Bryant 312AAV/JAV Codes and Standards, Electrostatic Discharge ESD Precautions Procedure

Page 5

80 / 27 C

60 / 16 C

A06745

Fig. 3 - Return Air Temperature

CODES AND STANDARDS

Follow all national and local codes and standards in addition to these instructions. The installation must comply with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.

In the United States, follow all codes and standards for the following:

Step 1 — Safety

National Fuel Gas Code (NFGC) NFPA 54-2009/ANSI Z223.1-2009 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B

Step 2 — General Installation

Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the American Gas Association, 400 N. Capitol Street, N.W., Washington DC 20001 (www.AGA.org.)

Step 3 — Combustion and Ventilation Air

Section 9.3 of the NFGC, NFPA 54/ ANSI Z223.1-2009 Air for Combustion and Ventilation

Step 4 — Duct Systems

Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter 34 or 2000 HVAC Systems and Equipment Handbook Chapters 9 and 16.

Step 5 — Acoustical Lining and Fibrous Glass Duct

Current edition of SMACNA and NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts

Step 6 — Gas Piping and Gas Pipe Pressure Testing

NFPA 54 / ANSI Z223.1-2009; chapters 5, 6, 7, and 8 and National Plumbing Codes

Step 7 — Electrical Connections

National Electrical Code (NEC) ANSI/NFPA 70-2008

Step 8 — Venting

NFGC; NFPA 54 / ANSI Z223.1-2009 chapters 12 and 13

ELECTROSTATIC DISCHARGE (ESD)

PRECAUTIONS PROCEDURE

!CAUTION

FURNACE RELIABILITY HAZARD

Improper installation or service of furnace may cause premature furnace component failure.

Electrostatic discharge can affect electronic components. Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.

1.Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR

TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.

2.Firmly touch the clean, unpainted, metal surface of the fur- nace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily dis- charged.

3.After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not touch un- grounded objects, etc.).

4.If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.

5.Use this procedure for installed and uninstalled (ungroun- ded) furnaces.

6.Before removing a new control from its container, dis- charge your body’s electrostatic charge to ground to pro- tect the control from damage. If the control is to be in- stalled in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the fur- nace. Put all used and new controls into containers before touching ungrounded objects.

7.An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.

312AAV

5

Image 5
Contents Service and Maintenance Procedures 312AAV Introduction Safety ConsiderationsFurnace Reliability Hazard CUT HazardClearances to Combustibles Codes and Standards Electrostatic Discharge ESD Precautions ProcedureCarbon Monoxide Poisoning and Unit Damage Hazard LocationGeneral FIRE, Injury or Death Hazard AIR for Combustion VentilationFire Hazard Property Damage HazardOutdoor Combustion Air Method Furnace Corrosion HazardCarbon Monoxide Poisoning Hazard Air for Combustion, Ventilation, and Dilution for Outdoors Upflow Installation InstallationHorizontal Installation Downflow InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportRoll-Out Protection Platform Furnace SupportDuct Flanges Opening dimensions In. mmHorizontal Unit Suspension AIR Ducts Filter Arrangement Carbon Monoxide Poisoning HazardGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsSpeed External Static Pressure IN. W.C Size Inlet Air Delivery CFM With FilterFurnace Downflow Furnaces Air Delivery CFM With Filter*Return Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Furnace Damage Hazard Maximum Capacity of PipeElectrical Shock and Fire Hazard WiringElectrical Connections Electrical Shock Hazard Furnace MAY not Operate HazardBOX Relocation Electrical DataElectrical Connection to J-BOX Electrical Box on Furnace Casing Side. See FigBX. Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXTwo-Stage Furnace with Two-Speed Air Conditioner For Figures Venting AccessoriesMasonry Chimney Requirements General Venting RequirementsChimney Inspection Chart Vent Height Appliance Application RequirementsInternal Area of Chimney Additional Venting Requirements Upflow Application-Vent Elbow UpDownflow Application-Vent Elbow Up then Left Horizontal Left Application Vent Elbow Left Diameter Vent Height Orientation INPUTBTUH/HR Venting Notes forFurnace Vent Burn Hazard START-UP, ADJUSTMENT, and Safety CheckGeneral Adjustments Start-Up ProceduresStage Furnace Setup Switch Description Fire and Explosion HazardRedundant Automatic Gas Control Valve Altitude Derate Multiplier for U.S.AOrifice Hole Seconds Size of Test Dial For Revolution Gas Rate cu ft. /hrFurnace Overheating Hazard Color Speed AS Shipped Speed SelectionChecklist Check Safety ControlsStage Furnace Blower OFF delay Setup Switch Desired Heating Mode Setup Switch Blower OFF Delay SECA10184 A10184A A10185 A10185A Introduction Service and Maintenance ProceduresCarbon Monoxide Poisoning and Fire Hazard Care and MaintenanceWiring Diagram Blower Motor and Wheel Electrical Shock Hazard Cleaning AND/OR Replacing AIR FilterFilter Size Information In. / Mm Igniter Position-Side View Cleaning Heat ExchangerIgniter Position-Top View Sequence of Operation312AAV Single-Speed Cooling Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeThermidistat Mode Continuous Blower Mode Wiring DiagramsTroubleshooting Troubleshooting Guide 2-Speed KitAdapter Chimneyin Usedswitch Shutoffvent Blocked Description Part Number Accessory ListParts Replacement Information Guide

312AAV/JAV specifications

The Bryant 312AAV/JAV is a prominent member of Bryant's series of high-efficiency air conditioning units, known for its reliability and advanced technology. Designed for residential and light commercial applications, this model combines exceptional performance with energy-efficient operation, making it a favorite among homeowners and builders alike.

One of the standout features of the 312AAV/JAV is its high SEER (Seasonal Energy Efficiency Ratio) rating, which allows users to enjoy significant savings on their energy bills. With a focus on energy efficiency, this unit minimizes electricity consumption while providing effective cooling throughout the hottest months. Its two-stage compressor technology not only enhances energy savings but also ensures consistent comfort by adjusting its operation to match the specific cooling needs of the space.

The Bryant 312AAV/JAV is equipped with Wi-Fi connectivity capabilities, allowing homeowners to control their cooling system remotely through a smartphone app. This feature adds a layer of convenience, enabling users to adjust settings, receive alerts, and track energy usage for optimal management of their home environment. Additionally, the unit’s compatibility with Smart Thermostats enhances its efficiency, facilitating further integration into a modern smart home setup.

Built for durability, the Bryant 312AAV/JAV features a robust construction that includes a galvanized steel cabinet designed to withstand harsh weather conditions. The rust-resistant finish not only prolongs the life of the unit but also ensures it maintains a sleek, attractive appearance. Quiet operation is another hallmark of this model; it operates at a low noise level, providing comfort without disruptive sound.

Moreover, this model employs environmentally friendly refrigerants, aligning with modern standards for eco-friendly cooling solutions. The 312AAV/JAV is designed with filters that provide superior air quality by effectively capturing dust and allergens, contributing to a healthier indoor environment.

In summary, the Bryant 312AAV/JAV air conditioning unit represents a blend of efficiency, technology, and durability. With its impressive energy-saving capabilities, smart connectivity, silent operation, and high-quality construction, it stands out as a top choice for those seeking reliable cooling solutions for their homes or light commercial settings. Whether for new installations or replacements, the 312AAV/JAV is designed to deliver exceptional performance while prioritizing comfort and sustainability.