Samsung AQ09XAXSER, AQ07XAXSEU, AQ09XANSER, AQ07XANSEU Cutting/Extending the Piping, 35 mm 52 mm

Page 11

INSTALLING THE UNIT

Cutting/Extending the Piping

5 metres of piping is supplied with the air conditioner(Optional). This length can if necessary be:

ˇExtended to a maximum of 15metres

ˇShortened as required

If more than 5 metres of piping is required:

ˇ The assembly cable must also be extended

ˇ Refrigerant must be added to the circuit by an approved installer; otherwise, the indoor unit may freeze

1Make sure that you have the required tools available (pipe cutter, reamer, flaring tool and pipe holder).

2If you wish to shorten the piping, cut it using a pipe cutter, taking care to

ensure that the cut edge remains at a 90O angle with the side of the pipe, and referring to the illustrations below for examples of edges cut correctly and incorrectly.

90O

Oblique

Rough

Burr

O

x

x

x

3To prevent any gas from leaking out, remove all burrs at the cut end of the pipe, using a reamer.

4Slide a flare nut on to the pipe and modify the flare.

Outer Diameter (D)

Depth (A)

6.35 mm

1.3 mm

9.52 mm

1.8 mm

5Check that the flaring is correct, referring to the illustrations below for

examples of incorrect flaring.

x

x

x

x

Inclined

Damaged Surface

Cracked

Uneven Thickness

6Align the pipes to be connected and tighten the flare nuts first manually and then with a torque wrench, applying the following torque.

Outer Diameter

Torque (kgf•cm)

6.35 mm

140 ~ 170

9.52 mm

250~280

7For further details on how to connect up to the outdoor unit and purge the circuit, refer to page 12.

E-11

Image 11
Contents Installation Manual Safety Precautions Contents Indoor Unit Deciding on Where to Install the Air ConditionerMm minimum Accessories in the Outdoor Unit Case Air Conditioner and AccessoriesAccessories in the Indoor Unit Case Wall Window frame Fixing the Installation PlatePurging the Unit Then follow StepsConnecting the Assembly Cable Installing and Connecting the Outdoor Unit Drain Hose Installing and Connecting the Indoor Unit Drain HoseTorque kgf cm Installing and Connecting the Indoor Unit Assembly Piping35 mm 52 mm Cutting/Extending the PipingOuter Diameter Torque kgfcm Connecting Up and Purging the CircuitPlacing the Indoor Unit in Position To check for gas leaks on Then, using a leak detector CheckPerforming Leak Tests Fixing the Outdoor Unit in Position Checking and Testing OperationsExplaining Operations to the Owner Electronics ÊìäéÇéÑëíÇé èé ìëíÄçéÇäÖ ÅÂ˚ è‰ÓÒÚÓÓÊÌÓÒÚË ËÓ‰ÂʇÌË ÄÓÏ̇ÚÌ˚È ·ÎÓÍ ˚·Ó ÏÂÒÚ‡ ‰Îfl ÛÒÚ‡ÌÓ‚ÍË ÍÓ̉ˈËÓÌÂ‡300 ÏÏ ËÎË ·ÓΠ125 ÏÏ ËÎË ·ÓΠË̇‰ÎÂÊÌÓÒÚË, ÛÔ‡ÍÓ‚‡ÌÌ˚ ‚ ÍÓÓ·ÍÛ ÍÓÏ̇ÚÌÓ„Ó ·ÎÓ͇ ÄÓ̉ˈËÓÌÂ Ë ÔË̇‰ÎÂÊÌÓÒÚË Í Ìâïû‰‡ÎÂÌË „‡Á‡ ËÁ ·ÎÓ͇ ÅÓÌÚ‡Ê ÛÒÚ‡ÌÓ‚Ó˜ÌÓÈ Ô·ÒÚËÌ˚‡‡ÍÚÂËÒÚËÍË Í‡·ÂÎfl ÔËÚ‡ÌËfl ÈÓ‰Íβ˜ÂÌË ÒÓ‰ËÌËÚÂθÌÓ„Ó Í‡·ÂÎflÌÒÚ‡Ìӂ͇ Ë èÓ‰ÒÓ‰ËÌÂÌË ÑÂ̇ÊÌÓ„Ó ò·̄‡ äÓÏ̇ÚÌÓ„Ó ÅÎÓ͇ ÅÓÌÚ‡Ê Ë ÔÓ‰ÒÓ‰ËÌÂÌË ‰Â̇ÊÌÓ„Ó ¯Î‡Ì„‡ Í ÍÓÏ̇ÚÌÓÏÛ ·ÎÓÍÛÂʸÚ ËÁÎ˯ÍË ÔÂÌÓÂÁËÌÓ‚ÓÈ ËÁÓÎflˆËË ÅÓÌÚ‡Ê Ë ÔÓ‰ÒÓ‰ËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡ Í ÍÓÏ̇ÚÌÓÏÛ ·ÎÓÍÛ‰ÎËÌÂÌ ÊÂÁ͇ ÚÛ·ÓÍ/ ì‰ÎËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡Ïóïâìúó ÈÓ‰ÒÓ‰ËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡ Ë Û‰‡ÎÂÌË ËÁ ÌÂ„Ó ‚ÓÁ‰Ûı‡ÌÒÚ‡Ìӂ͇ ÍÓÏ̇ÚÌÓ„Ó ·ÎÓ͇ ‚ Ìûêìóï Ôóîóêâìëë Ó‚Â͇ ÓÚÒÛÚÒÚ‚Ëfl ÛÚ˜ÍË „‡Á‡Ó‚ÂÍË Ë ÔÓ·Ì˚È Ôûòí ‡ÍÂÔÎÂÌË ç‡ÛÊÌÓ„Ó ÅÎÓ͇ÀÌÒÚÛÍÚ‡Ê ÔÓθÁÓ‚‡ÚÂÎfl AQ07X*RIM27212 1/19/07 1121 AM