Louisville Tin and Stove CF654C-R Trouble Shooting Chart for qualified serviceman Main Burner

Page 18

TROUBLE SHOOTING CHART for qualified serviceman - MAIN BURNER

SYMPTOM

POSSIBLE CAUSES

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

Flame too large

1.

Defective operator section of gas valve.

1.

Replace complete valve.

 

 

2.

Burner orifice too large.

2.

Check with local gas company for proper

 

 

 

 

 

orifice size and replace.

 

 

3.

If installed above 2,000 ft.

3.

Refer to orifice chart on Page 9.

 

Noisy Flame

1.

Noisy pilot.

1.

Reduce pilot gas with adjusting screw on combination

 

 

 

 

 

gas control valve.

 

 

2.

Burr in orifice (if it whistles or resonates).

2.

Remove burr or replace orifice (do not enlarge orifices)

.

 

3.

Excessive gas input.

3.

See “Flame Too Large” above.

 

Yellow tip flame (some

1.

Clogged main burner ports.

1.

Clean main burner ports. (Do not enlarge ports).

 

yellow tipping on LP

2.

Clogged draft hood.

2.

Clean draft hood.

 

gas is permissible

3.

Linted up mixer opening.

3.

Check for dust or lint at air mixer opening.

 

Floating Flame

1.

Blocked venting.

1.

Clean flue passageways to remove blockage.

 

Gas Odor

1.

Gas leak.

1.

Shut off gas service immediately. Check piping.

 

 

 

 

 

Call gas company. See “For Your Safety”, Page 1.

 

 

2.

Chimney or flue obstruction.

2.

Clean flue.

 

 

3.

Drafts around appliance.

3.

Eliminate drafts.

 

Delayed Ignition

1.

Pilot flame too small.

1.

Check pilot orifice. Increase pilot gas flow if

 

 

 

 

 

necessary by adjusting inlet pressure from gas

 

 

 

 

 

source (meter if natural gas or second stage

 

 

 

 

 

regulator if propane - maximum 7” w.c. for

 

 

 

 

 

Natural and 11” w.c. for propane).

 

 

2.

Burner ports clogged near pilot.

2.

Clean burner ports (do not enlarge ports).

 

 

3.

Low gas pressure.

3.

Check gas supply inlet pressure. Check gas outlet

 

 

 

 

 

(manifold) pressure for “minimum step” pressure

 

 

 

 

 

(for “step” pressure chart see “Operation”).

 

 

4.

Pilot decreases in size when main

4.

Supply piping inadequately sized or incorrect

 

 

 

burners come on.

 

inlet pressure.

 

 

5.

Drafts around appliance.

5.

Eliminate drafts.

 

 

6.

Bad venting.

6.

See “Venting”.

 

Failure to Ignite

1.

Main gas off.

1.

Open all manual gas valves.

 

 

2.

Defective gas valve.

2.

Replace gas valve.

 

Condensation of

1.

Improper venting.

1.

See “Venting”.

 

Water Vapor

 

 

 

 

 

Burner won’t

1.

Defective or sticking automatic valve.

1.

Replace valve.

 

turn off

2.

Excessive gas pressure (The supply gas

2.

To correct this situation contact the utility

 

 

 

pressure must not exceed 1/2 psi or

 

supplying the gas.

 

 

 

14” w.c.

 

 

 

Incorrect Gas Input

1.

Gas input not checked.

1.

Re-check gas input.

 

 

2.

Clogged orifice.

2.

Check orifice for clogging. If clogged, clean out

 

 

 

 

 

the hole carefully with a smooth wood toothpick.

 

 

 

 

 

(Do not in any way enlarge or distort it).

 

Not enough heat

1.

Appliance undersized.

1.

This is especially true when a dwelling or room is

 

 

 

 

 

enlarged. Have the heat loss calculated and compare

 

 

 

 

 

to the appliance output (approx. 70% of input).

 

 

 

 

 

Your gas company or installer can supply you with

 

 

 

 

 

this information. If appliance is undersized, replace

 

 

 

 

 

with correct size unit.

 

 

2.

Incorrect supply pressure.

2.

Check supply pressure as outlined above.

 

Too much heat

1.

Combination control valve sticks open.

1.

Replace combination control valve.

 

TROUBLE SHOOTING CHART - PILOT AND VALVE

 

Burner won’t

1.

Gas valve not turned on.

1.

Turn gas valve to “on” position”.

 

turn on

2.

