Encore 1450
Encore NC Clearance Chart
For use with either 6” or 8” flue collar/chimney connection
| Unprotected Surfaces | Protected Surfaces | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Stove Clearance |
|
|
| ||
|
|
|
|
|
|
| |||
| Stove Installed | Stove | Stove Installed | Stove | |||||
| Parallel to Wall | in Corner | Parallel to Wall | in Corner | |||||
|
|
|
|
|
|
|
| ||
Top Exit, single wall con- | Side | Rear | Corners | Side |
| Rear | Corners | ||
nector without shields, | (A) 17” | (B) | 29” | (C) 28” | (D) 8”1,4 |
| (E) 15”1,4 | (F) 8”1,4 | |
vertical flue collar heat | (432 mm) | (737 mm) | (711 mm) | (203 mm) |
| (380 mm) | (203 mm) | ||
shield installed (except |
| ||||||||
|
|
|
|
|
|
|
|
| |
where noted) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Top Exit, | (G) 17” | (H) | 17” | (I) 19” | (J) 8”1 |
| (K) 11”1 | (L) 7”1 | |
chimney connector heat | (432 mm) | (432 mm) | (483 mm) | (203 mm) |
| (280 mm) | (178 mm) | ||
shields2, vertical flue col- |
|
|
|
|
|
|
|
|
|
lar h.s. installed |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Rear Exit | (M) 18” | (N) | 24”5 | N/A | (P) 8” |
| (Q) 6” Collar | N/A | |
(457 mm) | (610 mm) |
| (203 mm) |
| 11” (279 mm) |
|
| ||
|
|
|
|
| |||||
|
|
|
|
|
|
| 8” Collar |
|
|
|
|
|
|
|
|
| 19” (483 mm) |
|
|
|
|
|
|
|
|
|
|
| |
Top Exit, | (G) 18” | (H) 6” Collar | (I) 19” |
|
|
|
|
| |
chimney connector, | (457 mm) | 23” (584 mm) | (483 mm) |
|
| * |
|
| |
vertical flue collar heat |
| 8” Collar |
|
|
|
|
|
| |
shield installed |
| 17” (432 mm) |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
| Chimney Connector Clearance |
|
| ||||
|
|
|
|
|
|
|
| ||
21” (533 mm) |
|
| 7” (178 mm) |
|
| ||||
|
|
|
| ||||||
No chimney connector |
|
|
|
|
|
|
|
|
|
heat shields |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
9” | (229 mm) |
|
| 3” | (76 mm)3 |
|
| ||
Chimney connector heat |
|
|
|
|
|
|
|
|
|
shields installed |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
6” Connector | 8” Connector |
|
|
|
|
| |||
| 15” (381 mm) | 9” (229 mm) |
|
| * |
|
| ||
|
|
|
|
|
|
|
| ||
|
| Clearance to Combustibles in Front of Stove |
|
| |||||
|
|
|
|
|
|
|
|
| |
|
|
| All Installations | (S) 48” (1219 mm) |
|
| |||
|
|
|
|
|
|
|
|
|
|
* Clearances with
1.A ceiling heat shield, 24” (610 mm) in diameter and suspended 1” (25 mm) from the ceiling, must surround the chimney connec- tor in installations in which the chimney connector penetrates the ceiling.
2.The chimney connector shield extends only to 36” (914 mm) above the flue collar.
3.The ceiling heat shield required when the chimney connector shields are used should meet the wall protector. This will require trimming the ceiling shield along the line of intersection with the wall protector.
4.The vertical collar heat shield is not required when wall protection is installed according to this manual.
5.All rear exit installations require a wall shield when combustible material is within 12” (305 mm) of the center of the rear wall pass through. The shield must be 24” (610 mm) in diameter, be spaced 1” (25 mm) from the wall and must surround the chim- ney connector.