Bryant 312AAV/JAV Venting Notes for, Furnace Vent, Diameter Vent Height Orientation INPUTBTUH/HR

Page 32

312AAV

SEE NOTES: 1,2,4,5,7,8,9

A02068

Fig. 47 - Horizontal Right Application-Vent Elbow Left

VENTING NOTES FOR FIG. 35 - 47

1.For common vent, vent connector sizing and vent material: United States-use the NFGC.

2.Immediately increase to 5-in. or 6-in. (127 or 152 mm) vent connector outside furnace casing when 5-in. (127 mm) vent connector is required, refer to Note 1 above.

3.Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when factory-approved Downflow Vent Guard Kit, is used in the downflow position. See Table 18 for accessory listing.

4.Type-B vent where required, refer to Note 1 above.

5.Four-in. (102 mm) single-wall (26 ga. min.) vent must be used inside furnace casing and when the factory-approved Downflow Vent Guard Kit is used external to the furnace. See Table 18 for accessory listing.

6.Accessory Downflow Vent Guard Kit required in downflow installations with lower vent configuration. See Table 18 for accessory listing.

7.Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit for sizing and complete application details. See Table 18 for accessory listing.

8.Secure vent connector to furnace elbow with (2) corrosion-resistant sheet metal screws, spaced approximately 180_ apart.

9.Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120_ apart. Secure Type-B vent connectors per vent connector manufacturer’s recommendations.

10.The total height of the vent and connector shall be at least seven feet (2 M) for the 154,000 Btuh gas input rate model when installed in a downflow application with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward. (See Fig. 40.)

Caution!! For the following applications, use the minimum vertical heights as specified below.

For all other applications, follow exclusively the National Fuel Gas Code

FURNACE

VENT

FURNACE

MINIMUM VENT

MINIMUM VERTICAL

DIAMETER

VENT HEIGHT

ORIENTATION

ORIENTATION

INPUT(BTUH/HR)

IN. (mm)*

FT. (M)**

 

 

 

 

 

 

 

 

 

Vent elbow left, then

154,000

 

 

Downflow

132,000

5 (127)

12 (3.6)

up Fig. 39

 

110,000 (036/--- 12 only)

 

 

 

 

 

 

 

 

 

 

 

Horizontal Left

Vent elbow right,

154,000

5 (127)

7 (.65)

then up Fig. 42

132,000

 

 

 

 

 

 

 

 

Horizontal Left

Vent Elbow up Fig.

154,000

5 (127)

7 (.65)

43

132,000

 

 

 

 

 

 

 

 

Horizontal Left

Vent elbow right Fig.

154,000

5 (127)

7 (.65)

44

 

 

 

 

 

 

 

 

 

Downflow

Vent elbow up then

110,000 (036/--- 12 only)

5 (127)

10 (3.0)

left Fig. 37

 

 

 

 

Downflow

Vent elbow up, then

110,000 (036/--- 12 only)

5 (127)

10 (3.0)

right Fig. 40

 

 

 

 

*4 in. (102 mm) inside casing or vent guard **Including 4 in. (102 mm) vent section(s)

NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.

