Performing the gas leak tests

Make sure to check for gas leaks before completing the installation process (connecting the assembly pipe and hose between indoor unit and outdoor unit, insulating the cables, hose and pipe, and fixing the indoor unit to the installation plate).

A

B

Test part for outdoor unit

Tightening torque for body cap (Refer to the table)

Spindle

Charging core

R-22: Diameter of the screw - 7/16-20UNF

R-410A: Diameter of the screw - 1/2-20UNF

Tightening torque for charging port cap (Refer to the table)

To check for gas leaks on the outdoor unit,

Check the valve A and B using a leak detector.

To check for gas leaks on the indoor unit,

Check the flare nut C and D using a leak detector.

C D

Test part for indoor unit

Before inspecting the leakage, use a torque wrench to close the cap for the service valve. (Comply with a tightening torque for each size of the diameter,and tighten the cap firmly to prevent any leakage.).

To check for any possible leakage, insert inert gas into the pipes connected to indoor/outdoor units and check the connection part of the indoor/outdoor units with soap lather or liquid for leakage test.

Outer

Tightening torque

Diameter

Body cap (N•m)

Charging port cap

(mm)

(N•m)

 

ø 6.35

20 ~ 25

 

ø 9.52

20 ~ 25

 

ø12.70

25 ~ 30

10 ~ 12

ø15.88

30 ~ 35

 

ø19.05

35 ~ 40

 

( 1 N•m = 10 kgf•cm )

05 INSTALLATION

Leak test with nitrogen (before opening valves)

In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-410A, it’s responsible of installer to pressurize the whole system with nitrogen (using a cylinder with pressure reducer) at a pressure above 40 bar (gauge).

Leak test with R-410A (after opening valves)

Before opening valves, discharge all the nitrogen from the system and create vacuum according to page 46~48. After opening valves, check leaks using a leak detector for refrigerant.

Pump down (before disconnecting the refrigerant connections for unit repair, removal or disposal) Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit.

This operation must be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere.

Shut off the liquid valve with the Allen wrench.

Turn the system on in cooling with fan operating at high velocity.

(Compressor will immediately start, provided 3 minutes have elapsed since the last stop).

After 2 minutes of operation, shut the suction valve with the same wrench.

Turn the system off and switch mains supply off.

Disconnect tubing. After disconnection, protect valves and tubing ends from dust.

Compressor damage may occur if run at a negative suction pressure.

English-49

A3050 TV_IB&IM_DB68-04043A-01_EN.indd 49

2014/8/15 15:44:39

Image 49 Contents
A3050 TVIB&IMDB68-04043A-01EN.indd 2014/8/15 Features of your new air conditioner Contents English-4 Safety precautionsEnglish-5 For Power SupplyEnglish-6 For UsingEnglish-7 English-8 Do not place objects or devices under the indoor unitEnglish-9 For CleaningOperation ranges Checking before useEnglish-10 English-11 Checking the power consumptionMain parts Checking the name of the partsDisplay English-12Remote controller buttons Checking the remote controllerEnglish-13 Battery changing time Remote controller displayStoring the remote controller Inserting the batteriesBasic function Press the button to set the desired fan speed Press the button to adjust the temperatureEnglish-16 Vertical air flow Adjusting the air flow directionHorizontal air flow ARHSF Horizontal air flow ARHSSUsing the Comfort function Using the Fast functionEnglish-18 Mode When the air conditioner is on and in cool/heat modeEnglish-19 Press the On Timer or Off Timer button to set the time Setting the On/Off timerPress the Set/Cancel button to activate it on Additional options available in On timer modeWhen the air conditioner is turned on Using the Auto Clean functionEnglish-21 If the air conditioner is on If the air conditioner is offUsing the Virus Doctor function Using the Single User functionEnglish-22 You can reduce the noise generated from an indoor unit Using the Quiet functionCleaning the indoor unit Cleaning the air conditionerCleaning the outdoor unit heat exchanger English-24Removing the Air filter Cleaning the air filterEnglish-25 Dry the Air filter in a ventilated areaEnglish-26 Reassembling the Air filterTop of the Air filter into the the main body..  English-27 Maintaining the air conditionerAir conditioner TroubleshootingEnglish-28 Check if you press the Set/Cancel button on the remote Adjustment is notCheck that there are strong lighting apparatus near the air Water is droppingGeneral information Installing the unitEnglish-30 Power supply line, fuse or circuit breaker Choosing the installation location a place where the air filter can be replaced easily Indoor unitOutdoor Unit Where sulfide gas existsEnglish-32 English-33 When installing more than 1 outdoor unitTop view Side view Accessories in the indoor unit case AccessoriesEnglish-34 Unit mmOptional accessories Accessories in the outdoor unit caseTools required for installation General Tools Tools for test operationsEnglish-36 Fixing the installation plateFix the indoor unit If you fix the indoor unit on a wall If you fix the indoor unit on a window frameAssembling the hanger screw This QR code for detail video of indoor unit installationRemoving the screws English-37English-38 Assembling the Cover panel After mounting the indoor unitCable specification Connecting the assembly cableConnecting the cable English-39English-40 Each wire is labeled with the corresponding terminal numberClose the cover panel English-41 Cutting or extending the pipe Evacuating the indoor unitEnglish-42 Unscrew the caps at the end of each pipePut a flare nut slightly into the pipe and modify the flare English-43Depth a English-44 Drain hose installationEnglish-45 English-46 Evacuating the connected pipesConnect a drain hose to the drain plug Ensure that condensation draining is adequateEnglish-47 Adding RefrigerantOuter Torque If you use a pipe longer than 7.5 mPlease fill in with indelible ink English-48 the factory refrigerant charge of the product 1975English-49 Performing the gas leak testsEnsure the wall will be able to suspend the weight of rack Outdoor unit installed on the wall by rackFixing the outdoor unit in place English-50English-51 Smart Install mode Off / Blinking / On English-52English-53 Final check and trial operationEnglish-54 How to connect your extended power cablesApply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withEnglish-55 A3050 TVIB&IMDB68-04043A-01EN.indd 2014/8/15 Register your product at DB68-04043A-01 Air Conditioner