Before connecting the thermostat, check to make sure the wires will be long enough for servicing at a later date. Make sure that thermostat wire is long enough to facilitate future removal of blower for service.

Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wiring diagram shown in figure 32. Use 18−gauge wire or larger that is suit- able for Class II rating for thermostat connections.

Electrically ground the unit according to local codes or, in the absence of local codes, according to the current Na- tional Electric Code (ANSI/NFPA No. 70). A green ground wire is provided in the field make−up box.

NOTE − The EL280UH furnace contains electronic compo- nents that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.

Accessory Terminals

One line voltage ade terminal is provided on

the furnace integrated control. See figure 33 for integrated control configuration. This terminal is energized when the indoor blower is operating. Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an exter- nal relay.

One line voltage ade terminal is provided on

the furnace integrated control. See figure 33 for integrated control configuration. This terminal is energized in the heating mode when the combustion air inducer is operat- ing. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con- nected to one of the provided neutral terminals. If a humidi- fier rated at greater than one amp is connected to this termi- nal, it is necessary to use an external relay relay.

Generator Use − Voltage Requirements

The following requirements must be kept in mind when specifying a generator for use with this equipment:

SThe furnace requires 120 volts + 10% (Range: 108 volts to 132 volts).

SThe furnace operates at 60 Hz + 5% (Range: 57 Hz to 63 Hz).

SThe furnace integrated control requires both polarity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or temporary power.

SGenerator should have a wave form distortion of less than 5% total harmonic distortion (THD).

Thermostat

Install the room thermostat according to the instructions provided with the thermostat. See table 10 for thermostat designations. If the furnace is being matched with a heat pump, refer to the FM21 installation instruction or appropri- ate dual fuel thermostat instructions.

Indoor Blower Speeds

1 − When the thermostat is set to AN ON," the indoor blower will run continuously on the low speed when there is no cooling or heating demand.

2 − When the EL280UH is operating in the high−fire or low− fire heating mode, the indoor blower will run on the cor- responding heating speed.

3 − When the EL280UH is operating in the low cool or the high cool cooling mode, the indoor blower will run on the corresponding cooling speed.

Page 26

Image 26
Contents Installation Instructions EL280UH Table of ContentsUnit Dimensions − inches mm Supply AIR OpeningParts Arrangement Shipping and Packing List Safety InformationEL280UH Gas Furnace Use of Furnace as Construction Heater GeneralCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Setting Equipment Return Air Bracket Filters Duct SystemVenting Upflow PositionHorizontal Left Position Horizontal Right PositionVent Connection Upflow and Horizontal Position Common Venting Using Metal−Lined Masonry Chimney −1/2 To these instructions and the provided venting tables. If Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Gas Piping Leum gasesHorizontal Applications Possible Gas Piping Configurations Electrostatic Discharge ESD Interior MAKE−UP BOX InstallationElectrical Page Field Wiring Applications OFF EL280UH Schematic Wiring Diagram Typical EL280UH Field Wiring Diagram TWO−STAGE Integrated ControlIntegrated Control For Your Safety Read Before Lighting Unit Start−UpHigh Altitude Gas Pressure AdjustmentProper Combustion Manifold Pressure Settings at all Altitudes Other Unit Adjustments Heat FAN-OFF Time in SecondsHeating Sequence of Operation Blower Data Pressure Bottom and One Side Service Electrical SHOCK, Fire Or Explosion HazardEL280UH BURNER, Combustion AIR Inducer Assembly Heat Exchanger RemovalPage Planned Service Repair Parts ListLED Integrated Control Diagnostic CodesFlash Code Status / Error Description Troubleshooting Heating Sequence of Operation On NextHeating Sequence of Operation U1.40 microamps Or Heat Demand is SATISFIED. a Five Troubleshooting Cooling Sequence of Operation Cooling Sequence of OperationTroubleshooting Continuous Fan Sequence of Operation Continuous LOW Speed FAN Sequence of OperationStart−Up & Performance Check List Unit Operation Cooling ModeTemperature Rise Drain Line
Related manuals
Manual 7 pages 50.25 Kb

Elite Series Gas Furnace Upflow/Horizontal Air Discharge, EL280UH specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, providing innovative solutions for both residential and commercial environments. One of their notable products is the EL280UH, a high-efficiency gas furnace designed to offer optimal comfort while minimizing energy consumption.

The EL280UH operates with an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This efficiency rating means that 80% of the fuel consumed is converted into heat, making it a cost-effective option for homeowners looking to reduce their utility bills. The furnace’s design is tailored to deliver reliable warmth during the coldest months, ensuring a comfortable home environment.

A key feature of the EL280UH is its two-stage heating capability. This technology allows the furnace to operate at a lower heating output for less demanding conditions, which not only conserves energy but also helps maintain a more consistent temperature in the home. When the demand for heat increases, the furnace can seamlessly transition to its higher output setting, providing quick and effective heating when needed.

Additionally, the EL280UH is equipped with a durable cabinet that minimizes heat loss, enhancing overall performance. The design incorporates several sound-dampening features as well, which contributes to quieter operation, allowing homeowners to enjoy a serene indoor environment.

The furnace also includes an advanced control system that integrates easily with smart home technology. This feature enables users to monitor and adjust their heating settings from anywhere using a smartphone app, creating added convenience and control over home heating.

Safety is another paramount aspect of the EL280UH. It includes an integrated flame sensor and pressure switch, ensuring reliable operation while minimizing risks associated with furnace malfunctions. The design adheres to stringent safety standards, providing users with peace of mind.

In summary, the Lennox EL280UH furnace stands out for its high efficiency, advanced features, and commitment to user safety. Its two-stage heating capability, quiet operation, and smart home integration make it an excellent choice for homeowners looking to enhance their heating system while being energy-conscious. The EL280UH embodies Lennox's dedication to quality and innovation, ensuring that comfort and efficiency go hand in hand.