Installing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

The smaller one is for the liquid refrigerant

The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may

 

 

need to extend the pipe using the assembly pipe (optional).

 

 

The connection procedure for the refrigerant pipe varies

 

 

according to the exit position of the pipe when facing the wall:

A

B

• Right(A)

• Left(B)

 

C

• Underside(C)

 

 

 

 

• Rear

 

 

 

 

Outer Diameter

Torque

1.

Cut out the appropriate knock-out piece (A, B, C) on the rear of the

 

 

N•m

kgf•cm

 

 

indoor unit unless you connect the pipe directly from the rear.

 

 

 

 

 

 

ø6.35 mm

14~18

140~180

2.

Smooth the cut edges.

 

 

 

ø9.52 mm

34~42

350~430

 

 

3.

Remove the protection caps of the pipes and connect the assembly

 

 

 

ø12.70 mm

49~61

500~620

 

pipe to each pipe. Tighten the nuts first with your hands, and then with

 

 

 

 

ø15.88 mm

68~82

690~830

 

a torque wrench, applying the following torque:

 

 

 

 

 

 

 

 

• If you want to shorten or extend the pipes, refer to page 42~43.

4.Cut off the remaining foam insulation.

5.If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

6.Pass the pipe through the hole in the wall.

7.For further details on how to connect to the outdoor unit and evacuate the air, refer to page 46~48.

• The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test;

refer to page 49 for further details.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

05 INSTALLATION

English-41

A3050 TV_IB&IM_DB68-04043A-01_EN.indd 41

2014/8/15 15:44:37

Image 41 Contents
A3050 TVIB&IMDB68-04043A-01EN.indd 2014/8/15 Features of your new air conditioner Contents English-4 Safety precautionsEnglish-5 For Power SupplyEnglish-6 For UsingEnglish-7 English-8 Do not place objects or devices under the indoor unitEnglish-9 For CleaningEnglish-10 Checking before useOperation ranges English-11 Checking the power consumptionMain parts Checking the name of the partsDisplay English-12English-13 Checking the remote controllerRemote controller buttons Battery changing time Remote controller displayStoring the remote controller Inserting the batteriesBasic function English-16 Press the button to adjust the temperaturePress the button to set the desired fan speed Vertical air flow Adjusting the air flow directionHorizontal air flow ARHSF Horizontal air flow ARHSSEnglish-18 Using the Fast functionUsing the Comfort function English-19 When the air conditioner is on and in cool/heat modeMode Press the On Timer or Off Timer button to set the time Setting the On/Off timerPress the Set/Cancel button to activate it on Additional options available in On timer modeWhen the air conditioner is turned on Using the Auto Clean functionEnglish-21 If the air conditioner is on If the air conditioner is offEnglish-22 Using the Single User functionUsing the Virus Doctor function You can reduce the noise generated from an indoor unit Using the Quiet functionCleaning the indoor unit Cleaning the air conditionerCleaning the outdoor unit heat exchanger English-24Removing the Air filter Cleaning the air filterEnglish-25 Dry the Air filter in a ventilated areaTop of the Air filter into the the main body..  Reassembling the Air filterEnglish-26 English-27 Maintaining the air conditionerEnglish-28 TroubleshootingAir conditioner Check if you press the Set/Cancel button on the remote Adjustment is notCheck that there are strong lighting apparatus near the air Water is droppingEnglish-30 Installing the unitGeneral information Power supply line, fuse or circuit breaker Choosing the installation location a place where the air filter can be replaced easily Indoor unitEnglish-32 Where sulfide gas existsOutdoor Unit Top view Side view When installing more than 1 outdoor unitEnglish-33 Accessories in the indoor unit case AccessoriesEnglish-34 Unit mmOptional accessories Accessories in the outdoor unit caseTools required for installation General Tools Tools for test operationsEnglish-36 Fixing the installation plateFix the indoor unit If you fix the indoor unit on a wall If you fix the indoor unit on a window frameAssembling the hanger screw This QR code for detail video of indoor unit installationRemoving the screws English-37English-38 Assembling the Cover panel After mounting the indoor unitCable specification Connecting the assembly cableConnecting the cable English-39Close the cover panel Each wire is labeled with the corresponding terminal numberEnglish-40 English-41 Cutting or extending the pipe Evacuating the indoor unitEnglish-42 Unscrew the caps at the end of each pipeDepth a English-43Put a flare nut slightly into the pipe and modify the flare English-44 Drain hose installationEnglish-45 English-46 Evacuating the connected pipesConnect a drain hose to the drain plug Ensure that condensation draining is adequateEnglish-47 Adding RefrigerantOuter Torque If you use a pipe longer than 7.5 mPlease fill in with indelible ink English-48 the factory refrigerant charge of the product 1975English-49 Performing the gas leak testsEnsure the wall will be able to suspend the weight of rack Outdoor unit installed on the wall by rackFixing the outdoor unit in place English-50English-51 Smart Install mode Off / Blinking / On English-52English-53 Final check and trial operationEnglish-54 How to connect your extended power cablesApply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withEnglish-55 A3050 TVIB&IMDB68-04043A-01EN.indd 2014/8/15 Register your product at DB68-04043A-01 Air Conditioner