Bryant 120 instruction manual AIR for Combustion Ventilation, Furnace Corrosion Hazard

Page 8

312A

equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.

AIR FOR COMBUSTION AND

VENTILATION

Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:

U.S. installations: Section 8.3 of the NFGC, Air for Combustion and Ventilation, and applicable provisions of the local building codes.

Canadian installations: Part 8 of the CAN/CSA-B149.1-05, Venting Systems and Air Supply for Appliances and all authorities having jurisdiction.

!CAUTION

FURNACE CORROSION HAZARD

Failure to follow this caution may result in furnace damage.

Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of make-up air is available.

The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.

SSpaces having less than 50 cubic feet per 1,000 Btuh require the Outdoor Combustion Air Method.

SSpaces having at least 50 cubic feet per 1,000 Btuh may use the Indoor Combustion Air, Standard or Known Air Infiltration Method.

Outdoor Combustion Air Method

1.Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent horihorizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.

2.Fig. 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.

a.One opening MUST commence within 12 in. (300 mm) of the ceiling and the second opening MUST commence within 12 in. (300 mm) of the floor.

b.Size openings and ducts per Fig. 7 and Table 2.

c.TWO HORIZONTAL DUCTS require 1 square inch of free area per 2,000 Btuh (1,100 mm2/kW) of combined input for all gas appliances in the space per Fig. 7 and Table 2.

d.TWO OPENINGS OR VERTICAL DUCTS require 1 square inch of free area per 4,000 Btuh (550 mm2/kW) for combined input of all gas appliances in the space per Fig. 7 and Table 2.

3.ONE OUTDOOR OPENING requires:

a.1 square inch of free area per 3,000 Btuh (734 mm2/kW) for combined input of all gas appliances in the space per Table 2 and

b.Not less than the sum of the areas of all vent connectors in the space.

Table 2 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors

 

 

TWO HORIZONTAL DUCTS

 

SINGLE DUCT OR OPENING

TWO OPENINGS OR VERTICAL

 

 

 

DUCTS

 

 

 

 

 

 

 

 

 

 

 

FURNACE

 

(1 SQ. IN./2,000 BTUH)

 

(1 SQ. IN./3,000 BTUH)

(1 SQ. IN./4,000 BTUH)

INPUT

 

(1,100 SQ. MM/KW)

 

 

(734 SQ. MM/KW)

(550 SQ. MM/KW)

(BTUH)

 

 

 

 

 

 

 

 

 

 

 

 

Free Area of

Round Duct

Free Area of

 

Round Duct

Free Area of

 

Round Duct

 

Opening and Duct

Opening and Duct

Opening and Duct

 

 

(in. Dia)

 

(in. Dia)

 

(In. Dia)

 

 

(Sq. In.)

 

(sq. In.)

 

(Sq. In.)

 

 

 

 

 

 

 

 

 

 

44,000

 

22

 

6

 

14.7

 

5

11

 

4

66,000

 

33

 

7

 

22

 

6

16.5

 

5

88,000

 

44

 

8

 

29.3

 

7

22

 

6

110,000

 

55

 

9

 

36.7

 

7

27.5

 

6

132,000

 

66

 

10

 

44

 

8

33

 

7

154,000

 

77

 

10

 

51.3

 

9

38.5

 

8

FURNACE

 

WATER HEATER

 

 

TOTAL INPUT

 

 

 

 

 

110,000

+

30,000

=

(140,000 divided by 4,000)

=

35.0 Sq. In. for each two Vertical Ducts or Openings

66,000

+

40,000

=

(106,000 divided by 3,000)

=

35.3 Sq. In. for a Single Duct or Opening

88,000

+

30,000

=

(118,000 divided by 2,000)

