Unconfined Space

An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com- bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be un- confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.

Confined Space

A confined space is an area with a volume less than 50 cu- bic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.

When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space contain- ing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.

EQUIPMENT IN CONFINED

SPACE ALL AIR FROM INSIDE

CHIMNEY

OR GAS

VENT

 

WATER

FURNACE

HEATER

 

OPENINGS

 

(To Adjacent

 

Room)

NOTE − Each opening shall have a free area of at least one square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of the total input rat- ing of all equipment in the enclosure, but not less than 100 square inches (64516 mm2).

FIGURE 3

Air from Inside

If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305

mm)of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 3.

Air from Outside

If air from outside is brought in for combustion and ventila- tion, the confined space must have two permanent open- ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305

mm)of the bottom. These openings must communicate di- rectly or by ducts with the outdoors or spaces (crawl or at- tic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment in the en- closure. See figures 4 and 5. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See figure 6.

When ducts are used, they shall be of the same cross−sec- tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective cov- ering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per- cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.

Page 7

Image 7
Contents Table of Contents Installation Instructions EL280UHSupply AIR Opening Unit Dimensions − inches mmParts Arrangement EL280UH Gas Furnace Safety InformationShipping and Packing List General Use of Furnace as Construction HeaterCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Setting Equipment Return Air Bracket Duct System FiltersUpflow Position VentingHorizontal Right Position Horizontal Left PositionVent Connection Upflow and Horizontal Position Common Venting Using Metal−Lined Masonry Chimney −1/2 To these instructions and the provided venting tables. If Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Leum gases Gas PipingHorizontal Applications Possible Gas Piping Configurations Electrical Interior MAKE−UP BOX InstallationElectrostatic Discharge ESD Page Field Wiring Applications OFF EL280UH Schematic Wiring Diagram TWO−STAGE Integrated Control Typical EL280UH Field Wiring DiagramIntegrated Control Unit Start−Up For Your Safety Read Before LightingProper Combustion Gas Pressure AdjustmentHigh Altitude Manifold Pressure Settings at all Altitudes Heat FAN-OFF Time in Seconds Other Unit AdjustmentsHeating Sequence of Operation Blower Data Pressure Bottom and One Side Electrical SHOCK, Fire Or Explosion Hazard ServiceHeat Exchanger Removal EL280UH BURNER, Combustion AIR Inducer AssemblyPage Repair Parts List Planned ServiceFlash Code Status / Error Description Integrated Control Diagnostic CodesLED On Next Troubleshooting Heating Sequence of OperationHeating Sequence of Operation U1.40 microamps Or Heat Demand is SATISFIED. a Five Cooling Sequence of Operation Troubleshooting Cooling Sequence of OperationContinuous LOW Speed FAN Sequence of Operation Troubleshooting Continuous Fan Sequence of OperationStart−Up & Performance Check List Drain Line Cooling ModeTemperature Rise Unit Operation
Related manuals
Manual 7 pages 50.25 Kb

Elite Series Gas Furnace Upflow/Horizontal Air Discharge, EL280UH specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, providing innovative solutions for both residential and commercial environments. One of their notable products is the EL280UH, a high-efficiency gas furnace designed to offer optimal comfort while minimizing energy consumption.

The EL280UH operates with an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This efficiency rating means that 80% of the fuel consumed is converted into heat, making it a cost-effective option for homeowners looking to reduce their utility bills. The furnace’s design is tailored to deliver reliable warmth during the coldest months, ensuring a comfortable home environment.

A key feature of the EL280UH is its two-stage heating capability. This technology allows the furnace to operate at a lower heating output for less demanding conditions, which not only conserves energy but also helps maintain a more consistent temperature in the home. When the demand for heat increases, the furnace can seamlessly transition to its higher output setting, providing quick and effective heating when needed.

Additionally, the EL280UH is equipped with a durable cabinet that minimizes heat loss, enhancing overall performance. The design incorporates several sound-dampening features as well, which contributes to quieter operation, allowing homeowners to enjoy a serene indoor environment.

The furnace also includes an advanced control system that integrates easily with smart home technology. This feature enables users to monitor and adjust their heating settings from anywhere using a smartphone app, creating added convenience and control over home heating.

Safety is another paramount aspect of the EL280UH. It includes an integrated flame sensor and pressure switch, ensuring reliable operation while minimizing risks associated with furnace malfunctions. The design adheres to stringent safety standards, providing users with peace of mind.

In summary, the Lennox EL280UH furnace stands out for its high efficiency, advanced features, and commitment to user safety. Its two-stage heating capability, quiet operation, and smart home integration make it an excellent choice for homeowners looking to enhance their heating system while being energy-conscious. The EL280UH embodies Lennox's dedication to quality and innovation, ensuring that comfort and efficiency go hand in hand.