Bryant 312AAV/JAV Electrical Data, BOX Relocation, Electrical Connection to J-BOX

Page 21

Table 7 – Electrical Data

 

 

VOLTS

 

OPERATING VOLTAGE

MAX

 

MAXIMUM

MAXIMUM

MINIMUM

FURNACE

 

 

RANGE

UNIT

WIRE

FUSE OR

HERTZ

 

 

UNIT

WIRE

 

SIZE

 

 

AMPACITY#

LENGTH

CKT BKR

 

PHASE

 

MAX*

MIN.*

AMPS

GAUGE

 

 

 

 

FT. (M)‡

AMPS†

045---

08/024045

115---

60---

1

127

104

5.3

7.42

49 (14.9)

15

14

045---

12/036045

115---

60---

1

127

104

7.1

9.67

38 (11.5)

15

14

070---

08/024070

115---

60---

1

127

104

5.2

7.22

51 (15.5)

15

14

070---

12/036070

115---

60---

1

127

104

7.3

9.90

37 (11.2)

15

14

070---

16/048070

115---

60---

1

127

104

10.1

13.42

27 (8.2)

15

14

090---

14/042090

115---

60---

1

127

104

8.2

10.84

34 (10.3)

15

14

090---

16/048090

115---

60---

1

127

104

9.9

13.0

28 (8.5)

15

14

090---

20/060090

115---

60---

1

127

104

12.9

16.70

34 (10.3)

20

12

110---

12/036110

115---

60---

1

127

104

8.2

10.76

34 (10.3)

15

14

110---

16/048110

115---

60---

1

127

104

10.1

13.19

28 (8.5)

15

14

110---

22/066110

115---

60---

1

127

104

13.7

17.60

32 (9.7)

20

12

135---

16/048135

115---

60---

1

127

104

10.2

13.28

27 (8.2)

15

14

135---

22/066135

115---

60---

1

127

104

14.5

18.61

30 (9.1)

20

12

155---

20/060155

115---

60---

1

127

104

15.0

19.34

29 (8.8)

20

12

* Permissible limits of the voltage range at which the unit operates satisfactorily.

#Unit ampacity = 125% of largest operating component’s full load amps plus 100% of all other potential operating components (EAC, humidifier, etc.) full load amps.

{ Time---delay type is recommended.

} Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.

312AAV

U.S. Installations: Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70-2008 and any local codes or ordinances that might apply.

!WARNING

FIRE HAZARD

Failure to follow this warning could result in personal injury, death, or property damage.

Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.

Use a separate branch electrical circuit with a properly sized fuse or circuit breaker for this furnace. See Table 7 for wire size and fuse specifications. A readily accessible means of electrical disconnect must be located within sight of the furnace.

NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control LED status indicator light will flash rapidly and furnace will NOT operate.

J-BOX RELOCATION

NOTE: If factory location of J-Box is acceptable, go to next section (ELECTRICAL CONNECTION TO J-BOX).

NOTE: On 14” wide casing models, the J-Box shall not be relocated to other side of furnace casing when the vent pipe is routed within the casing.

1.Remove and save two screws holding J-Box. (See Fig. 24

.)

NOTE: The J-Box cover need not be removed from the J-Box in order to move the J-Box. Do NOT remove green ground screw inside J-Box.

2.Cut wire tie on loop in furnace wires attached to J-Box.

3.Move J-Box to desired location.

4.Fasten J-Box to casing with the two screws removed in Step 1.

5.Route J-Box wires within furnace away from sharp edges, rotating parts, and hot surfaces.

Factory

Installed

Alternate

Location

A10291

Fig. 24 - Relocating J-Box

ELECTRICAL CONNECTION TO J-BOX

6.Reinstall cover to J-Box. Do not pinch wires between cover and bracket.

Electrical Box on Furnace Casing Side. See Fig. 25.

!WARNING

FIRE OR ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury, death, or property damage.

If field-supplied manual disconnect switch is to be mounted on furnace casing side, select a location where a drill or fastener cannot damage electrical or gas components.

