Bryant 120 Electrical Connections Electrical Shock and Fire Hazard, Electrical Shock Hazard

Page 21

FIELD 24-VOLT WIRING

FIELD 115-, 208/230-, 460-VOLT WIRING

FACTORY 24-VOLT WIRING

FACTORY 115-VOLT WIRING

 

NOTE 2

1-STAGE

 

 

 

 

FIVE

W C Y

R G THERMOSTAT

FIELD-SUPPLIED

 

TERMINALS

WIRE

 

FUSED DISCONNECT

 

 

THREE-WIRE

HEATING-

ONLY

BLK

BLK

 

W2

 

 

WHT

WHT

 

COM

 

 

 

 

 

W/W1

 

GND

 

Y/Y2

115-VOLT FIELD-

JUNCTION

 

 

SUPPLIED

BOX

R

 

FUSED

CONTROL

 

DISCONNECT

BOX

G

 

 

 

24-VOLT

 

 

TERMINAL

 

 

 

BLOCK

 

 

FURNACE

 

208/230- OR

 

460-VOLT

 

THREE

 

PHASE

 

208/230-

NOTE 1

VOLT

 

SINGLE

 

PHASE

 

GND

 

CONDENSING

 

UNIT

NOTES: 1. Connect Y/Y2-terminal as shown for proper operation.

2.Some thermostats require a "C" terminal connection as shown.

3.If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.

312A

A95236

Fig. 24 - Field Wiring Diagram

Piping should be pressure and leak tested in accordance with NFGC in the United States or CAN/CSA-B149.1-05 in Canada, local, and national plumbing and gas codes before the furnace has been connected. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.

If pressure exceeds 0.5 psig (14-in. wc), gas supply pipe must be disconnected from furnace and capped before and during supply pipe pressure test. If test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on furnace gas control valve and accessible manual equipment shutoff valve before and during supply pipe pressure test. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.

The gas supply pressure shall be within the maximum and minimum inlet supply pressures marked on the rating plate with the furnace burners ON and OFF.

ELECTRICAL CONNECTIONS

!WARNING

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personal injury, death, or property damage.

The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-2006 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer’s ratings for proper wire gauge. Do not use gas piping as an electrical ground.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Blower access panel door switch opens 115-v power to control. No component operation can occur. Do not bypass or close switch with panel removed.

See Fig. 24 for field wiring diagram showing typical field 115-v wiring. Check all factory and field electrical connections for tightness.

Field-supplied wiring shall conform with the limitations of 63_F (33_C) rise.

!CAUTION

FURNACE MAY NOT OPERATE HAZARD

Failure to follow this caution may result in intermittent furnace operation.

Furnace control must be grounded for proper operation or else control will lock out. Control must remain grounded through green/yellow wire routed to gas valve and manifold bracket screw.

115-V WIRING

Verify that the voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 7 for equipment electrical specifications.