32

Image 32
Contents Service and Maintenance Procedures 312AAV Safety Considerations IntroductionFurnace Reliability Hazard CUT HazardClearances to Combustibles Electrostatic Discharge ESD Precautions Procedure Codes and StandardsCarbon Monoxide Poisoning and Unit Damage Hazard LocationGeneral AIR for Combustion Ventilation FIRE, Injury or Death HazardFire Hazard Property Damage HazardOutdoor Combustion Air Method Furnace Corrosion HazardCarbon Monoxide Poisoning Hazard Air for Combustion, Ventilation, and Dilution for Outdoors Installation Upflow InstallationDownflow Installation Horizontal InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportPlatform Furnace Support Roll-Out ProtectionOpening dimensions In. mm Duct FlangesHorizontal Unit Suspension Filter Arrangement Carbon Monoxide Poisoning Hazard AIR DuctsGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsSpeed External Static Pressure IN. W.C Size Inlet Air Delivery CFM With FilterFurnace Air Delivery CFM With Filter* Downflow FurnacesReturn Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Maximum Capacity of Pipe Furnace Damage HazardWiring Electrical Shock and Fire HazardElectrical Connections Electrical Shock Hazard Furnace MAY not Operate HazardElectrical Data BOX RelocationElectrical Connection to J-BOX Electrical Box on Furnace Casing Side. See FigPower Cord Installation in Furnace J-BOX BX. Cable Installation in Furnace J-BOXTwo-Stage Furnace with Two-Speed Air Conditioner For Figures Accessories VentingGeneral Venting Requirements Masonry Chimney RequirementsChimney Inspection Chart Vent Height Appliance Application RequirementsInternal Area of Chimney Upflow Application-Vent Elbow Up Additional Venting RequirementsDownflow Application-Vent Elbow Up then Left Horizontal Left Application Vent Elbow Left Diameter Vent Height Orientation INPUTBTUH/HR Venting Notes forFurnace Vent Burn Hazard START-UP, ADJUSTMENT, and Safety CheckGeneral Start-Up Procedures AdjustmentsStage Furnace Setup Switch Description Fire and Explosion HazardAltitude Derate Multiplier for U.S.A Redundant Automatic Gas Control ValveOrifice Hole Seconds Size of Test Dial For Revolution Gas Rate cu ft. /hrFurnace Overheating Hazard Speed Selection Color Speed AS ShippedCheck Safety Controls ChecklistStage Furnace Blower OFF delay Setup Switch Desired Heating Mode Setup Switch Blower OFF Delay SECA10184 A10184A A10185 A10185A Service and Maintenance Procedures IntroductionCare and Maintenance Carbon Monoxide Poisoning and Fire HazardWiring Diagram Blower Motor and Wheel Electrical Shock Hazard Cleaning AND/OR Replacing AIR FilterFilter Size Information In. / Mm Cleaning Heat Exchanger Igniter Position-Side ViewSequence of Operation Igniter Position-Top View312AAV Single-Speed Cooling Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeThermidistat Mode Continuous Blower Mode Wiring DiagramsTroubleshooting Troubleshooting Guide 2-Speed KitAdapter Chimneyin Usedswitch Shutoffvent Blocked Accessory List Description Part NumberParts Replacement Information Guide

312AAV/JAV specifications

The Bryant 312AAV/JAV is a prominent member of Bryant's series of high-efficiency air conditioning units, known for its reliability and advanced technology. Designed for residential and light commercial applications, this model combines exceptional performance with energy-efficient operation, making it a favorite among homeowners and builders alike.

One of the standout features of the 312AAV/JAV is its high SEER (Seasonal Energy Efficiency Ratio) rating, which allows users to enjoy significant savings on their energy bills. With a focus on energy efficiency, this unit minimizes electricity consumption while providing effective cooling throughout the hottest months. Its two-stage compressor technology not only enhances energy savings but also ensures consistent comfort by adjusting its operation to match the specific cooling needs of the space.

The Bryant 312AAV/JAV is equipped with Wi-Fi connectivity capabilities, allowing homeowners to control their cooling system remotely through a smartphone app. This feature adds a layer of convenience, enabling users to adjust settings, receive alerts, and track energy usage for optimal management of their home environment. Additionally, the unit’s compatibility with Smart Thermostats enhances its efficiency, facilitating further integration into a modern smart home setup.

Built for durability, the Bryant 312AAV/JAV features a robust construction that includes a galvanized steel cabinet designed to withstand harsh weather conditions. The rust-resistant finish not only prolongs the life of the unit but also ensures it maintains a sleek, attractive appearance. Quiet operation is another hallmark of this model; it operates at a low noise level, providing comfort without disruptive sound.

Moreover, this model employs environmentally friendly refrigerants, aligning with modern standards for eco-friendly cooling solutions. The 312AAV/JAV is designed with filters that provide superior air quality by effectively capturing dust and allergens, contributing to a healthier indoor environment.

In summary, the Bryant 312AAV/JAV air conditioning unit represents a blend of efficiency, technology, and durability. With its impressive energy-saving capabilities, smart connectivity, silent operation, and high-quality construction, it stands out as a top choice for those seeking reliable cooling solutions for their homes or light commercial settings. Whether for new installations or replacements, the 312AAV/JAV is designed to deliver exceptional performance while prioritizing comfort and sustainability.