Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the U.S.

Table 6 – Maximum Capacity of Pipe

NOMINAL

INTERNAL

 

LENGTH OF PIPE --- FT. (M)

 

IRON PIPE

 

 

 

 

 

 

DIA.

 

 

 

 

 

 

SIZE

10

 

20

30

40

50

IN. (MM)

 

IN. (MM)

(3.0)

 

(6.0)

(9.1)

(12.1)

(15.2)

 

 

 

 

 

 

 

 

 

 

1/2 (12.7)

0.622

175

 

120

97

82

73

(158)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4 (19.0)

0.824

360

 

250

200

170

151

(20.9)

 

 

 

 

 

 

 

 

1( 25.4)

1.049

680

 

465

375

320

285

(26.6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-1/4

1.380

1400

 

950

770

660

580

(31.8)

(35.0)

 

 

 

 

 

 

 

1-1/2

1.610

2100

 

1460

1180

990

900

(38.1)

(40.9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Cubic ft. of natural gas per hr for gas pressures of 0.5 psig (14---In. W.C.) or less and a pressure drop of 0.5---In. W.C. (based on a 0.60 specific gravity gas). Ref: Table 6 and NFPA54/ANSI Z223.1---2009.

Installations must be made in accordance with all authorities having jurisdiction. If possible, the gas supply line should be a separate line running directly from meter to furnace.

NOTE: In the state of Massachusetts:

1.Gas supply connections MUST be performed by a li- censed plumber or gas fitter.

2.When flexible connectors are used, the maximum length shall not exceed 36 inches (915 mm).

3.When lever handle type manual equipment shutoff valves are used, they shall be T-handle valves.

4.The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.

Refer to Table 6 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. (1.8 M). Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to the action of propane gas.

!WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury, death, and/or property damage.

If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance. Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 in. (51 mm) outside the furnace.

!CAUTION

FURNACE DAMAGE HAZARD

Failure to follow this caution may result in furnace damage.

Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls and burner misalignment.

An accessible manual equipment shutoff valve MUST be installed external to furnace casing and within 6 ft. of furnace. A 1/8-in. (3 mm) NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.

NOTE: The furnace gas control valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0.5 psig (14-In. W.C.) stated on gas control valve. (See Fig. 48.) Some installations require gas entry on right side of furnace (as viewed in upflow). (See Fig. 21.)

312AAV

2” (51mm)

Street Elbow

A08551

Fig. 21 - Burner and Manifold

Install a sediment trap in riser leading to furnace as shown in Fig.

22.Connect a capped nipple into lower end of tee. Capped nipple should extend below level of furnace gas controls. Place a ground joint union between furnace gas control valve manifold and exterior manual equipment gas shutoff valve.

GAS

SUPPLY

MANUAL

SHUTOFF

VALVE (REQUIRED)

