Bryant 120 Filter Arrangement Carbon Monoxide Poisoning Hazard, AIR Ducts, General Requirements

Page 15

LINE CONTACT ONLY PERMISSIBLE BETWEEN

LINES FORMED BY INTERSECTIONS OF

THE TOP AND TWO SIDES OF THE FURNACE

JACKET AND BUILDING JOISTS,

STUDS, OR FRAMING.

GAS

ENTRY

17 3/4

SHEET

METAL

22

EQUIPMENT MANUAL

 

SHUT-OFF GAS VALVE

 

SEDIMENT

UNION

TRAP

 

17 3/4OVER ALL

43/4UNDER DOOR

1UNDER FURNACE

 

TYPE-B

EXTEND OUT 12OUT

 

VENT

 

FROM FACE OF DOOR

6

MIN*

30-IN. MIN

 

 

 

 

* WHEN USED WITH

 

 

 

 

 

WORK AREA

 

 

SINGLE WALL VENT

 

 

 

 

 

 

 

 

 

 

CONNECTIONS

 

 

 

 

A03177

312A

Fig. 17 - Typical Attic Installation

Not all horizontal furnaces are approved for side return air connections. (See Fig. 20.)

FILTER ARRANGEMENT

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury, or death.

Never operate a furnace without a filter or with filter access door removed.

There are no provisions for an internal filter rack in these furnaces. An external filter rack is required.

This furnace is shipped with a factory-supplied Media Filter Cabinet. The Media Filter Cabinet uses either a factory-supplied standard 1-inch filter or 4-inch wide Media Filter which can be purchased separately.

Refer to the instructions supplied with Media Cabinet for assembly and installation options.

AIR DUCTS

General Requirements

The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure. The furnace airflow rates are provided in Table 5-Air Delivery CFM (With Filter).

When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.

Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and return-duct connections to furnace with code approved tape or duct sealer.

NOTE: Flexible connections should be used between ductwork and furnace to prevent transmission of vibration.

Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.

Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.

Ductwork Acoustical Treatment

NOTE: Metal duct systems that do not have a 90_ elbow and 10 ft of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.

Supply Air Connections

For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.

Upflow and Horizontal Furnaces

Connect supply-air duct to flanges on furnace supply-air outlet. Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.) The supply-air duct must be connected to ONLY the furnace supply-outlet-air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace main casing.

