Samsung AQ09XANSER, AQ07XAXSEU manual Performing Leak Tests, Placing the Indoor Unit in Position

Page 13

COMPLETING THE INSTALLATION

Performing Leak Tests

Before completing the installation (insulation of the cables, hose and piping and fixing of the indoor unit to the installation plate), you must check that there are no gas leaks.

To check for gas leaks on the...

Then, using a leak detector,

 

check the...

 

 

Indoor unit

Flare nuts at the end of sections

 

C and D.

 

 

Outdoor unit

Valves on sections A and B.

 

 

C D

A

B

The designs and shape are subject to change according to the model.

Placing the Indoor Unit in Position

Once you have checked that there are no leaks in the system, you can insulate the piping, hose and cables and place the indoor unit on the installation plate.

1To avoid condensation problems, place heat-resistant polyethylene foam separately around each refrigerant pipe in the lower part of the indoor unit.

2Wrap the refrigerant pipes and the drain hose located at the rear of the indoor unit up in the absorbent pad.

Triply wind the pipes and hose to the end of the indoor unit with the absorbent pad (make intervals of 20mm).

3Wind insulating tape around the pipes, assembly cable and drain hose.

4Place the resulting bundle carefully in the lower part of the indoor unit, making sure that it does not jut out from the rear of the indoor unit.

5Hook the indoor unit on to the installation plate and move the unit to the right and left until you are sure that it is securely in place.

6Finish wrapping vinyl tape around the rest of the piping leading to the outdoor unit.

7Using clamps (optionally supplied), attach the piping to the wall wherever possible.

Installation plate

E-13

Image 13
Contents Installation Manual Safety Precautions Contents Indoor Unit Deciding on Where to Install the Air ConditionerMm minimum Accessories in the Indoor Unit Case Air Conditioner and AccessoriesAccessories in the Outdoor Unit Case Purging the Unit Fixing the Installation PlateThen follow Steps Wall Window frameConnecting the Assembly Cable Installing and Connecting the Outdoor Unit Drain Hose Installing and Connecting the Indoor Unit Drain HoseTorque kgf cm Installing and Connecting the Indoor Unit Assembly Piping35 mm 52 mm Cutting/Extending the PipingOuter Diameter Torque kgfcm Connecting Up and Purging the CircuitPerforming Leak Tests To check for gas leaks on Then, using a leak detector CheckPlacing the Indoor Unit in Position Fixing the Outdoor Unit in Position Checking and Testing OperationsExplaining Operations to the Owner Electronics ÊìäéÇéÑëíÇé èé ìëíÄçéÇäÖ ÅÂ˚ è‰ÓÒÚÓÓÊÌÓÒÚË ËÓ‰ÂʇÌË ÄÓÏ̇ÚÌ˚È ·ÎÓÍ ˚·Ó ÏÂÒÚ‡ ‰Îfl ÛÒÚ‡ÌÓ‚ÍË ÍÓ̉ˈËÓÌÂ‡300 ÏÏ ËÎË ·ÓΠ125 ÏÏ ËÎË ·ÓΠË̇‰ÎÂÊÌÓÒÚË, ÛÔ‡ÍÓ‚‡ÌÌ˚ ‚ ÍÓÓ·ÍÛ ÍÓÏ̇ÚÌÓ„Ó ·ÎÓ͇ ÄÓ̉ˈËÓÌÂ Ë ÔË̇‰ÎÂÊÌÓÒÚË Í Ìâïû‰‡ÎÂÌË „‡Á‡ ËÁ ·ÎÓ͇ ÅÓÌÚ‡Ê ÛÒÚ‡ÌÓ‚Ó˜ÌÓÈ Ô·ÒÚËÌ˚‡‡ÍÚÂËÒÚËÍË Í‡·ÂÎfl ÔËÚ‡ÌËfl ÈÓ‰Íβ˜ÂÌË ÒÓ‰ËÌËÚÂθÌÓ„Ó Í‡·ÂÎflÌÒÚ‡Ìӂ͇ Ë èÓ‰ÒÓ‰ËÌÂÌË ÑÂ̇ÊÌÓ„Ó ò·̄‡ äÓÏ̇ÚÌÓ„Ó ÅÎÓ͇ ÅÓÌÚ‡Ê Ë ÔÓ‰ÒÓ‰ËÌÂÌË ‰Â̇ÊÌÓ„Ó ¯Î‡Ì„‡ Í ÍÓÏ̇ÚÌÓÏÛ ·ÎÓÍÛÂʸÚ ËÁÎ˯ÍË ÔÂÌÓÂÁËÌÓ‚ÓÈ ËÁÓÎflˆËË ÅÓÌÚ‡Ê Ë ÔÓ‰ÒÓ‰ËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡ Í ÍÓÏ̇ÚÌÓÏÛ ·ÎÓÍÛ‰ÎËÌÂÌ ÊÂÁ͇ ÚÛ·ÓÍ/ ì‰ÎËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡Ïóïâìúó ÈÓ‰ÒÓ‰ËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡ Ë Û‰‡ÎÂÌË ËÁ ÌÂ„Ó ‚ÓÁ‰Ûı‡ÌÒÚ‡Ìӂ͇ ÍÓÏ̇ÚÌÓ„Ó ·ÎÓ͇ ‚ Ìûêìóï Ôóîóêâìëë Ó‚Â͇ ÓÚÒÛÚÒÚ‚Ëfl ÛÚ˜ÍË „‡Á‡Ó‚ÂÍË Ë ÔÓ·Ì˚È Ôûòí ‡ÍÂÔÎÂÌË ç‡ÛÊÌÓ„Ó ÅÎÓ͇ÀÌÒÚÛÍÚ‡Ê ÔÓθÁÓ‚‡ÚÂÎfl AQ07X*RIM27212 1/19/07 1121 AM
Related manuals
Manual 56 pages 14.38 Kb Manual 56 pages 38.01 Kb