21

Image 21
Contents Service and Maintenance Procedures 312AAV Introduction Safety ConsiderationsFurnace Reliability Hazard CUT HazardClearances to Combustibles Codes and Standards Electrostatic Discharge ESD Precautions ProcedureLocation GeneralCarbon Monoxide Poisoning and Unit Damage Hazard FIRE, Injury or Death Hazard AIR for Combustion VentilationFire Hazard Property Damage HazardFurnace Corrosion Hazard Carbon Monoxide Poisoning HazardOutdoor Combustion Air Method Air for Combustion, Ventilation, and Dilution for Outdoors Upflow Installation InstallationHorizontal Installation Downflow InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportRoll-Out Protection Platform Furnace SupportDuct Flanges Opening dimensions In. mmHorizontal Unit Suspension AIR Ducts Filter Arrangement Carbon Monoxide Poisoning HazardGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsAir Delivery CFM With Filter FurnaceSpeed External Static Pressure IN. W.C Size Inlet Downflow Furnaces Air Delivery CFM With Filter*Return Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Furnace Damage Hazard Maximum Capacity of PipeElectrical Shock and Fire Hazard WiringElectrical Connections Electrical Shock Hazard Furnace MAY not Operate HazardBOX Relocation Electrical DataElectrical Connection to J-BOX Electrical Box on Furnace Casing Side. See FigBX. Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXTwo-Stage Furnace with Two-Speed Air Conditioner For Figures Venting AccessoriesMasonry Chimney Requirements General Venting RequirementsChimney Inspection Chart Appliance Application Requirements Internal Area of ChimneyVent Height Additional Venting Requirements Upflow Application-Vent Elbow UpDownflow Application-Vent Elbow Up then Left Horizontal Left Application Vent Elbow Left Venting Notes for Furnace VentDiameter Vent Height Orientation INPUTBTUH/HR START-UP, ADJUSTMENT, and Safety Check GeneralBurn Hazard Adjustments Start-Up ProceduresStage Furnace Setup Switch Description Fire and Explosion HazardRedundant Automatic Gas Control Valve Altitude Derate Multiplier for U.S.AOrifice Hole Gas Rate cu ft. /hr Furnace Overheating HazardSeconds Size of Test Dial For Revolution Color Speed AS Shipped Speed SelectionChecklist Check Safety ControlsStage Furnace Blower OFF delay Setup Switch Desired Heating Mode Setup Switch Blower OFF Delay SECA10184 A10184A A10185 A10185A Introduction Service and Maintenance ProceduresCarbon Monoxide Poisoning and Fire Hazard Care and MaintenanceWiring Diagram Cleaning AND/OR Replacing AIR Filter Filter Size Information In. / MmBlower Motor and Wheel Electrical Shock Hazard Igniter Position-Side View Cleaning Heat ExchangerIgniter Position-Top View Sequence of Operation312AAV Single-Stage Thermostat and Two-Speed Cooling Adaptive Mode Thermidistat ModeSingle-Speed Cooling Wiring Diagrams TroubleshootingContinuous Blower Mode Troubleshooting Guide 2-Speed KitAdapter Chimneyin Usedswitch Shutoffvent Blocked Description Part Number Accessory ListParts Replacement Information Guide

312AAV/JAV specifications

The Bryant 312AAV/JAV is a prominent member of Bryant's series of high-efficiency air conditioning units, known for its reliability and advanced technology. Designed for residential and light commercial applications, this model combines exceptional performance with energy-efficient operation, making it a favorite among homeowners and builders alike.

One of the standout features of the 312AAV/JAV is its high SEER (Seasonal Energy Efficiency Ratio) rating, which allows users to enjoy significant savings on their energy bills. With a focus on energy efficiency, this unit minimizes electricity consumption while providing effective cooling throughout the hottest months. Its two-stage compressor technology not only enhances energy savings but also ensures consistent comfort by adjusting its operation to match the specific cooling needs of the space.

The Bryant 312AAV/JAV is equipped with Wi-Fi connectivity capabilities, allowing homeowners to control their cooling system remotely through a smartphone app. This feature adds a layer of convenience, enabling users to adjust settings, receive alerts, and track energy usage for optimal management of their home environment. Additionally, the unit’s compatibility with Smart Thermostats enhances its efficiency, facilitating further integration into a modern smart home setup.

Built for durability, the Bryant 312AAV/JAV features a robust construction that includes a galvanized steel cabinet designed to withstand harsh weather conditions. The rust-resistant finish not only prolongs the life of the unit but also ensures it maintains a sleek, attractive appearance. Quiet operation is another hallmark of this model; it operates at a low noise level, providing comfort without disruptive sound.

Moreover, this model employs environmentally friendly refrigerants, aligning with modern standards for eco-friendly cooling solutions. The 312AAV/JAV is designed with filters that provide superior air quality by effectively capturing dust and allergens, contributing to a healthier indoor environment.

In summary, the Bryant 312AAV/JAV air conditioning unit represents a blend of efficiency, technology, and durability. With its impressive energy-saving capabilities, smart connectivity, silent operation, and high-quality construction, it stands out as a top choice for those seeking reliable cooling solutions for their homes or light commercial settings. Whether for new installations or replacements, the 312AAV/JAV is designed to deliver exceptional performance while prioritizing comfort and sustainability.