SEDIMENT TRAP

UNION

A02035

Fig. 22 - Typical Gas Pipe Arrangement

19

Image 19
Contents Service and Maintenance Procedures 312AAV CUT Hazard Safety ConsiderationsIntroduction Furnace Reliability HazardClearances to Combustibles Codes and Standards Electrostatic Discharge ESD Precautions ProcedureGeneral LocationCarbon Monoxide Poisoning and Unit Damage Hazard Property Damage Hazard AIR for Combustion VentilationFIRE, Injury or Death Hazard Fire HazardCarbon Monoxide Poisoning Hazard Furnace Corrosion HazardOutdoor Combustion Air Method Air for Combustion, Ventilation, and Dilution for Outdoors Upflow Installation InstallationSuspended Furnace Support Downflow InstallationHorizontal Installation FIRE, EXPLOSION, and Carbon Monoxide Poisoning HazardRoll-Out Protection Platform Furnace SupportDuct Flanges Opening dimensions In. mmHorizontal Unit Suspension Ductwork Acoustical Treatment Supply Air Connections Filter Arrangement Carbon Monoxide Poisoning HazardAIR Ducts General RequirementsFurnace Air Delivery CFM With FilterSpeed External Static Pressure IN. W.C Size Inlet GAS Piping Fire or Explosion Hazard Air Delivery CFM With Filter*Downflow Furnaces Return Air ConnectionsUpflow Return Air Configurations and Restrictions Furnace Damage Hazard Maximum Capacity of PipeFurnace MAY not Operate Hazard WiringElectrical Shock and Fire Hazard Electrical Connections Electrical Shock HazardElectrical Box on Furnace Casing Side. See Fig Electrical DataBOX Relocation Electrical Connection to J-BOXBX. Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXTwo-Stage Furnace with Two-Speed Air Conditioner For Figures Venting AccessoriesMasonry Chimney Requirements General Venting RequirementsChimney Inspection Chart Internal Area of Chimney Appliance Application RequirementsVent Height Additional Venting Requirements Upflow Application-Vent Elbow UpDownflow Application-Vent Elbow Up then Left Horizontal Left Application Vent Elbow Left Furnace Vent Venting Notes forDiameter Vent Height Orientation INPUTBTUH/HR General START-UP, ADJUSTMENT, and Safety CheckBurn Hazard Fire and Explosion Hazard Start-Up ProceduresAdjustments Stage Furnace Setup Switch DescriptionRedundant Automatic Gas Control Valve Altitude Derate Multiplier for U.S.AOrifice Hole Furnace Overheating Hazard Gas Rate cu ft. /hrSeconds Size of Test Dial For Revolution Color Speed AS Shipped Speed SelectionDesired Heating Mode Setup Switch Blower OFF Delay SEC Check Safety ControlsChecklist Stage Furnace Blower OFF delay Setup SwitchA10184 A10184A A10185 A10185A Introduction Service and Maintenance ProceduresCarbon Monoxide Poisoning and Fire Hazard Care and MaintenanceWiring Diagram Filter Size Information In. / Mm Cleaning AND/OR Replacing AIR FilterBlower Motor and Wheel Electrical Shock Hazard Igniter Position-Side View Cleaning Heat ExchangerIgniter Position-Top View Sequence of Operation312AAV Thermidistat Mode Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeSingle-Speed Cooling Troubleshooting Wiring DiagramsContinuous Blower Mode Troubleshooting Guide 2-Speed KitAdapter Chimneyin Usedswitch Shutoffvent Blocked Description Part Number Accessory ListParts Replacement Information Guide

312AAV/JAV specifications

The Bryant 312AAV/JAV is a prominent member of Bryant's series of high-efficiency air conditioning units, known for its reliability and advanced technology. Designed for residential and light commercial applications, this model combines exceptional performance with energy-efficient operation, making it a favorite among homeowners and builders alike.

One of the standout features of the 312AAV/JAV is its high SEER (Seasonal Energy Efficiency Ratio) rating, which allows users to enjoy significant savings on their energy bills. With a focus on energy efficiency, this unit minimizes electricity consumption while providing effective cooling throughout the hottest months. Its two-stage compressor technology not only enhances energy savings but also ensures consistent comfort by adjusting its operation to match the specific cooling needs of the space.

The Bryant 312AAV/JAV is equipped with Wi-Fi connectivity capabilities, allowing homeowners to control their cooling system remotely through a smartphone app. This feature adds a layer of convenience, enabling users to adjust settings, receive alerts, and track energy usage for optimal management of their home environment. Additionally, the unit’s compatibility with Smart Thermostats enhances its efficiency, facilitating further integration into a modern smart home setup.

Built for durability, the Bryant 312AAV/JAV features a robust construction that includes a galvanized steel cabinet designed to withstand harsh weather conditions. The rust-resistant finish not only prolongs the life of the unit but also ensures it maintains a sleek, attractive appearance. Quiet operation is another hallmark of this model; it operates at a low noise level, providing comfort without disruptive sound.

Moreover, this model employs environmentally friendly refrigerants, aligning with modern standards for eco-friendly cooling solutions. The 312AAV/JAV is designed with filters that provide superior air quality by effectively capturing dust and allergens, contributing to a healthier indoor environment.

In summary, the Bryant 312AAV/JAV air conditioning unit represents a blend of efficiency, technology, and durability. With its impressive energy-saving capabilities, smart connectivity, silent operation, and high-quality construction, it stands out as a top choice for those seeking reliable cooling solutions for their homes or light commercial settings. Whether for new installations or replacements, the 312AAV/JAV is designed to deliver exceptional performance while prioritizing comfort and sustainability.