Samsung AQ07XAXSEU, AQ09XANSER Connecting Up and Purging the Circuit, Outer Diameter Torque kgfcm

Page 12

COMPLETING THE INSTALLATION

Connecting Up and Purging the Circuit

Outdoor unit

Indoor unit

A

Gas pipe side

C

B

Liquid pipe side

D

Vacuum Pump

*The designs and shape are subject to change according to the model.

Valve stem

Stem cap

A

(gas)

B

(liquid)

The outdoor unit is loaded with sufficient R22 refrigerant for 5 metres of piping. The air in the indoor unit and in the pipe must be purged.

If air remains in the refrigeration pipes, it will affect the compressor, reduce to cooling/heating capacity and could lead to a malfunction.

Refrigerant for air purging is not charged in the outdoor unit. Use Vacuum Pump as shown at the figure.

1Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.

2Referring to the illustration opposite, tighten the flare nut first manually and then with a torque wrench, applying the following torque.

Outer Diameter

Torque (kgf•cm)

6.35 mm

140~170

9.52 mm

250~280

3Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port as shown at the figure.

4Open the valve of the low pressure side of manifold gauge counterclockwise.

5Purge the air from the system using vacuum pump for about 10 minutes.

-Close the valve of the low pressure side of manifold gauge clockwise.

-Make sure that pressure gauge show -0.1MPa(-76cmHg) after about

-10minutes.

-This procedure is very important in order to avoid gas leak.

-Turn off the vacuum pump.

-Remove the hose of the low pressure side of manifold gauge.

6Set valve cork of both liquid side and gas side of packed valve to the open position.

7Mount the valve stem nuts and the service port cap to the valve, and tighten them at the torque of 183kgf•cm with a torque wrench.

8Check for gas leakage.

-At this time, especially check for gas leakage from the 3-way valve’s stem nuts, and from the service port cap.

Adding Refrigerant

Refrigerant must be added if the piping measures more than 5 metres in length. This operation can only be performed by a qualified refrigeration specialist.

 

If you have used...

Then...

 

 

 

 

More than 5 metres

'20'g of refrigerant R22

 

of piping

must be added for each

 

 

extra metre.

 

 

 

 

Less than 5 metres

The purge time is normal.

 

of piping

 

 

 

 

 

 

 

Refer to the Service Manual for more details on this operation.

E-12

Image 12
Contents Installation Manual Safety Precautions Contents Deciding on Where to Install the Air Conditioner Indoor UnitMm minimum Air Conditioner and Accessories Accessories in the Indoor Unit CaseAccessories in the Outdoor Unit Case Fixing the Installation Plate Purging the UnitThen follow Steps Wall Window frameConnecting the Assembly Cable Installing and Connecting the Indoor Unit Drain Hose Installing and Connecting the Outdoor Unit Drain HoseInstalling and Connecting the Indoor Unit Assembly Piping Torque kgf cmCutting/Extending the Piping 35 mm 52 mmConnecting Up and Purging the Circuit Outer Diameter Torque kgfcmTo check for gas leaks on Then, using a leak detector Check Performing Leak TestsPlacing the Indoor Unit in Position Checking and Testing Operations Fixing the Outdoor Unit in PositionExplaining Operations to the Owner Electronics ÊìäéÇéÑëíÇé èé ìëíÄçéÇäÖ ÅÂ˚ è‰ÓÒÚÓÓÊÌÓÒÚË ËÓ‰ÂʇÌË ˚·Ó ÏÂÒÚ‡ ‰Îfl ÛÒÚ‡ÌÓ‚ÍË ÍÓ̉ˈËÓÌÂ‡ ÄÓÏ̇ÚÌ˚È ·ÎÓÍ300 ÏÏ ËÎË ·ÓΠ125 ÏÏ ËÎË ·ÓΠÄÓ̉ˈËÓÌÂ Ë ÔË̇‰ÎÂÊÌÓÒÚË Í Ìâïû Ë̇‰ÎÂÊÌÓÒÚË, ÛÔ‡ÍÓ‚‡ÌÌ˚ ‚ ÍÓÓ·ÍÛ ÍÓÏ̇ÚÌÓ„Ó ·ÎÓ͇ÅÓÌÚ‡Ê ÛÒÚ‡ÌÓ‚Ó˜ÌÓÈ Ô·ÒÚËÌ˚ ‰‡ÎÂÌË „‡Á‡ ËÁ ·ÎÓ͇ÈÓ‰Íβ˜ÂÌË ÒÓ‰ËÌËÚÂθÌÓ„Ó Í‡·ÂÎfl ‡‡ÍÚÂËÒÚËÍË Í‡·ÂÎfl ÔËÚ‡ÌËflÅÓÌÚ‡Ê Ë ÔÓ‰ÒÓ‰ËÌÂÌË ‰Â̇ÊÌÓ„Ó ¯Î‡Ì„‡ Í ÍÓÏ̇ÚÌÓÏÛ ·ÎÓÍÛ ÌÒÚ‡Ìӂ͇ Ë èÓ‰ÒÓ‰ËÌÂÌË ÑÂ̇ÊÌÓ„Ó ò·̄‡ äÓÏ̇ÚÌÓ„Ó ÅÎÓ͇ÅÓÌÚ‡Ê Ë ÔÓ‰ÒÓ‰ËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡ Í ÍÓÏ̇ÚÌÓÏÛ ·ÎÓÍÛ ÂʸÚ ËÁÎ˯ÍË ÔÂÌÓÂÁËÌÓ‚ÓÈ ËÁÓÎflˆËËÊÂÁ͇ ÚÛ·ÓÍ/ ì‰ÎËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡ ‰ÎËÌÂÌÈÓ‰ÒÓ‰ËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡ Ë Û‰‡ÎÂÌË ËÁ ÌÂ„Ó ‚ÓÁ‰Ûı‡ ÏóïâìúóÓ‚Â͇ ÓÚÒÛÚÒÚ‚Ëfl ÛÚ˜ÍË „‡Á‡ ÌÒÚ‡Ìӂ͇ ÍÓÏ̇ÚÌÓ„Ó ·ÎÓ͇ ‚ Ìûêìóï Ôóîóêâìëë‡ÍÂÔÎÂÌË ç‡ÛÊÌÓ„Ó ÅÎÓ͇ Ó‚ÂÍË Ë ÔÓ·Ì˚È ÔûòíÀÌÒÚÛÍÚ‡Ê ÔÓθÁÓ‚‡ÚÂÎfl AQ07X*RIM27212 1/19/07 1121 AM