21

Image 21
Contents Ama Safety Considerations Furnace Reliability HazardCUT Hazard Introduction DimensionsWidth Bottom Flue Cabinet SizeInstallation Codes and Standards Electrostatic Discharge ESD Precautions ProcedureLocation GeneralCarbon Monoxide Poisoning and Unit Damage Hazard Fire Hazard FIRE, Injury or Death HazardProperty Damage Hazard Location Relative to Cooling EquipmentFurnace Corrosion Hazard AIR for Combustion VentilationCarbon Monoxide Poisoning Hazard Outdoor Combustion Air MethodAir for Combustion, Ventilation and Dilution for Outdoors Upflow Installation InstallationHorizontal Installation Downflow InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportRoll-Out Protection Floor and Plenum Opening DimensionsOpening dimensions Furnace Plenum Opening Floor Opening CasingWidth Horizontal Unit Suspension AIR Ducts Filter Arrangement Carbon Monoxide Poisoning HazardGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsSpeed External Static Pressure IN. WC Size Inlet Air Delivery CFM With Filter2380 2285 2200 2085 1970 1835 Downflow Furnaces Air Delivery CFM With Filter*Return Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Furnace Damage Hazard Maximum Capacity of PipeElectrical Connections Electrical Shock and Fire Hazard WiringElectrical Shock Hazard Furnace MAY not Operate HazardElectrical Data BOX RelocationElectrical Connection to J-BOX BX. Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXElectrical Box on Furnace Casing Side. See Fig Fire or Electrical Shock HazardTwo-Stage Furnace with Two-Speed Air Conditioner See notes 2, 11, and 12 on the page following these figures Venting AccessoriesMasonry Chimney Requirements General Venting RequirementsChimney Inspection Chart Vent Height Internal Area of Chimney Appliance Application RequirementsUpflow Application-Vent Elbow Up Downflow Application-Vent Elbow Up Horizontal Right Application Vent Elbow Right Orientation Tion PUTBTUH/HR Diameter Height FT Furnace Vent OrientaBurn Hazard Rounded End of KnockoutStart-Up Procedures START-UP, ADJUSTMENT, and Safety CheckGeneral Fire and Explosion HazardStage Furnace Setup Switch Description AdjustmentsU.S Altitude Derate Multiplier for U.S.ARedundant Automatic Gas Control Valve Gas Rate cu ft/hr Furnace Overheating HazardSeconds Size of Test Dial For Revolution Color Speed AS Shipped Speed SelectionCheck Safety Controls Stage Furnace Blower OFF delay Setup SwitchDesired Heating Mode Setup Switch Blower OFF Delay SEC Checklist Specific Gravity of Natural GAS Altitude RangeBTUH/CU Gravity6001 to Specific Gravity of Natural GAS Altitude Range BTUH/CU FTSpecific Gravity of Natural GAS Altitude Range Heat Value Electrical SHOCK, Fire or Explosion Hazard Service and Maintenance ProceduresFIRE, Personal Injury and Unit Damage Specific Gravity of Natural GAS Heat Value AT AltitudeElectrical Controls and Wiring Electrical Shock Hazard Care and MaintenanceIntroduction Unit Operation HazardService Wiring Diagram Filter size information Cleaning AND/OR Replacing AIR FilterBlower Motor and Wheel Electrical Shock Hazard Furnace Filter Size CasingUnit Damage Hazard Cleaning Heat ExchangerIgniter Position Top View Sequence of OperationTwo-Stage Heating Adaptive mode with Single-Stage Thermostat Single-Stage Thermostat and Two-Speed Cooling Adaptive Mode Thermidistat ModeSingle-Speed Cooling Wiring Diagrams TroubleshootingContinuous Blower Mode Troubleshooting Guide 2-Speed Blocked vent shutoff switch used in Chimney Adapter Kit Page Catalog No. II312A---45---8

120 specifications

The Bryant 120 is a remarkable system designed for residential and commercial heating and cooling needs, showcasing an impressive blend of efficiency, reliability, and advanced technology. As a part of Bryant's extensive line of HVAC solutions, the Bryant 120 stands out with its features and performance, making it an ideal choice for those seeking comfort year-round.

One of the main features of the Bryant 120 is its exceptional energy efficiency. It boasts a high Seasonal Energy Efficiency Ratio (SEER) rating, enabling homeowners to save on energy costs while enjoying consistent temperature control. This efficiency is aided by its variable-speed compressor, which allows the system to adjust its output based on current requirements, optimizing both energy consumption and comfort.

In terms of technology, the Bryant 120 incorporates advanced controls that enhance user experience and system performance. The system comes equipped with smart thermostats that allow homeowners to monitor and adjust their environment remotely. These thermostats not only provide convenience but also help in optimizing energy usage by learning the household's heating and cooling patterns.

Another characteristic of the Bryant 120 is its durable construction. The unit is built to withstand various weather conditions, featuring a robust cabinet and components designed for longevity. This durability ensures that homeowners can rely on the system for years without the need for frequent repairs or replacements.

Noise levels are also a critical consideration in HVAC systems, and the Bryant 120 addresses this with its quiet operation. The system is designed to minimize sound output, making it suitable for residential areas where noise can be a concern. This is particularly beneficial for nighttime use, providing a comfortable sleeping environment.

Additionally, the Bryant 120 supports eco-friendly refrigerants that comply with environmental standards, contributing to a reduction in greenhouse gas emissions. This commitment to sustainability reflects Bryant's dedication to creating products that are not only effective but also responsible.

Overall, the Bryant 120 encapsulates a harmonious balance of efficiency, advanced technology, durability, and quiet operation. Whether for a new installation or a replacement, the Bryant 120 presents an ideal solution to meet diverse heating and cooling requirements, enhancing comfort while prioritizing energy savings and environmental responsibility.