STANDING PILOT TROUBLESHOOTING

With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken.

1.Spark ignitor will not light pilot after repeated triggering of piezo ignitor button.

a.Defective ignitor (no spark electrode)

—Check for spark at electrode and pilot; if no spark and electrode wire is properly connected, replace ignitor.

b.No gas or low gas pressure.

—Check remote shut off valves from fireplace. Usually there is a valve near the main. There can be more than one

(1) valve between the fireplace and main.

—Low pressure can be caused by a variety of situations such as a bent line, too narrow diameter of pipe, or low line pressure. Consult with plumber or gas supplier.

c.No LP in tank.

—Check LP (propane) tank. Refill tank.

2.Pilot will not stay lit after carefully following lighting instructions.

a.Defective thermocouple.

—Check that pilot flame impinges on thermocouple. Clean and/or adjust pilot for maximum flame impingement. —Ensure the thermocouple connection at the gas valve is fully inserted and tight (hand tight plus 1/4 turn). Faulty thermocouple if reading is below specified minimum of 15 millivolts.

—Disconnect the thermocouple from the valve, place one millivolt meter lead wire on the end of the thermocouple and the other millivolt meter lead wire on the thermocouple copper wire. Start the pilot and hold the valve knob in. If the millivolt reading is less than 15 millivolt, replace the thermocouple.

b.Defective valve.

—If thermocouple is producing more than 15 millivolts, replace faulty valve.

3.Pilot burning, no gas to burner, valve knob “ON”, REMOTE/ OFF/ON switch “ON.”

a.REMOTE/OFF/ON switch, wall switch, remote control or wires defective.

—Check REMOTE/OFF/ON switch and wires for proper connections. Place jumper wires across terminal at switch. If burner comes on, replace defective switch. If OK, place jumper wires across switch wires at gas valve-if burner comes on, wires are faulty or connections are bad.

b.Thermopile may not be generating sufficient millivolts. —If the pilot flame is not close enough physically to the thermopile, adjust the pilot flame.

—Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket.

—Check the thermopile with a millivolt meter. Take the reading at TH-TP & TP terminals of the gas valve. The meter should read 350 millivolts minimum, while holding the valve knob depressed in the pilot position, with the pilot lit, and the REMOTE/OFF/ON switch in the OFF position.

Replace the faulty thermopile if the reading is below the specified minimum.

—With the pilot in the ON position, disconnect the thermopile leads from the valve. Take a reading at the thermopile leads. The reading should be 350 millivolts minimum. Replace the thermopile if the reading is below the minimum.

c.Defective valve.

—Turn valve knob to ON. Place REMOTE/OFF/ON switch to ON. Check with millivolt meter at thermopile terminals. Millivolt meter should read greater than 200 millivolts. If the reading is okay and the main burner does not ignite, replace the gas valve.

d.Plugged main burner orifice.

—Check main burner orifice for blockage and remove.

4.Frequent pilot outage problem.

a.Pilot flame may be too high or too low, or blowing (high), causing pilot safety to drop out.

—Cleanandadjustflameformaximumflameimpingementon the thermocouple. Follow lighting instructions carefully.

5.The pilot and main burner extinguish while in operation.

a.No LP (Propane) in tank.

Check LP (Propane) tank. Refill fuel tank.

b.Inner vent pipe leaking exhaust gases back into system —Check for leaks.

c.Glass too loose, gasket leaks in corners after usage. —Be certain glass assembly is installed correctly.

d.Horizontal vent improperly pitched.

—The horizontal vent cap should slope down only enough to prevent any water from entering the unit. The maximum downwards slope is 1/4 inch.

e.Bad thermopile or thermocouple. —Replace if necessary.

f.Improper vent cap installation.

—Check for proper installation and freedom from debris or blockage.

6.Glass soots.

a.Flame impingement on logs.

—Check and adjust log position. Contact Empire Comfort Systems, Inc.

b.Debris around throat of main burner.

—Inspect the opening at the base of the main burner. It is imperative that NO material be placed in this opening.

7.Flame burns blue and lifts off main burner.

a.Insufficient oxygen being supplied.

—Check to make sure vent cap is installed properly and free of debris. Make sure that vent system joints are tight and have no leaks.

—Check to make sure that no material has been placed at the main burner base.

