Bryant 120 Single-Speed Cooling, Single-Stage Thermostat and Two-Speed Cooling Adaptive Mode

Page 53

low-heat and high-heat pressure switch contacts LPS and HPS are open, and starts the inducer motor IDM in high-speed.

The start up and shut down functions and delays described in item 1. above apply to the 2-stage heating mode as well, except for switching from low- to high-Heat and vice versa.

a.Switching from Low- to High-Heat-If the thermostat R-to- W1 circuit is closed and the R-to-W2 circuit closes, the furnace control CPU will switch the inducer motor IDM speed from low to high. The high-heat pressure switch relay HPSR is de-energized to close the NC contact. When sufficient pressure is available the high-heat pressure switch HPS closes, and the high-heat gas valve solenoid GV-HI is energized. The blower motor BLWM will switch to HI HEAT speed five seconds after the R-to-W2 circuit closes.

b.Switching from High- to Low-Heat-If the thermostat R-to-W2 circuit opens, and the R-to-W1 circuit remains closed, the furnace control CPU will switch the inducer motor IDM speed from high to low. The high-heat pressure switch relay HPSR is energized to open the NC contact and de-energize the high-heat gas valve solenoid GV-HI.When the inducer motor IDM reduces pressure sufficiently, the high-heat pressure switch HPS will open. The gas valve solenoid GV-M will remain energized as long as the low-heat pressure switch LPS remains closed. The blower motor BLWM will switch to LO HEAT speed five seconds after the R-to-W2 circuit opens.

3.Cooling Mode-The thermostat “calls for cooling.”

a.Single-Speed Cooling-

(See Fig. 28 for thermostat connections)

The thermostat closes the R-to-G-and-Y circuits. The R-to- Y circuit starts the outdoor unit, and the R-to-G-and-Y/Y2 circuits start the furnace blower motor BLWM on COOL speed.

The electronic air cleaner terminal EAC-1 is energized with 115 vac when the blower motor BLWM is operating.

When the thermostat is satisfied, the R-to-G and-Y circuits are opened. The outdoor unit will stop, and the furnace blower motor BLWM will continue operating on the COOL speed for an additional 90 seconds. Jumper Y/Y2 to DHUM to reduce the cooling off-delay to 5 seconds. (See Fig. 25.)

b.Single-Stage Thermostat and Two-Speed Cooling (Adaptive Mode)

(See Fig. 33 for thermostat connections)

This furnace can operate a two-speed cooling unit with a single-stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low-cooling or high-cooling operation. This selection is based upon the stored history of the length of previous cooling period of the single-stage thermostat.

NOTE: The air conditioning relay disable jumper ACRDJ must be connected to enable the adaptive cooling mode in response to a call for cooling. (See Fig. 34.) When ACRDJ is in place, the furnace control CPU can turn on the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high-cooling.

The furnace control CPU can start up the cooling unit in either low- or high-cooling. If starting up in low-cooling, the furnace control CPU determines the low-cooling on-time (from 0 to 20 minutes) which is permitted before switching to high-cooling. If the power is interrupted, the stored history is erased and the furnace control CPU will select low-cooling for up to 20 minutes and then energize the air conditioning relay ACR to energize the

Y/Y2 terminal and switch the outdoor unit to high-cooling, as long as the thermostat continues to call for cooling. Subsequent selection is based on stored history of the thermostat cycle times. The wall thermostat “calls for cooling”, closing the R-to-G-and-Y circuits. The R-to-Y1 circuit starts the outdoor unit on low-cooling speed, and the R-to-G-and-Y1 circuits starts the furnace blower motor BLWM at low-cool speed (same speed as LO HEAT).

If the furnace control CPU switches from low-cooling to high-cooling, the furnace control CPU will energize the air conditioning relay ACR. When the air conditioning relay ACR is energized the R-to-Y1-and-Y2 circuits switch the outdoor unit to high-cooling speed, and the R-to-G-and-Y1-and-Y/Y2 circuits switch the furnace blower motor BLWM to COOL speed.

NOTE: When transitioning from low-cooling to high-cooling the outdoor unit compressor will shut down for 1 minute while the BLWM continues to run at low-cool speed (same speed as LO-HEAT) until the outdoor unit compressor comes back on at high speed.

The electronic air cleaner terminal EAC-1 is energized with 115 vac whenever the blower motor BLWM is operating. When the thermostat is satisfied, the R-to-G-and-Y circuit are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC-1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to 5 seconds. (See Fig. 34.)

c.Two-Stage Thermostat and Two-Speed Cooling (See Fig. 32 for thermostat connections)

NOTE: The air conditioning relay disable jumper ACRDJ must be disconnected to allow thermostat control of the outdoor unit staging. (See Fig. 34.)

