Quadra-Fire 31M-ACC-GT, 31ST-ACC, 31M-ACC-NT, 31M-ACC-MBK Components, Air Clearances, Instructions

Page 17

R

3100 Wood Stove Series (ACC)

Thimble

Site constructed for masonry chimney installation:

Components

A minimum length of 12 inches [305mm] (longer for thicker walls) of solid insulated factory-built chimney length constructed to UL 103 Type HT 8 inch (203mm) inside diameter. Chimney needs to extend a minimum of 2 inches (51mm) from the interior wall and a mini- mum of 1 inch (25mm) from the exterior wall.

Wall spacer, trim collar and wall band to fit solid pack chimney selected.

Minimum 8 inch (203mm) diameter clay liner section (if not already present in chimney) and refractory mortar.

Air Clearances

Masonry chimney clearance must meet NFPA 211 mini- mum requirement of 2 inches (51mm) to sheet metal supports and combustibles.

Minimum of 1 inch (25mm) clearance around the chim- ney connector.

Top of wall opening is a minimum of 13-1/2 inches (343mm) from ceiling or 4-1/2 inches (114mm) below minimum clearance specified by chimney connector manufacturer. NFPA 211 minimum vertical clearance of 18 inches (457mm) from chimney connector and ceil- ing or minimum recommended by chimney connector manufacturer. Figure 17.1.

Instructions:

1.Open inside wall at proper height for the chimney con- nector to entry the masonry chimney. Figure 17.1

2.Entry hole to masonry chimney must be lined with an 8 inch (203mm) minimum diameter clay liner, or equiva- lent, secured with refractory mortar.

3.Construct a 17 inch x 17 inch (432mm x 432mm) out- side dimension frame from 2 x 2 framing lumber to fit into wall opening. Inside opening of frame should be no less than 14 inch x 14 inch (356mm x 356mm).

Figure 17.1.

4.Attach the wall spacer to the chimney side of the frame.

5.Nail the frame into the wall opening. The spacer should be on the chimney side.

6.Insert the section of the solid insulated chimney into the outer wall of the masonry chimney.

 

 

 

C

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ceiling

 

13.5” below ceiling to top

 

 

 

 

 

 

 

Wall

of opening

 

 

 

or top of opening is a min.of

Minimum18.0”

4.5” below min.clearance

NFPA 211

specified by connector mfg.

1.5

2x2 framing stud

 

 

 

 

2.0

min air clearance

 

 

 

 

1.0

min air clearance

 

 

 

 

4.5

 

 

 

 

 

 

 

 

1.5”

 

2.0”

 

 

 

 

 

 

 

 

 

 

 

17.0” OD 14.0” ID

 

 

 

 

 

 

 

1.0”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.0”

 

 

 

 

C

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

1.0”

Center of Hole

 

 

 

1.5”

2.0”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thimble

 

 

 

 

 

 

 

 

Include depth of hearth pad

Figure 17.1

Solid Pack Chimney with Metal Supports as a Thimble

 

Fire Clay Flue

 

Liner

 

with Airspace

 

Masonry

Trim Collar

Chimney

Chimney Section

Wall Spacer

 

with 2 inch

Wall Band to

(51mm)

Secure Chimney

Clearance to

Section

Combustibles

 

Chimney

Wood Studs Used

Connector

for Framing - Spaced

 

 

2 inch (51mm)

clearance from

Masonry Chimney

Figure 17.2

7.

Tightly secure the length of the solid insulated chimney

 

WARNING

 

with the wall band to the masonry chimney.

 

 

 

 

 

 

Fire Risk.

8.

Insert a section of chimney connector into the chimney.

 

 

Make sure it does not protrude past the edge of the

 

Do NOT pack insulation or other combustibles between

 

 

spacers.

 

clay chimney liner inside the chimney.

 

 

 

 

 

• ALWAYS maintain specified clearances around vent-

9.

Seal the end of the chimney connector to the clay liner

 

ing and spacers.

