Bryant 312AAV/JAV instruction manual Air for Combustion, Ventilation, and Dilution for Outdoors

Page 9

 

 

 

 

 

1 SQ IN.

 

 

 

DUCTS

 

PER 4000

 

 

 

 

BTUH*

 

 

 

TO

 

 

 

 

 

 

 

 

OUTDOORS

 

 

 

(305mm) 12MAX

 

 

 

D

12

(305mm)

1 SQ IN.

 

CIRCULATING

AIR DUCTS

VENT

MAX

 

PER 2000

B

THROUGH

F

 

BTUH*

 

ROOF

1 SQ IN.

 

 

 

 

 

 

 

 

PER

 

 

 

 

4000

 

 

 

 

BTUH*

 

 

 

 

 

 

 

DUCTS

 

CLEARANCE IN FRONT

OF COMBUSTION AIR OPENINGS SHALL BE AT LEAST 3 IN.

 

OUTDOORS

 

TO

 

 

 

OUTDOORS

 

 

 

 

 

 

 

 

 

 

1 SQ IN.

 

 

 

 

PER

 

 

 

 

4000

 

1 SQ IN.

 

 

BTUH*

 

 

E

G

 

PER 2000

A

 

BTUH*

 

(76mm)

12

(305mm)

(305mm) 12MAX

 

 

 

C

MAX

 

 

 

 

12MAX

 

 

 

 

 

(305mm)

 

CIRCULATING AIR DUCTS

DUCT

1 SQ IN.

 

 

 

 

 

 

 

 

 

 

TO

PER 4000

 

 

 

 

 

OUTDOORS

BTUH*

 

*Minimum dimensions of 3---in. (76 mm).

 

 

Note: Use any of the following combinations of openings:

 

A & B C & D D & E F & G

 

 

 

 

 

 

 

 

 

 

A03174

Fig. 7 - Air for Combustion, Ventilation, and Dilution for

Outdoors

The opening shall commence within 12 in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

Indoor Combustion AirE NFPA & AGA Standard and Known-Air-Infiltration Rate Methods

Indoor air is permitted for combustion, ventilation, and dilution, if the Standard or Known-Air-InfiltrationMethod is used.

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in death and/or personal injury.

Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in accordance with this instruction manual.

 

CIRCULATING AIR

VENT THROUGH ROOF

 

 

DUCTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

 

 

12"

 

MAX (305mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMBUSTIONOFFRONT IN.3LEASTATBESHALL

 

 

 

 

 

 

 

IN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 SQ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER 1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BTUH* IN DOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OR WALL

 

 

 

INTERIOR

 

 

 

 

 

 

 

 

 

UNCONFINED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPACE

 

 

 

HEATED

 

 

 

 

 

 

 

 

 

 

 

 

SPACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6" MIN (152mm)

 

 

 

 

 

 

 

 

 

 

CLEARANCEIN OPENINGS

 

 

 

(FRONT)Ü

312AAV

 

 

 

 

 

 

 

 

 

 

 

 

1 SQ IN.

 

 

 

 

 

 

 

 

 

 

 

 

 

PER 1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BTUH* IN DOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OR WALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12" MAX (305mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCULATING AIR DUCTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Minimum opening size is 100 sq in. (64516 sq. mm) with minimum dimensions of 3 in. (76 mm)

† Minimum of 3 in. (76 mm) when type-B1 vent is used.

A03175

Fig. 8 - Air for Combustion, Ventilation, and Dilution from

Indoors

The Standard Method:

1.The space has no less volume than 50 cubic feet per 1,000 Btuh of the maximum input ratings for all gas appliances installed in the space and

2.The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).

The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:

1.Less than 0.40 ACH and

2.Equal to or greater than 0.10 ACH

Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 3 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the space.