=

59.0 Sq. In. for each of two Horizontal Ducts

8

Image 8
Contents Ama CUT Hazard Safety ConsiderationsFurnace Reliability Hazard Dimensions IntroductionWidth Bottom Flue Cabinet SizeInstallation Electrostatic Discharge ESD Precautions Procedure Codes and StandardsCarbon Monoxide Poisoning and Unit Damage Hazard LocationGeneral FIRE, Injury or Death Hazard Fire HazardProperty Damage Hazard Location Relative to Cooling EquipmentAIR for Combustion Ventilation Furnace Corrosion HazardCarbon Monoxide Poisoning Hazard Outdoor Combustion Air MethodAir for Combustion, Ventilation and Dilution for Outdoors Installation Upflow InstallationDownflow Installation Horizontal InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportFloor and Plenum Opening Dimensions Roll-Out ProtectionWidth Opening dimensionsFurnace Plenum Opening Floor Opening Casing Horizontal Unit Suspension Filter Arrangement Carbon Monoxide Poisoning Hazard AIR DuctsGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsAir Delivery CFM With Filter Speed External Static Pressure IN. WC Size Inlet2380 2285 2200 2085 1970 1835 Air Delivery CFM With Filter* Downflow FurnacesReturn Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Maximum Capacity of Pipe Furnace Damage HazardWiring Electrical Connections Electrical Shock and Fire HazardElectrical Shock Hazard Furnace MAY not Operate HazardElectrical Connection to J-BOX Electrical DataBOX Relocation Power Cord Installation in Furnace J-BOX BX. Cable Installation in Furnace J-BOXElectrical Box on Furnace Casing Side. See Fig Fire or Electrical Shock HazardTwo-Stage Furnace with Two-Speed Air Conditioner See notes 2, 11, and 12 on the page following these figures Accessories VentingGeneral Venting Requirements Masonry Chimney RequirementsChimney Inspection Chart Appliance Application Requirements Vent Height Internal Area of ChimneyUpflow Application-Vent Elbow Up Downflow Application-Vent Elbow Up Horizontal Right Application Vent Elbow Right Furnace Vent Orienta Orientation Tion PUTBTUH/HR Diameter Height FTRounded End of Knockout Burn HazardSTART-UP, ADJUSTMENT, and Safety Check Start-Up ProceduresGeneral Fire and Explosion HazardAdjustments Stage Furnace Setup Switch DescriptionU.S Altitude Derate Multiplier for U.S.ARedundant Automatic Gas Control Valve Seconds Size of Test Dial For Revolution Gas Rate cu ft/hrFurnace Overheating Hazard Speed Selection Color Speed AS ShippedDesired Heating Mode Setup Switch Blower OFF Delay SEC Check Safety ControlsStage Furnace Blower OFF delay Setup Switch Checklist Altitude Range Specific Gravity of Natural GASBTUH/CU Gravity6001 to Specific Gravity of Natural GAS Altitude Range Heat Value Specific Gravity of Natural GAS Altitude RangeBTUH/CU FT Service and Maintenance Procedures Electrical SHOCK, Fire or Explosion HazardFIRE, Personal Injury and Unit Damage Specific Gravity of Natural GAS Heat Value AT AltitudeCare and Maintenance Electrical Controls and Wiring Electrical Shock HazardIntroduction Unit Operation HazardService Wiring Diagram Cleaning AND/OR Replacing AIR Filter Filter size informationBlower Motor and Wheel Electrical Shock Hazard Furnace Filter Size CasingCleaning Heat Exchanger Unit Damage HazardSequence of Operation Igniter Position Top ViewTwo-Stage Heating Adaptive mode with Single-Stage Thermostat Single-Speed Cooling Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeThermidistat Mode Continuous Blower Mode Wiring DiagramsTroubleshooting Troubleshooting Guide 2-Speed Blocked vent shutoff switch used in Chimney Adapter Kit Page Catalog No. II312A---45---8

120 specifications

The Bryant 120 is a remarkable system designed for residential and commercial heating and cooling needs, showcasing an impressive blend of efficiency, reliability, and advanced technology. As a part of Bryant's extensive line of HVAC solutions, the Bryant 120 stands out with its features and performance, making it an ideal choice for those seeking comfort year-round.

One of the main features of the Bryant 120 is its exceptional energy efficiency. It boasts a high Seasonal Energy Efficiency Ratio (SEER) rating, enabling homeowners to save on energy costs while enjoying consistent temperature control. This efficiency is aided by its variable-speed compressor, which allows the system to adjust its output based on current requirements, optimizing both energy consumption and comfort.

In terms of technology, the Bryant 120 incorporates advanced controls that enhance user experience and system performance. The system comes equipped with smart thermostats that allow homeowners to monitor and adjust their environment remotely. These thermostats not only provide convenience but also help in optimizing energy usage by learning the household's heating and cooling patterns.

Another characteristic of the Bryant 120 is its durable construction. The unit is built to withstand various weather conditions, featuring a robust cabinet and components designed for longevity. This durability ensures that homeowners can rely on the system for years without the need for frequent repairs or replacements.

Noise levels are also a critical consideration in HVAC systems, and the Bryant 120 addresses this with its quiet operation. The system is designed to minimize sound output, making it suitable for residential areas where noise can be a concern. This is particularly beneficial for nighttime use, providing a comfortable sleeping environment.

Additionally, the Bryant 120 supports eco-friendly refrigerants that comply with environmental standards, contributing to a reduction in greenhouse gas emissions. This commitment to sustainability reflects Bryant's dedication to creating products that are not only effective but also responsible.

Overall, the Bryant 120 encapsulates a harmonious balance of efficiency, advanced technology, durability, and quiet operation. Whether for a new installation or a replacement, the Bryant 120 presents an ideal solution to meet diverse heating and cooling requirements, enhancing comfort while prioritizing energy savings and environmental responsibility.