 

with refractory mortar.

 

 

• Install spacers as specified.

 

 

 

Failure to keep insulation or other material away from

10. Install trim collar around the sold pack chimney section.

 

 

vent pipe may cause fire.

 

 

 

 

 

 

 

 

 

 

 

 

 

March 2, 2007

7033-277C

Page 17

Image 17
Contents Fire Risk Step Top Uni-Body Model Millennium ModelPedestal Model Shown Welcome to the Quadra-Fire Family Wood Stove Series ACCTable of Contents BTU & Efficiency Specifications Listing and Code ApprovalsAppliance Certification Mobile Home ApprovedService / Maintenance Tip Fire SafetyAsphyxiation Risk Any such action that may cause a fire hazard Fire RiskWood Stove Series ACC Negative Pressure Appliance needs to draft properly for safetyVenting Systems Wood Stove Series ACC Flue Draft ConsiderationsTools And Supplies Needed Inspect Appliance & Components and Pre-Use Check ListMasonry Chimney Wood Stove Series ACC Typical Stove SystemsMillennium Model 3Dimensions and ClearancesAppliance Dimensions 34-1/4 in mm 457mm 14-15/16 19-1/16 in.379mm 484mm 33-1/8 Double Wall Pipe Wood Stove Series ACC Clearances to Combustibles UL and ULCHearth Protection Requirements InstallationMillennium Model See FigureWood Stove Series ACC Step-Top Uni-Body Model Fire Risk Asphyxiation Risk Wood Stove Series ACC Outside Air Kit InstallationItems Needed for Installation not supplied Shock Risk Wood Stove Series ACC Blower OptionalVenting Components Chimney Systems 5Chimney RequirementsAir Clearances ComponentsInstructions Solid Pack Chimney with Metal Supports as a ThimbleChimney Height / Rise and Run Installing Chimney ComponentsSolid Pack Chimney with Metal Supports as a Thimble Cont’d Rule Wood Stove Series ACC Chimney Termination RequirementsPart SRV7033-041 for installation in a mobile Home Mobile Home InstallationBegin installing the ARS System 7Appliance Set UpStep Top model with a pedestal assembly you must attach Installing Pedestal AssemblyFinishing the ARS Installation Attach the 2 bottom screws of the mounting brackets to Installing Leg KitAdjusting The Blower Speed Control Wood Stove Series ACC Door Handle AssemblyBurning Process Operating InstructionsWood Selection & Storage Kindling or First StageAir Controls Automatic Combustion Control ACCBurn Rates and Operating Efficiency Wood Stove Series ACC Building a Fire Wood Stove Series ACC Blower Operating Instructions Initial cold start-up and all Burn SettingsOpacity Smoke OverfiringIssues Solutions Wood Stove Series ACC Frequently Asked QuestionsCreosote Chimney Cleaning General MaintenanceARS Operating and Cleaning Disposal of AshesGlass Cleaning Glass ReplacementCleaning Plated Surfaces Fire Risk Injury RiskBrick Size Qty Wood Stove Series ACC Firebrick ReplacementBaffle Wood Stove Series ACC Baffle Removal Snap Disc ReplacementReplacing Tube Channel Assembly Wood Stove Series ACC Tube Channel Assembly ReplacementRemoving Tube Channel Assembly Diagnostic Question Possible Causes of Condition Solutions TroubleshootingDon’t get enough/any heat. What can I do about it? Exploded view Reference MaterialsSizes Step Top Uni-Body Model Item # Accessories Wood Stove Series ACC Service Parts & AccessoriesItem # Service Parts Item # Service Parts Date of Service Performed By Description of Service Wood Stove Series ACC Service And Maintenance LogWood Stove Series ACC Homeowner’s Notes Wood Stove Series ACC Homeowner’s Notes Cont’d Wood Stove Series ACC Warranty Policy Lifetime WarrantyContact Information Wood Stove Series ACC