Lennox International Inc Elite Series Gas Furnace Upflow/Horizontal Air Discharge, EL280UH

Page 15

The EL280UH series units are classified as fan−assisted Category I furnaces when vertically vented according to the latest edition of National Fuel Gas Code (NFPA 54 / ANSI Z223.1) in the USA. A fan−assisted Category I fur- nace is an appliance equipped with an integral mechanical means to either draw or force combustion products through the combustion chamber and/or heat exchanger. The EL280UH is not approved for use with horizontal venting. NOTE − Use these instructions as a guide. They do not su- persede local codes. This furnace must be vented accord- ing to all local codes these installation instructions, and the provided venting tables in these instructions

The venting tables in this manual were extracted from the National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are provided as a guide for proper vent installation. Proper ap- plication, termination, construction and location of vents must conform to local codes having jurisdiction. In the ab- sence of local codes, the NFGC serves as the defining doc- ument.

Refer to the tables and the venting information contained in these instructions to properly size and install the venting system.

Use self−drilling sheet metal screws or a mechanical fas- tener to firmly secure the vent pipe to the round collar of the flue transition. If self−drilling screws are used to attach the vent pipe, it is recommended that three be used. Drive one self−drilling screw through the front and one through each side of the vent pipe and collar. See figure 23.

Install the first vent connector elbow at a minimum of six inches (152 mm) from the furnace vent outlet. See figure 23.

Venting Using a Masonry Chimney

The following additional requirements apply when a lined masonry chimney is used to vent this furnace.

Masonry chimneys used to vent Category I central fur- naces must be either tile-lined or lined with a listed metal lining system or dedicated gas vent. Unlined masonry chimneys are prohibited. See figures 24 and 25 for com- mon venting.

A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney.

An exterior masonry chimney that is not tile−lined must be lined with B1 vent or a listed insulated flexible metal vent. An exterior tile−lined chimney that is sealed and capped may be lined with a listed uninsulated flexible metal vent.

If the existing chimney will not accommodate a listed metal liner, either the chimney must be rebuilt to accommodate one of these liners or an alternate approved venting meth- od must be found.

Insulation for the flexible vent pipe must be an encapsu- lated fiberglass sleeve recommended by the flexible vent pipe manufacturer. See figure 24.

IMPORTANT

Once the venting system is installed, attach the connected Vent" warning sticker to a visible area of the plenum near the vent pipe. See figure 23. The warning sticker is provided in the bag assembly. Or- der kit 66W04 for additional stickers.

WARNING

Asphyxiation hazard. The exhaust vent for this fur- nace must be securely connected to the furnace flue transition at all times.

 

VENT CONNECTION UPFLOW AND HORIZONTAL POSITION

 

 

“DISCONNECTED VENT”

 

 

WARNING

 

 

STICKER

 

 

OPTIONAL SIDE

 

VENT PIPE

VENTING

 

(min. 6" length)

 

(min. 6" length)

 

“DISCONNECTED VENT”

 

 

 

 

WARNING

 

 

STICKER

 

FLUE TRANSITION

 

 

COLLAR

 

 

 

 

FLUE

 

VENT PIPE

TRANSITION

 

COLLAR

 

(min. 6" length)

FIGURE 23

Page 15

Image 15
Contents Table of Contents Installation Instructions EL280UHSupply AIR Opening Unit Dimensions − inches mmParts Arrangement Safety Information EL280UH Gas FurnaceShipping and Packing List General Use of Furnace as Construction HeaterCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Setting Equipment Return Air Bracket Duct System FiltersUpflow Position VentingHorizontal Right Position Horizontal Left PositionVent Connection Upflow and Horizontal Position Common Venting Using Metal−Lined Masonry Chimney −1/2 To these instructions and the provided venting tables. If Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Leum gases Gas PipingHorizontal Applications Possible Gas Piping Configurations Interior MAKE−UP BOX Installation ElectricalElectrostatic Discharge ESD Page Field Wiring Applications OFF EL280UH Schematic Wiring Diagram TWO−STAGE Integrated Control Typical EL280UH Field Wiring DiagramIntegrated Control Unit Start−Up For Your Safety Read Before LightingGas Pressure Adjustment Proper CombustionHigh Altitude Manifold Pressure Settings at all Altitudes Heat FAN-OFF Time in Seconds Other Unit AdjustmentsHeating Sequence of Operation Blower Data Pressure Bottom and One Side Electrical SHOCK, Fire Or Explosion Hazard ServiceHeat Exchanger Removal EL280UH BURNER, Combustion AIR Inducer AssemblyPage Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Flash Code Status / Error DescriptionLED On Next Troubleshooting Heating Sequence of OperationHeating Sequence of Operation U1.40 microamps Or Heat Demand is SATISFIED. a Five Cooling Sequence of Operation Troubleshooting Cooling Sequence of OperationContinuous LOW Speed FAN Sequence of Operation Troubleshooting Continuous Fan Sequence of OperationStart−Up & Performance Check List Drain Line Cooling ModeTemperature Rise Unit Operation
Related manuals
Manual 7 pages 50.25 Kb

Elite Series Gas Furnace Upflow/Horizontal Air Discharge, EL280UH specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, providing innovative solutions for both residential and commercial environments. One of their notable products is the EL280UH, a high-efficiency gas furnace designed to offer optimal comfort while minimizing energy consumption.

The EL280UH operates with an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This efficiency rating means that 80% of the fuel consumed is converted into heat, making it a cost-effective option for homeowners looking to reduce their utility bills. The furnace’s design is tailored to deliver reliable warmth during the coldest months, ensuring a comfortable home environment.

A key feature of the EL280UH is its two-stage heating capability. This technology allows the furnace to operate at a lower heating output for less demanding conditions, which not only conserves energy but also helps maintain a more consistent temperature in the home. When the demand for heat increases, the furnace can seamlessly transition to its higher output setting, providing quick and effective heating when needed.

Additionally, the EL280UH is equipped with a durable cabinet that minimizes heat loss, enhancing overall performance. The design incorporates several sound-dampening features as well, which contributes to quieter operation, allowing homeowners to enjoy a serene indoor environment.

The furnace also includes an advanced control system that integrates easily with smart home technology. This feature enables users to monitor and adjust their heating settings from anywhere using a smartphone app, creating added convenience and control over home heating.

Safety is another paramount aspect of the EL280UH. It includes an integrated flame sensor and pressure switch, ensuring reliable operation while minimizing risks associated with furnace malfunctions. The design adheres to stringent safety standards, providing users with peace of mind.

In summary, the Lennox EL280UH furnace stands out for its high efficiency, advanced features, and commitment to user safety. Its two-stage heating capability, quiet operation, and smart home integration make it an excellent choice for homeowners looking to enhance their heating system while being energy-conscious. The EL280UH embodies Lennox's dedication to quality and innovation, ensuring that comfort and efficiency go hand in hand.