas line joints and the gas control valve prior to and after starting the appliance.

Before making the gas connection, ensure that the appliance you are installing is designed for the type of gas being supplied. This information can be found on the Ratings Label under the appliance. If the appliance has been converted to propane (LP), the valve cover should have a label stating that the unit has been converted to propane.

Connect the gas line at the 3/8 in. (9.5mm) pipe connector on the valve at the back of appliance. We recommend connecting the appliance with an approved flex gas line. If flex gas lines are not approved in your area, you must connect a hard pipe to the gas hookup.

You must supply a manual shut-off valve in a visible location within 3 feet (914mm) of the appliance.

Quadra-Fire • Sapphire • 7055-116 Rev. D • 6/11

25

Image 25
Contents Do not Discard this Manual What to do if you smell gasDo Discardnot Mfg Date Serial Number Model NameTable of Contents 1Listing and Code Approvals BELOW. Keep Clear of ALL Obstructions Requirements for the Commonwealth of MassachusettsManufacturer Requirements Getting Started Design & Installation ConsiderationsTools and Supplies Needed Inspect Appliance & ComponentsClearances to Combustibles Selecting Appliance LocationDesign Purposes only Vent Termination Minimum Clearances 4Termination LocationsAlcove Applications Venting Components Vent InformationUse of Elbows Measuring StandardsVenting Guidelines for Horizontal Runs How to Use the Vent GraphType B Straight Out Installation Type a Up and Out InstallationType C 45 Elbow in Corner Installation Horizontal Termination203mm Step Direct Vent Pipe Vertical TerminationStep Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Type a & B Co-Axial to Co-Linear Type C Up & Out Installation Type D Hearth MountExisting Masonry Chimney Type a Fire Risk Explosion Risk Retro Connector Gas Information Installation Propane LP Natural GasFuel Conversions Converting to LP GasScrews Rubber Gasket Identification Label F Valve Regulator ReplacementPressure Gas Pressures Gas ConnectionCheck for GAS Leaks High Altitude InstallationsConnecting to the Appliance Recommendation for WireWire Size Max. Length Electrical InformationStanding Pilot Ignition System Wiring SwitchIgnitor ValveAccessories Appliance SetupRemove Shipping Materials Top to Rear Vent ConversionBrick Installation Baffle Installation/AdjustmentLeg Leveling System Mineral Wool Positioning the LogsEmbers Do not use substitute material Glass Door Assembly Optional Blower InstallationBlower Shutter Adjustment Before Lighting Appliance Operating InstructionsControls Lighting Appliance For Your Safety Read Before LightingInitial Break-in Procedure Frequently Asked QuestionsAfter Appliance is Lit Symptom Possible Cause Corrective Action TroubleshootingBe Placed in this Opening After servicing Maintaining and Servicing Your ApplianceNecessary. USE Caution When CLEANING/HANDLING Ceramic Burner Maintenance Tasks InspectReference Materials Appliance Dimension DiagramMm inner pipe 6-5/8 in mm outer pipe Vent Components DiagramDescription Vent Components ListSimpson Dura-VentSimpson HHT SLPDescription Dura-Vent Termination Caps & KitsService Parts Log Set AssemblyPart number list on following 19 18Stocked At DepotBK-GAS Description Comments Part NumberNGK-30K StockedLPK-30K Limited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Contact Information