The thermostat closes the R-to-G-and-Y1 circuits for low-cooling or closes the R-to-G-and-Y1-and-Y2 circuits for high-cooling. The R-to-Y1 circuit starts the outdoor unit on low-cooling speed, and the R-to-G-and-Y1 circuit starts the furnace blower motor BLWM on low-cool speed (same speed as LO HEAT). The R-to-Y1-and-Y2 circuits start the outdoor unit on high-cooling speed, and the R-to-G-and- Y/Y2 circuits start the furnace blower motor BLWM on COOL speed. The electronic air cleaner terminal EAC-1 is energized with 115 vac whenever the blower motor BLWM is operating. When the thermostat is satisfied, the R-to-G-and-Y1 or R-to-G-and-Y1-and-Y2 circuits are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC-1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to 5 seconds. (See Fig. 34.)

4.Thermidistat Mode

(See Fig. 27 - 29 for Thermidistat connections) The dehumidification output, DHUM on the Thermidistat should be connected to the furnace control thermostat terminal DHUM. When there is a dehumidify demand, the DHUM input is activated, which means 24 vac signal is removed from the DHUM input terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned ON when no dehumidify demand exists. Once 24 vac is detected by the furnace control on the DHUM input, the furnace control operates in Thermidistat mode. If the DHUM input is low for more than 48 hours, the furnace control reverts back to non-Thermidistat mode.

The cooling operation described in item 3. above also applies to operation with a Thermidistat. The exceptions are listed below:

a.Low cooling - When the R-to-G-and-Y1 circuit is closed and there is a demand for dehumidification,the furnace blower motor BLWM will continue running at low-cool speed (same speed as LO HEAT).

312A

53

Image 53
Contents Ama CUT Hazard Safety ConsiderationsFurnace Reliability Hazard Introduction DimensionsWidth Bottom Flue Cabinet SizeInstallation Codes and Standards Electrostatic Discharge ESD Precautions ProcedureCarbon Monoxide Poisoning and Unit Damage Hazard LocationGeneral Fire Hazard FIRE, Injury or Death HazardProperty Damage Hazard Location Relative to Cooling EquipmentFurnace Corrosion Hazard AIR for Combustion VentilationCarbon Monoxide Poisoning Hazard Outdoor Combustion Air MethodAir for Combustion, Ventilation and Dilution for Outdoors Upflow Installation InstallationHorizontal Installation Downflow InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportRoll-Out Protection Floor and Plenum Opening DimensionsWidth Opening dimensionsFurnace Plenum Opening Floor Opening Casing Horizontal Unit Suspension AIR Ducts Filter Arrangement Carbon Monoxide Poisoning HazardGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsSpeed External Static Pressure IN. WC Size Inlet Air Delivery CFM With Filter2380 2285 2200 2085 1970 1835 Downflow Furnaces Air Delivery CFM With Filter*Return Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Furnace Damage Hazard Maximum Capacity of PipeElectrical Connections Electrical Shock and Fire Hazard WiringElectrical Shock Hazard Furnace MAY not Operate HazardElectrical Connection to J-BOX Electrical DataBOX Relocation BX. Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXElectrical Box on Furnace Casing Side. See Fig Fire or Electrical Shock HazardTwo-Stage Furnace with Two-Speed Air Conditioner See notes 2, 11, and 12 on the page following these figures Venting AccessoriesMasonry Chimney Requirements General Venting RequirementsChimney Inspection Chart Vent Height Internal Area of Chimney Appliance Application RequirementsUpflow Application-Vent Elbow Up Downflow Application-Vent Elbow Up Horizontal Right Application Vent Elbow Right Orientation Tion PUTBTUH/HR Diameter Height FT Furnace Vent OrientaBurn Hazard Rounded End of KnockoutStart-Up Procedures START-UP, ADJUSTMENT, and Safety CheckGeneral Fire and Explosion HazardStage Furnace Setup Switch Description AdjustmentsU.S Altitude Derate Multiplier for U.S.ARedundant Automatic Gas Control Valve Seconds Size of Test Dial For Revolution Gas Rate cu ft/hrFurnace Overheating Hazard Color Speed AS Shipped Speed SelectionDesired Heating Mode Setup Switch Blower OFF Delay SEC Check Safety ControlsStage Furnace Blower OFF delay Setup Switch Checklist Specific Gravity of Natural GAS Altitude RangeBTUH/CU Gravity6001 to Specific Gravity of Natural GAS Altitude Range Heat Value Specific Gravity of Natural GAS Altitude RangeBTUH/CU FT Electrical SHOCK, Fire or Explosion Hazard Service and Maintenance ProceduresFIRE, Personal Injury and Unit Damage Specific Gravity of Natural GAS Heat Value AT AltitudeElectrical Controls and Wiring Electrical Shock Hazard Care and MaintenanceIntroduction Unit Operation HazardService Wiring Diagram Filter size information Cleaning AND/OR Replacing AIR FilterBlower Motor and Wheel Electrical Shock Hazard Furnace Filter Size Casing Unit Damage Hazard Cleaning Heat ExchangerIgniter Position Top View Sequence of OperationTwo-Stage Heating Adaptive mode with Single-Stage Thermostat Single-Speed Cooling Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeThermidistat Mode Continuous Blower Mode Wiring DiagramsTroubleshooting Troubleshooting Guide 2-Speed Blocked vent shutoff switch used in Chimney Adapter Kit Page Catalog No. II312A---45---8