15

Image 15
Contents Ama Safety Considerations Furnace Reliability HazardCUT Hazard Size DimensionsIntroduction Width Bottom Flue CabinetInstallation Codes and Standards Electrostatic Discharge ESD Precautions ProcedureLocation GeneralCarbon Monoxide Poisoning and Unit Damage Hazard Location Relative to Cooling Equipment FIRE, Injury or Death HazardFire Hazard Property Damage HazardOutdoor Combustion Air Method AIR for Combustion VentilationFurnace Corrosion Hazard Carbon Monoxide Poisoning HazardAir for Combustion, Ventilation and Dilution for Outdoors Upflow Installation InstallationSuspended Furnace Support Downflow InstallationHorizontal Installation FIRE, EXPLOSION, and Carbon Monoxide Poisoning HazardRoll-Out Protection Floor and Plenum Opening DimensionsOpening dimensions Furnace Plenum Opening Floor Opening CasingWidth Horizontal Unit Suspension Ductwork Acoustical Treatment Supply Air Connections Filter Arrangement Carbon Monoxide Poisoning HazardAIR Ducts General RequirementsSpeed External Static Pressure IN. WC Size Inlet Air Delivery CFM With Filter2380 2285 2200 2085 1970 1835 GAS Piping Fire or Explosion Hazard Air Delivery CFM With Filter*Downflow Furnaces Return Air ConnectionsUpflow Return Air Configurations and Restrictions Furnace Damage Hazard Maximum Capacity of PipeFurnace MAY not Operate Hazard WiringElectrical Connections Electrical Shock and Fire Hazard Electrical Shock HazardElectrical Data BOX RelocationElectrical Connection to J-BOX Fire or Electrical Shock Hazard Power Cord Installation in Furnace J-BOXBX. Cable Installation in Furnace J-BOX Electrical Box on Furnace Casing Side. See FigTwo-Stage Furnace with Two-Speed Air Conditioner See notes 2, 11, and 12 on the page following these figures Venting AccessoriesMasonry Chimney Requirements General Venting RequirementsChimney Inspection Chart Vent Height Internal Area of Chimney Appliance Application RequirementsUpflow Application-Vent Elbow Up Downflow Application-Vent Elbow Up Horizontal Right Application Vent Elbow Right Orientation Tion PUTBTUH/HR Diameter Height FT Furnace Vent OrientaBurn Hazard Rounded End of KnockoutFire and Explosion Hazard START-UP, ADJUSTMENT, and Safety CheckStart-Up Procedures GeneralAltitude Derate Multiplier for U.S.A AdjustmentsStage Furnace Setup Switch Description U.SRedundant Automatic Gas Control Valve Gas Rate cu ft/hr Furnace Overheating HazardSeconds Size of Test Dial For Revolution Color Speed AS Shipped Speed SelectionCheck Safety Controls Stage Furnace Blower OFF delay Setup SwitchDesired Heating Mode Setup Switch Blower OFF Delay SEC Checklist Gravity Altitude RangeSpecific Gravity of Natural GAS BTUH/CU6001 to Specific Gravity of Natural GAS Altitude Range BTUH/CU FTSpecific Gravity of Natural GAS Altitude Range Heat Value Specific Gravity of Natural GAS Heat Value AT Altitude Service and Maintenance ProceduresElectrical SHOCK, Fire or Explosion Hazard FIRE, Personal Injury and Unit DamageUnit Operation Hazard Care and MaintenanceElectrical Controls and Wiring Electrical Shock Hazard IntroductionService Wiring Diagram Furnace Filter Size Casing Cleaning AND/OR Replacing AIR FilterFilter size information Blower Motor and Wheel Electrical Shock HazardUnit Damage Hazard Cleaning Heat ExchangerIgniter Position Top View Sequence of OperationTwo-Stage Heating Adaptive mode with Single-Stage Thermostat Single-Stage Thermostat and Two-Speed Cooling Adaptive Mode Thermidistat ModeSingle-Speed Cooling Wiring Diagrams TroubleshootingContinuous Blower Mode Troubleshooting Guide 2-Speed Blocked vent shutoff switch used in Chimney Adapter Kit Page Catalog No. II312A---45---8

120 specifications

The Bryant 120 is a remarkable system designed for residential and commercial heating and cooling needs, showcasing an impressive blend of efficiency, reliability, and advanced technology. As a part of Bryant's extensive line of HVAC solutions, the Bryant 120 stands out with its features and performance, making it an ideal choice for those seeking comfort year-round.

One of the main features of the Bryant 120 is its exceptional energy efficiency. It boasts a high Seasonal Energy Efficiency Ratio (SEER) rating, enabling homeowners to save on energy costs while enjoying consistent temperature control. This efficiency is aided by its variable-speed compressor, which allows the system to adjust its output based on current requirements, optimizing both energy consumption and comfort.

In terms of technology, the Bryant 120 incorporates advanced controls that enhance user experience and system performance. The system comes equipped with smart thermostats that allow homeowners to monitor and adjust their environment remotely. These thermostats not only provide convenience but also help in optimizing energy usage by learning the household's heating and cooling patterns.

Another characteristic of the Bryant 120 is its durable construction. The unit is built to withstand various weather conditions, featuring a robust cabinet and components designed for longevity. This durability ensures that homeowners can rely on the system for years without the need for frequent repairs or replacements.

Noise levels are also a critical consideration in HVAC systems, and the Bryant 120 addresses this with its quiet operation. The system is designed to minimize sound output, making it suitable for residential areas where noise can be a concern. This is particularly beneficial for nighttime use, providing a comfortable sleeping environment.

Additionally, the Bryant 120 supports eco-friendly refrigerants that comply with environmental standards, contributing to a reduction in greenhouse gas emissions. This commitment to sustainability reflects Bryant's dedication to creating products that are not only effective but also responsible.

Overall, the Bryant 120 encapsulates a harmonious balance of efficiency, advanced technology, durability, and quiet operation. Whether for a new installation or a replacement, the Bryant 120 presents an ideal solution to meet diverse heating and cooling requirements, enhancing comfort while prioritizing energy savings and environmental responsibility.