Lennox International Inc EL280UH installation instructions Return Air

Page 10

Return Air −− Upflow Applications

Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.

Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.

NOTE − 60C and 60D units that require air volumes over 1800 cfm (850 L/s) must have one of the following:

1 − Single side return air with transition to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. (Re- quired to maintain proper air velocity.) See figure 9.

2 − Single side return air with optional return airbase. See fig- ure 10.

3 − Bottom return air.

4 − Return air from both sides.

5 − Bottom and one side return air.

Refer to Engineering Handbook for additional information.

Single Side Return Air

(with transition and filter)

20” X 25” X 1”

(508mm X 635mm X 25mm)

Cleanable Filter

Return Air

Plenum

AIR FLOW

Transition

FIGURE 9

Optional Return Air Base

(Upflow Applications Only −− For use with A, B, C and D cabinets)

 

FURNACE

 

 

FRONT

 

 

 

IF BASE

3−1/4

 

 

IS USED

 

 

WITHOUT

(83)

 

INDOOR AIR

IAQ CABINET,

 

 

A SINGLE

 

 

 

RETURN AIR

 

 

 

PLENUM

 

AIR FLOW

 

MUST

 

 

COVER BOTH

 

 

 

 

 

 

UNIT AND

 

 

 

RETURN

 

 

 

AIR BASE

7−1/4

 

 

OPENINGS

(184)

14−1/2” (368) A Width (65W75)

OPTIONAL

 

 

17−1/2” (446) B Width (50W98)

RETURN AIR BASE

 

21”− (533) C Width (50W99)

24−1/2”− (622) D Width (51W00)

123 (584)

 

Overall

 

 

 

 

 

 

1 Minimum

(Maximum)

 

 

 

11 (279)

 

1 Unit side return air

2 Maximum

14 (356)

 

Opening

 

 

 

 

 

 

 

 

 

 

 

 

5−5/8

SIDE RETURN

 

 

AIR OPENINGS

 

 

(143)

 

 

 

(Either Side)

 

 

23

(584)

26−7/8

(683)

SIDE VIEW

122−7/16

(570)

Overall

(Maximum)

3/4

(19)

NOTE− Optional Side Return Air Filter Kits are not for use with Optional Return Air Base.

1Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.

Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.

Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air

opening. The size of the opening must not extend beyond the markings on the furnace cabinet.

2To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.

FIGURE 10

Page 10

Image 10
Contents Installation Instructions EL280UH Table of ContentsUnit Dimensions − inches mm Supply AIR OpeningParts Arrangement EL280UH Gas Furnace Safety InformationShipping and Packing List Use of Furnace as Construction Heater GeneralCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Setting Equipment Return Air Bracket Filters Duct SystemVenting Upflow PositionHorizontal Left Position Horizontal Right PositionVent Connection Upflow and Horizontal Position Common Venting Using Metal−Lined Masonry Chimney −1/2 To these instructions and the provided venting tables. If Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Gas Piping Leum gasesHorizontal Applications Possible Gas Piping Configurations Electrical Interior MAKE−UP BOX InstallationElectrostatic Discharge ESD Page Field Wiring Applications OFF EL280UH Schematic Wiring Diagram Typical EL280UH Field Wiring Diagram TWO−STAGE Integrated ControlIntegrated Control For Your Safety Read Before Lighting Unit Start−UpProper Combustion Gas Pressure AdjustmentHigh Altitude Manifold Pressure Settings at all Altitudes Other Unit Adjustments Heat FAN-OFF Time in SecondsHeating Sequence of Operation Blower Data Pressure Bottom and One Side Service Electrical SHOCK, Fire Or Explosion HazardEL280UH BURNER, Combustion AIR Inducer Assembly Heat Exchanger RemovalPage Planned Service Repair Parts ListFlash Code Status / Error Description Integrated Control Diagnostic CodesLED Troubleshooting Heating Sequence of Operation On NextHeating Sequence of Operation U1.40 microamps Or Heat Demand is SATISFIED. a Five Troubleshooting Cooling Sequence of Operation Cooling Sequence of OperationTroubleshooting Continuous Fan Sequence of Operation Continuous LOW Speed FAN Sequence of OperationStart−Up & Performance Check List Unit Operation Cooling ModeTemperature Rise Drain Line
Related manuals
Manual 7 pages 50.25 Kb

Elite Series Gas Furnace Upflow/Horizontal Air Discharge, EL280UH specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, providing innovative solutions for both residential and commercial environments. One of their notable products is the EL280UH, a high-efficiency gas furnace designed to offer optimal comfort while minimizing energy consumption.

The EL280UH operates with an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This efficiency rating means that 80% of the fuel consumed is converted into heat, making it a cost-effective option for homeowners looking to reduce their utility bills. The furnace’s design is tailored to deliver reliable warmth during the coldest months, ensuring a comfortable home environment.

A key feature of the EL280UH is its two-stage heating capability. This technology allows the furnace to operate at a lower heating output for less demanding conditions, which not only conserves energy but also helps maintain a more consistent temperature in the home. When the demand for heat increases, the furnace can seamlessly transition to its higher output setting, providing quick and effective heating when needed.

Additionally, the EL280UH is equipped with a durable cabinet that minimizes heat loss, enhancing overall performance. The design incorporates several sound-dampening features as well, which contributes to quieter operation, allowing homeowners to enjoy a serene indoor environment.

The furnace also includes an advanced control system that integrates easily with smart home technology. This feature enables users to monitor and adjust their heating settings from anywhere using a smartphone app, creating added convenience and control over home heating.

Safety is another paramount aspect of the EL280UH. It includes an integrated flame sensor and pressure switch, ensuring reliable operation while minimizing risks associated with furnace malfunctions. The design adheres to stringent safety standards, providing users with peace of mind.

In summary, the Lennox EL280UH furnace stands out for its high efficiency, advanced features, and commitment to user safety. Its two-stage heating capability, quiet operation, and smart home integration make it an excellent choice for homeowners looking to enhance their heating system while being energy-conscious. The EL280UH embodies Lennox's dedication to quality and innovation, ensuring that comfort and efficiency go hand in hand.