Page 50

21759-6-0608

Image 50
Contents Remote RF Models Millivolt Standing PilotIntermittent Pilot UL File NO. MH30033Table of Contents Important Safety Information Some Points to Remember LP-GAS Warning OdorNo Odor Detected Odor Fade Requirements for Massachusetts Vent Directly BELOW. Keep Clear of ALL ObstructionsIntroduction Remote Control Options Description SpecificationsFireplace Dimensions DVP42 DVP48Clearances Figure ClearancesLocating Fireplace Combustible MaterialChecking Manifold Pressures Installing a New Main Gas CockGAS Supply Rear Vent Conversion Converting flue take-off to rear ventingVent Pipe Clearance InstallationFraming and Finishing Finishing Figures 12 Flush Mount Mantel Installation FigureFraming Figure Vent Runs Figures 14, 15, 16, 17 Flush Wall InstallationCombustible Surround Installation VERTICAL, 90 Elbow with Horizontal TerminationVERTICAL, 90 Elbow to Horizontal OUT the Wall ModelExample a Venting Fireplace TOPTo Use the Vent Graph Figure Example BBelow Grade Installation Typical Basement InstallationPositioning the Fireplace Cutting the Hole FiguresExamples TOP Vent RUN Venting Examples When Using DVA47 Adaptor Vertically Off Top of Fireplace OnlyInstallation Instructions DVVK-4FV Direct Vent Termination KITInstallation Note Items Required For Installation Tools Building SuppliesInstallation of the Vertical Flex Termination Kit Before You StartStep-By-Step Installation For Flex DV Kit Roof Pitch DIA. Flex AIR Intake Pipe 35 ft. Max Quantity Number Item Description Repair Part No SuppliedDimensions in Feet Venting Fireplace RearExamples Rear Vent RUN Parts Verification DVVK-4RE Vent KIT Installation InstructionsInstalling Wall Thimble/Firestop Assembly DVVK-4RE Vent KIT Installation Instructions Sealing 4 102mm Diameter Flue Outlet TubeParts List Connecting to Rigid Vent SystemInstallation DVVK-4F Flex Vent Instructions TOP Vent onlyInformation on Various Venting Routes and Components Vertical Sidewall InstallationsTermination Clearances Vent Clearances Vent System Identification Special Venting Components Simpson DuraventInstalling Vent Components Figure DVVK-5RPInstalling Support Brackets Figure Venting Framing and FinishingSee Horizontal Termination Page 41 and Vertical Termination Installing Firestops Figures 64, 65, 66 ⅝ Venting Framing and Finishing⅝ Venting Framing and Finishing Horizontal Termination Installation DVVK-5F Flex Vent InstructionsVertical Termination General MaintenanceSee Figure Installing the Vent System in a Chase Determining Minimum Vent Height Above the RoofReassembly and Resealing Vent Pipe System Vertical TerminationLOG Placement 4 LOG SET Initial Lighting Operating InstructionsMillivolt System Pilot Flame FigureTRW Standing Pilot Wiring Diagram Lighting Instructions For Your SAFETY, Read Before LightingStanding Pilot Lighting Instructions To Turn OFF GAS to FireplacePilot and main burner extinguish while in operation Standing Pilot TroubleshootingFrequent pilot outage problem Glass sootsElectrical Connection Figure Intermittent Pilot Wiring DiagramIntermittent Pilot Operating Instructions Damage, personal injury or loss of life Intermittent Pilot Lighting InstructionsTo Turn OFF GAS to Appliance Checkout Intermittent Pilot TroubleshootingS8600H Intermittent Ignition Module Specifications OperationSafety Lockout Main Burner OperationIgnition System Checks Check ignition cable. Make sure ARC Length ActionIntermittent Pilot Troubleshooting Green LED Status Codes RF Standing Pilot Operating Instructions RF Transmitter Functions Status ActionWiring Diagram with Blower RF Wiring DiagramWhat to do if YOU Smell GAS For Your Safety Read Before LightingRF Standing Pilot Lighting Instructions Maintenance and Service Parts View Parts List Index Part Number Description DVP42 DVP48Parts List Blower Wheels FBB4 Optional Variable Speed Blower InstallationBlower Motor Volt AC Junction BOX Wiring Installation Instructions Optional Brick Liner Installation InstructionsAccessories FBB4Service Notes HOW to Order Repair Parts Service Notes

DVP42FP, P)-2 specifications

Empire Comfort Systems has established itself as a leader in the heating and venting industry, providing innovative solutions that cater to modern home heating needs. One of their standout products is the Empire Comfort Systems DVP42FP,P)-2, a direct vent gas fireplace that seamlessly combines aesthetics, efficiency, and technology.

At the heart of the DVP42FP,P)-2 is its contemporary design, which enhances the ambiance of any living space. With a sleek glass front and a range of stylish finishes, this fireplace serves as a perfect centerpiece, embodying both function and fashion. The generous viewing area allows for an unobstructed view of the mesmerizing flames, creating a cozy atmosphere in any room.

This fireplace is engineered for efficiency and performance. With an impressive heating output, the DVP42FP,P)-2 can effectively warm spaces while consuming minimal fuel. It boasts a high-efficiency rating, ensuring that homeowners can enjoy the warmth without incurring high energy costs. The direct vent technology allows for a sealed combustion system that draws air from outside while expelling exhaust gases directly outdoors. This ensures that the air quality inside the home is maintained while providing optimal heating performance.

Ease of use is another hallmark of the DVP42FP,P)-2. It features an intuitive remote control system, allowing users to adjust the temperature and flame settings conveniently from anywhere in the room. This level of user-friendly control enhances the overall experience, making it easy to create the perfect environment.

Another notable characteristic of this model is its safety features. Equipped with safety screens and an auto shut-off feature, the DVP42FP,P)-2 is designed to offer peace of mind, allowing families to enjoy their fireplace without worries about safety.

Maintenance is straightforward with the DVP42FP,P)-2, thanks to its accessible design. Regular upkeep is minimal, allowing homeowners to spend more time enjoying the warmth and beauty of their fireplace rather than worrying about system maintenance.

In conclusion, the Empire Comfort Systems DVP42FP,P)-2 is a captivating, efficient, and technologically advanced direct vent gas fireplace. With its modern design, high efficiency, user-friendly controls, and robust safety features, it represents a wise investment for anyone looking to enhance their home's comfort and aesthetic appeal. Whether for a new build or a renovation, this fireplace stands out as a premier choice for discerning homeowners.