9

Image 9
Contents Service and Maintenance Procedures 312AAV Introduction Safety ConsiderationsFurnace Reliability Hazard CUT HazardClearances to Combustibles Codes and Standards Electrostatic Discharge ESD Precautions ProcedureLocation GeneralCarbon Monoxide Poisoning and Unit Damage Hazard FIRE, Injury or Death Hazard AIR for Combustion VentilationFire Hazard Property Damage HazardFurnace Corrosion Hazard Carbon Monoxide Poisoning HazardOutdoor Combustion Air Method Air for Combustion, Ventilation, and Dilution for Outdoors Upflow Installation InstallationHorizontal Installation Downflow InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportRoll-Out Protection Platform Furnace SupportDuct Flanges Opening dimensions In. mmHorizontal Unit Suspension AIR Ducts Filter Arrangement Carbon Monoxide Poisoning HazardGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsAir Delivery CFM With Filter FurnaceSpeed External Static Pressure IN. W.C Size Inlet Downflow Furnaces Air Delivery CFM With Filter*Return Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Furnace Damage Hazard Maximum Capacity of PipeElectrical Shock and Fire Hazard WiringElectrical Connections Electrical Shock Hazard Furnace MAY not Operate HazardBOX Relocation Electrical DataElectrical Connection to J-BOX Electrical Box on Furnace Casing Side. See FigBX. Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXTwo-Stage Furnace with Two-Speed Air Conditioner For Figures Venting AccessoriesMasonry Chimney Requirements General Venting RequirementsChimney Inspection Chart Appliance Application Requirements Internal Area of ChimneyVent Height Additional Venting Requirements Upflow Application-Vent Elbow UpDownflow Application-Vent Elbow Up then Left Horizontal Left Application Vent Elbow Left Venting Notes for Furnace VentDiameter Vent Height Orientation INPUTBTUH/HR START-UP, ADJUSTMENT, and Safety Check GeneralBurn Hazard Adjustments Start-Up ProceduresStage Furnace Setup Switch Description Fire and Explosion HazardRedundant Automatic Gas Control Valve Altitude Derate Multiplier for U.S.AOrifice Hole Gas Rate cu ft. /hr Furnace Overheating HazardSeconds Size of Test Dial For Revolution Color Speed AS Shipped Speed SelectionChecklist Check Safety ControlsStage Furnace Blower OFF delay Setup Switch Desired Heating Mode Setup Switch Blower OFF Delay SECA10184 A10184A A10185 A10185A Introduction Service and Maintenance ProceduresCarbon Monoxide Poisoning and Fire Hazard Care and MaintenanceWiring Diagram Cleaning AND/OR Replacing AIR Filter Filter Size Information In. / MmBlower Motor and Wheel Electrical Shock Hazard Igniter Position-Side View Cleaning Heat ExchangerIgniter Position-Top View Sequence of Operation312AAV Single-Stage Thermostat and Two-Speed Cooling Adaptive Mode Thermidistat ModeSingle-Speed Cooling Wiring Diagrams TroubleshootingContinuous Blower Mode Troubleshooting Guide 2-Speed KitAdapter Chimneyin Usedswitch Shutoffvent Blocked Description Part Number Accessory ListParts Replacement Information Guide

312AAV/JAV specifications

The Bryant 312AAV/JAV is a prominent member of Bryant's series of high-efficiency air conditioning units, known for its reliability and advanced technology. Designed for residential and light commercial applications, this model combines exceptional performance with energy-efficient operation, making it a favorite among homeowners and builders alike.

One of the standout features of the 312AAV/JAV is its high SEER (Seasonal Energy Efficiency Ratio) rating, which allows users to enjoy significant savings on their energy bills. With a focus on energy efficiency, this unit minimizes electricity consumption while providing effective cooling throughout the hottest months. Its two-stage compressor technology not only enhances energy savings but also ensures consistent comfort by adjusting its operation to match the specific cooling needs of the space.

The Bryant 312AAV/JAV is equipped with Wi-Fi connectivity capabilities, allowing homeowners to control their cooling system remotely through a smartphone app. This feature adds a layer of convenience, enabling users to adjust settings, receive alerts, and track energy usage for optimal management of their home environment. Additionally, the unit’s compatibility with Smart Thermostats enhances its efficiency, facilitating further integration into a modern smart home setup.

Built for durability, the Bryant 312AAV/JAV features a robust construction that includes a galvanized steel cabinet designed to withstand harsh weather conditions. The rust-resistant finish not only prolongs the life of the unit but also ensures it maintains a sleek, attractive appearance. Quiet operation is another hallmark of this model; it operates at a low noise level, providing comfort without disruptive sound.

Moreover, this model employs environmentally friendly refrigerants, aligning with modern standards for eco-friendly cooling solutions. The 312AAV/JAV is designed with filters that provide superior air quality by effectively capturing dust and allergens, contributing to a healthier indoor environment.

In summary, the Bryant 312AAV/JAV air conditioning unit represents a blend of efficiency, technology, and durability. With its impressive energy-saving capabilities, smart connectivity, silent operation, and high-quality construction, it stands out as a top choice for those seeking reliable cooling solutions for their homes or light commercial settings. Whether for new installations or replacements, the 312AAV/JAV is designed to deliver exceptional performance while prioritizing comfort and sustainability.