Bryant 312AAV/JAV instruction manual Furnace Corrosion Hazard, Carbon Monoxide Poisoning Hazard

Page 8

312AAV

!CAUTION

FURNACE CORROSION HAZARD

Failure to follow this caution may result in furnace damage.

Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of make-up air is available.

The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.

SSpaces having less than 50 cubic feet per 1,000 Btuh require the Outdoor Combustion Air Method.

SSpaces having at least 50 cubic feet per 1,000 Btuh may use the Indoor Combustion Air, Standard or Known Air Infiltration Method.

Outdoor Combustion Air Method

1.Provide the space with sufficient air for proper combus- tion, ventilation, and dilution of flue gases using perman- ent horizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.

2.Fig. 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.

e.One opening MUST commence within 12 in. (300 mm) of the ceiling and the second opening MUST commence within 12 in. (300 mm) of the floor.

f.Size openings and ducts per Fig. 7 and Table 2.

g.TWO HORIZONTAL DUCTS require 1 -in2of free area per 2,000 Btuh (1,100 mm2/kW) of combined input for all gas appliances in the space per Fig.7 and Table 2.

h.TWO OPENINGS OR VERTICAL DUCTS require 1 -in2of free area per 4,000 Btuh (550 mm2/kW) for com- bined input of all gas appliances in the space per Fig. 7 and Table 2.

3.ONE OUTDOOR OPENING requires:

a.One square inch of free area per 3,000 Btuh (734 mm2/kW) for combined input of all gas appliances in the space per Table 2 and

b.Not less than the sum of the areas of all vent connectors in the space.

Table 2 – Minimum Free Area Required for Each Combustion Air opening of Duct to Outdoors

 

TWO HORIZONTAL DUCTS

SINGLE DUCT OR OPENING

TWO OPENINGS OR VERTICAL DUCTS

FURNACE

(1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW)

(1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW)

(1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW)

INPUT

 

 

 

 

 

 

Free Area of Opening

Round Duct

Free Area of Opening

Round Duct

Free Area of Opening

Round Duct

(BTUH)

and Duct

Dia.

and Duct

Dia.

and Duct

Dia.

 

Sq. In. (Sq. mm)

In. (mm)

Sq. In. (Sq. mm)

In. (mm)

Sq. In. (Sq. mm)

In. (mm)

44,000

22 (14194)

6 (152)

14.7 (9484)

5 (127)

11 (7096)

4 (102)

66,000

33 (21290)

7 (178)

22 (14193)

6 (152)

16.5 (10645)

5 (127)

88,000

44 (28387)

8 (203)

29.3 (18903)

7 (178)

22 (14193)

6 (152)

110,000

55 (35484)

9 (229)

36.7 (23677)

7 (178)

27.5 (17742)

6 (152)

132,000

66 (42580)

10 (254)

44 (28387)

8 (203)

33 (21290)

7 (178)

154,000

77 (49677)

10 (254)

51.3 (33096)

9 (229)

38.5 (24839)

8 (203)

EXAMPLES: Determining Free Area

FURNACE

 

WATER HEATER

 

TOTAL INPUT

 

 

 

110,000

+

30,000

= (140,000 divided by 4,000)

=

35.0

Sq. In. for each two Vertical Ducts or Openings

66,000

+

40,000

=

(106,000 divided by 3,000)

=

35.3

Sq. In. for a Single Duct or Opening

88,000

+

30,000

=

(118,000 divided by 2,000)

=

59.0

Sq. In. for each of two Horizontal Ducts

 

 

 

 

 

 

 

 

