Other Unit Adjustments

Primary and Secondary Limits

The primary limit is located on the heating compartment vestibule panel. The secondary limits (if equipped) are lo- cated in the blower compartment, attached to the back side of the blower. These auto reset limits are factory−set and re- quire no adjustment.

Flame Rollout Switches

This manually reset switches are located on the baffle plate in the burner assembly.

Pressure Switch

The pressure switch is located in the heating compartment adjacent to the combustion air inducer. The switch checks for proper combustion air inducer operation before allow- ing ignition trial. The switch is factory−set and requires no adjustment.

Temperature Rise

After the furnace has been started, and supply and return air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature. Decrease the blower speed to increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation.

Fan Control

The fan−on time of 30 seconds is not adjustable. The heat fan−off delay (amount of time that the blower operates after the heat demand has been satisfied) may be adjusted by changing DIP switches 3 and 4. See figure 35 and table 11. The unit is shipped with a factory fan−off delay setting of 90 seconds. The fan−off delay affects comfort and is adjust- able to satisfy individual applications. Adjust the fan−off delay to achieve a supply air temperature between 90° and 110°F at the moment that the blower is de−energized. Lon- ger off delay settings provide lower return air temperatures; shorter settings provide higher return air temperatures.

Thermostat Heat Anticipation

Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.

NOTE − Do not secure the electrical conduit directly to the air ducts or structure.

HEAT FAN-OFF TIME IN SECONDS

60sec.90sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

4

5

 

 

1

2

 

3

 

4

 

5

 

 

 

120sec.

 

 

 

 

 

 

 

180sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

4

5

 

 

1

2

 

3

 

4

 

5

 

To adjust fan−off timing, flip dip switch to desired setting.

FIGURE 35

Electrical

1 − Check all wiring for loose connections.

2 − Check for the correct voltage at the furnace (furnace operating). Correct voltage is 120VAC + 10%.

3 − Check amp−draw on the blower motor with inner blow- er panel in place.

Unit Nameplate__________Actual__________

Blower Speeds

Follow the steps below to change the blower speeds. 1 − Turn off electrical power to furnace.

2 − Remove blower access panel.

3 − Disconnect existing speed tap at integrated control speed terminal.

NOTE − Termination of any unused motor leads must be insulated.

4 − Place unused blower speed tap on integrated control PARK" terminal or insulate.

5 − Refer to blower speed selection chart on unit wiring dia- gram for desired heating or cooling speed. See Blower performance data beginning on the next page.

6 − Connect selected speed tap at integrated control speed terminal.

7 − Resecure blower access panel.

8 − Turn on electrical power to furnace.

9 − Recheck temperature rise. Electronic Ignition

The integrated control has an added feature of an internal Watchguard control. The feature serves as an automatic re- set device for integrated control lockout caused by ignition failure. This type of lockout is usually due to low gas line pressure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the inte- grated control to begin the ignition sequence.

Page 35

Image 35
Contents Table of Contents Installation Instructions EL280UHSupply AIR Opening Unit Dimensions − inches mmParts Arrangement Shipping and Packing List Safety InformationEL280UH Gas Furnace General Use of Furnace as Construction HeaterCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Setting Equipment Return Air Bracket Duct System FiltersUpflow Position VentingHorizontal Right Position Horizontal Left PositionVent Connection Upflow and Horizontal Position Common Venting Using Metal−Lined Masonry Chimney −1/2 To these instructions and the provided venting tables. If Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Leum gases Gas PipingHorizontal Applications Possible Gas Piping Configurations Electrostatic Discharge ESD Interior MAKE−UP BOX InstallationElectrical Page Field Wiring Applications OFF EL280UH Schematic Wiring Diagram TWO−STAGE Integrated Control Typical EL280UH Field Wiring DiagramIntegrated Control Unit Start−Up For Your Safety Read Before LightingHigh Altitude Gas Pressure AdjustmentProper Combustion Manifold Pressure Settings at all Altitudes Heat FAN-OFF Time in Seconds Other Unit AdjustmentsHeating Sequence of Operation Blower Data Pressure Bottom and One Side Electrical SHOCK, Fire Or Explosion Hazard ServiceHeat Exchanger Removal EL280UH BURNER, Combustion AIR Inducer AssemblyPage Repair Parts List Planned ServiceLED Integrated Control Diagnostic CodesFlash Code Status / Error Description On Next Troubleshooting Heating Sequence of OperationHeating Sequence of Operation U1.40 microamps Or Heat Demand is SATISFIED. a Five Cooling Sequence of Operation Troubleshooting Cooling Sequence of OperationContinuous LOW Speed FAN Sequence of Operation Troubleshooting Continuous Fan Sequence of OperationStart−Up & Performance Check List Drain Line Cooling ModeTemperature Rise Unit Operation
Related manuals
Manual 7 pages 50.25 Kb

Elite Series Gas Furnace Upflow/Horizontal Air Discharge, EL280UH specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, providing innovative solutions for both residential and commercial environments. One of their notable products is the EL280UH, a high-efficiency gas furnace designed to offer optimal comfort while minimizing energy consumption.

The EL280UH operates with an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This efficiency rating means that 80% of the fuel consumed is converted into heat, making it a cost-effective option for homeowners looking to reduce their utility bills. The furnace’s design is tailored to deliver reliable warmth during the coldest months, ensuring a comfortable home environment.

A key feature of the EL280UH is its two-stage heating capability. This technology allows the furnace to operate at a lower heating output for less demanding conditions, which not only conserves energy but also helps maintain a more consistent temperature in the home. When the demand for heat increases, the furnace can seamlessly transition to its higher output setting, providing quick and effective heating when needed.

Additionally, the EL280UH is equipped with a durable cabinet that minimizes heat loss, enhancing overall performance. The design incorporates several sound-dampening features as well, which contributes to quieter operation, allowing homeowners to enjoy a serene indoor environment.

The furnace also includes an advanced control system that integrates easily with smart home technology. This feature enables users to monitor and adjust their heating settings from anywhere using a smartphone app, creating added convenience and control over home heating.

Safety is another paramount aspect of the EL280UH. It includes an integrated flame sensor and pressure switch, ensuring reliable operation while minimizing risks associated with furnace malfunctions. The design adheres to stringent safety standards, providing users with peace of mind.

In summary, the Lennox EL280UH furnace stands out for its high efficiency, advanced features, and commitment to user safety. Its two-stage heating capability, quiet operation, and smart home integration make it an excellent choice for homeowners looking to enhance their heating system while being energy-conscious. The EL280UH embodies Lennox's dedication to quality and innovation, ensuring that comfort and efficiency go hand in hand.