No voltage to valve.

2.

Check for 24 Volts to Valve.

 

 

3.

Defective thermostat.

3.

Check wall thermostat.

 

 

4.

No 115 Volt Line Voltage.

4.

Jump fan switch to check for voltage (fan will

 

 

 

 

 

come on).

 

 

5.

Auxiliary limit switch open.

5.

Push on red buton to close.

 

 

6.

Blocked flue switch open.

6.

Push red button in to close.

 

 

7.

Gas valve defective.

7.

Replace gas valve

 

Page 18

Image 18
Contents This Unit is not to be Installed in Mobile Homes What to do if YOU Smell GASContents Counterflow Wall Furnace SpecificationsSafety Rules Read Carefully Before Installing UnitVenting Venting See List of Possible Causes and Corrections onCombustion and Ventilation AIR ALL Combustion AIR from Adjacent IndoorOpenings Location and Special Precautions ROUGH-IN InstructionsElectrical ROUGH-IN GAS ROUGH-IN Installation When Installed Flush to Wall Installation / When RecessedNatural GAS Pilot AdjustmentPilot Flame Adjustment GASTo Turn OFF GAS to Appliance Standing Pilot For Your Safety Read Before LightingLighting Instructions What to do if YOU Smell GASMaximum High GAS Control Pressure Regulator Lever Maximum High Pressure Regulator GAS ControlProper Burner Flame OperationAuxiliary Limit Switch Maintenance InstructionsTerminal Block Wiring Diagram Standing Pilot Pictorial SchematicSchematic LadderModel NO. Amps IgnitionModule Model no AmpsRear Optional Accessory KitsROUGH-INS for Rear or Side Discharge SideModel Optional KitsSide Discharge on Casing NumberTrouble Shooting Chart for qualified serviceman Main Burner Trouble Shooting Chart Pilot and ValveSymptom Possible Causes Corrective Action Possible Causes Corrective ActionControl Assembly Counterflow Wall Furnace / Standing PilotModels NAT. GAS Requires TWO Volt System with LOW-B.T.U. Standing PilotCounterflow Wall Furnace / I.I.D. Pilot Models NAT. GAS L.P. GASVolt System with Intermittent Vent Trim KIT Enclosure KIT no 306SR-A Side Register Flush Rear Register W Boot FlushBoot RecessREV /97 March Your GAS Control and Pilot Light System Tampering is DangerousLouisville TIN and Stove Company Table a

CF354C-R, CF504R, CF654C-R specifications

The Louisville Tin and Stove CF654C-R, CF504R, and CF354C-R are three distinctive models designed to provide efficient heating solutions tailored for various spaces and specific needs. Known for their stylish design and practical functionality, these units stand as a testament to craftsmanship in modern heating technology.

One of the main features of these models is their robust construction. Crafted from durable materials, they are designed to withstand the rigors of daily use while providing reliable heat. The units showcase a combination of classic aesthetics and modern functionality, allowing them to fit seamlessly in any home environment, be it traditional or contemporary.

The CF654C-R model stands out with its higher heating capacity, making it ideal for larger rooms or spaces that require significant warmth. It uses innovative heat distribution technology that ensures even warmth throughout the area, eliminating cold spots and enhancing comfort. The integrated thermostat allows users to maintain optimal temperatures effortlessly, further emphasizing energy efficiency.

The CF504R model, while slightly smaller, does not compromise on performance. It offers a perfect solution for medium-sized spaces, featuring a user-friendly interface that makes it easy to adjust settings to suit individual preferences. Advanced combustion technology maximizes fuel efficiency, resulting in lower energy bills while still delivering the heating power you expect.

The CF354C-R is tailored for smaller areas, making it the perfect choice for cozy rooms or as an additional heat source in larger homes. Despite its compact size, it is engineered with a high thermal efficiency rating, ensuring that it uses minimal fuel to produce significant heat. Its minimalist design fits easily into smaller spaces without occupying much room, making it a versatile addition to any home.

Each model integrates modern safety features, including flame failure safety devices and protective screens, ensuring peace of mind for users. Additionally, all three models are designed to accommodate a variety of fuel types, allowing homeowners to choose based on convenience and availability.

In summary, the Louisville Tin and Stove CF654C-R, CF504R, and CF354C-R are versatile heating solutions that cater to different needs, with a focus on durability, efficiency, and user-friendly operation. With their unique features and technologies, they remain a popular choice for anyone looking to enhance their home’s heating system.