8

Image 8
Contents Service and Maintenance Procedures 312AAV Safety Considerations IntroductionFurnace Reliability Hazard CUT HazardClearances to Combustibles Electrostatic Discharge ESD Precautions Procedure Codes and StandardsCarbon Monoxide Poisoning and Unit Damage Hazard LocationGeneral AIR for Combustion Ventilation FIRE, Injury or Death HazardFire Hazard Property Damage HazardOutdoor Combustion Air Method Furnace Corrosion HazardCarbon Monoxide Poisoning Hazard Air for Combustion, Ventilation, and Dilution for Outdoors Installation Upflow InstallationDownflow Installation Horizontal InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportPlatform Furnace Support Roll-Out ProtectionOpening dimensions In. mm Duct FlangesHorizontal Unit Suspension Filter Arrangement Carbon Monoxide Poisoning Hazard AIR DuctsGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsSpeed External Static Pressure IN. W.C Size Inlet Air Delivery CFM With FilterFurnace Air Delivery CFM With Filter* Downflow FurnacesReturn Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Maximum Capacity of Pipe Furnace Damage HazardWiring Electrical Shock and Fire HazardElectrical Connections Electrical Shock Hazard Furnace MAY not Operate HazardElectrical Data BOX RelocationElectrical Connection to J-BOX Electrical Box on Furnace Casing Side. See FigPower Cord Installation in Furnace J-BOX BX. Cable Installation in Furnace J-BOXTwo-Stage Furnace with Two-Speed Air Conditioner For Figures Accessories VentingGeneral Venting Requirements Masonry Chimney RequirementsChimney Inspection Chart Vent Height Appliance Application RequirementsInternal Area of Chimney Upflow Application-Vent Elbow Up Additional Venting RequirementsDownflow Application-Vent Elbow Up then Left Horizontal Left Application Vent Elbow Left Diameter Vent Height Orientation INPUTBTUH/HR Venting Notes forFurnace Vent Burn Hazard START-UP, ADJUSTMENT, and Safety CheckGeneral Start-Up Procedures AdjustmentsStage Furnace Setup Switch Description Fire and Explosion HazardAltitude Derate Multiplier for U.S.A Redundant Automatic Gas Control ValveOrifice Hole Seconds Size of Test Dial For Revolution Gas Rate cu ft. /hrFurnace Overheating Hazard Speed Selection Color Speed AS ShippedCheck Safety Controls ChecklistStage Furnace Blower OFF delay Setup Switch Desired Heating Mode Setup Switch Blower OFF Delay SECA10184 A10184A A10185 A10185A Service and Maintenance Procedures IntroductionCare and Maintenance Carbon Monoxide Poisoning and Fire HazardWiring Diagram Blower Motor and Wheel Electrical Shock Hazard Cleaning AND/OR Replacing AIR FilterFilter Size Information In. / Mm Cleaning Heat Exchanger Igniter Position-Side ViewSequence of Operation Igniter Position-Top View312AAV Single-Speed Cooling Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeThermidistat Mode Continuous Blower Mode Wiring DiagramsTroubleshooting Troubleshooting Guide 2-Speed KitAdapter Chimneyin Usedswitch Shutoffvent Blocked Accessory List Description Part NumberParts Replacement Information Guide

312AAV/JAV specifications

The Bryant 312AAV/JAV is a prominent member of Bryant's series of high-efficiency air conditioning units, known for its reliability and advanced technology. Designed for residential and light commercial applications, this model combines exceptional performance with energy-efficient operation, making it a favorite among homeowners and builders alike.

One of the standout features of the 312AAV/JAV is its high SEER (Seasonal Energy Efficiency Ratio) rating, which allows users to enjoy significant savings on their energy bills. With a focus on energy efficiency, this unit minimizes electricity consumption while providing effective cooling throughout the hottest months. Its two-stage compressor technology not only enhances energy savings but also ensures consistent comfort by adjusting its operation to match the specific cooling needs of the space.

The Bryant 312AAV/JAV is equipped with Wi-Fi connectivity capabilities, allowing homeowners to control their cooling system remotely through a smartphone app. This feature adds a layer of convenience, enabling users to adjust settings, receive alerts, and track energy usage for optimal management of their home environment. Additionally, the unit’s compatibility with Smart Thermostats enhances its efficiency, facilitating further integration into a modern smart home setup.

Built for durability, the Bryant 312AAV/JAV features a robust construction that includes a galvanized steel cabinet designed to withstand harsh weather conditions. The rust-resistant finish not only prolongs the life of the unit but also ensures it maintains a sleek, attractive appearance. Quiet operation is another hallmark of this model; it operates at a low noise level, providing comfort without disruptive sound.

Moreover, this model employs environmentally friendly refrigerants, aligning with modern standards for eco-friendly cooling solutions. The 312AAV/JAV is designed with filters that provide superior air quality by effectively capturing dust and allergens, contributing to a healthier indoor environment.

In summary, the Bryant 312AAV/JAV air conditioning unit represents a blend of efficiency, technology, and durability. With its impressive energy-saving capabilities, smart connectivity, silent operation, and high-quality construction, it stands out as a top choice for those seeking reliable cooling solutions for their homes or light commercial settings. Whether for new installations or replacements, the 312AAV/JAV is designed to deliver exceptional performance while prioritizing comfort and sustainability.