Bryant 120 instruction manual Adjustments, Stage Furnace Setup Switch Description, U.S

Page 36

Table 10 – 2-Stage Furnace Setup Switch Description

 

 

 

 

SETUP

SWITCH

NORMAL

DESCRIPTION

SWITCH NO.

NAME

POSITION

OF USE

 

 

 

When OFF, allows 2--- stage operation with a single stage thermostat.

SW--- 1

Adaptive Heat Mode

OFF

Turn ON when using 2 stage thermostat to allow Low Heat opera---

tion when R to W/W1 closes and High Heat operation when R to

 

 

 

 

 

 

W/W1 and W2 close.

SW--- 2

Blower OFF delay

ON or OFF

Control blower OFF delay time. Used in conjunction with SW--- 3.

See Table 14.

 

 

 

SW--- 3

Blower OFF delay

ON or OFF

Control blower OFF delay time. Used in conjunction with SW--- 2.

See Table 14.

 

 

 

312A

Step 3 — Adjustments

!WARNING

FIRE HAZARD

Failure to follow this warning could result in injury, death and/or property damage.

DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess over-fire and heat exchanger failures.

!CAUTION

FURNACE DAMAGE HAZARD

Failure to follow this caution may result in reduced furnace life.

DO NOT re-drill orifices. Improper drilling (burrs, out-of round holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of heat exchangers, causing failures. (See Fig. 50.)

Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft Furnace input rate must be within +/-2% of furnace rating plate input. For altitudes above 5500 ft, a field-supplied high altitude pressure switch is required.

1.Determine the correct gas input rate.

In the U.S.:

The input rating for altitudes above 2,000 ft must be re- duced by 4% for each 1,000 ft above sea level.

For installations below 2000 ft, refer to the unit rating plate.

For installations above 2000 ft, multiply the input on the rating plate by the derate multiplier in Table 11 for the cor- rect input rate.

EXAMPLE:

88,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT

 

 

Derate

 

Furnace Input Rate

Furnace Input Rate

X

Multiplier

=

at Installation

at Sea Level

 

Factor

 

Altitude

88,000

X

0.90

=

79,200

In Canada: The input rating must be reduced by 10% for altitudes of 2,000 ft to 4,500 ft above sea level by an authorized Gas Conversion Station or Dealer. To determine correct input rate for altitude, see example and use 0.90 as derate multiplier factor.

2.Determine the correct orifice and manifold pressure adjustment. All models in all positions except Low NOx

models in downflow and horizontal positions use Table 15 (22,000 BTUH per burner).

Table 11 – Altitude Derate Multiplier for U.S.A.

ALTITUDE

%

DERATE MULTIPLIER

(FT)

OF DERATE

FACTOR*

0–2000

0

1.00

2001–3000

8–12

0.90

3001–4000

12–16

0.86

4001–5000

16–20

0.82

5001–6000

20–24

0.78

6001–7000

24–28

0.74

7001–8000

28–32

0.70

8001–9000

32–36

0.66

9001–10,000

36–40

0.62

*Derate multiplier factors are based on midpoint altitude for altitude range.

Low NOx models in downflow or horizontal positions MUST use Table 16 (21,000 BTUH per burner). See input listed on rating plate.

a.Obtain average yearly gas heat value (at installed altitude) from local gas supplier.

b.Obtain average yearly gas specific gravity from local gas supplier.

c.Find installation altitude in Table 15 or 16.

d.Find closest natural gas heat value and specific gravity in Table 15 or 16

e.Follow heat value and specific gravity lines to point of intersection to find orifice size and low-and high-heat manifold pressure settings for proper operation.

f.Check and verify burner orifice size in furnace. NEVER ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.

g.Replace orifice with correct size, if required by Table 15 or 16. Use only factory-supplied orifices. See EXAMPLE 2.

EXAMPLE 2: (0-2000 ft altitude)

For 22,000 Btuh per burner application, use Table 15. Heating value = 1000 Btuh/cu ft

Specific gravity = 0.62 Therefore: Orifice No. 43*

Manifold pressure: 3.7-in. wc for high-heat 1.6-in. wc for low-heat

*Furnace is shipped with No. 43 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain proper input rate.

3.Adjust manifold pressure to obtain low fire input rate. (See Fig. 54.)

36

Image 36
Contents Ama Safety Considerations Furnace Reliability HazardCUT Hazard Dimensions IntroductionWidth Bottom Flue Cabinet SizeInstallation Electrostatic Discharge ESD Precautions Procedure Codes and StandardsLocation GeneralCarbon Monoxide Poisoning and Unit Damage Hazard FIRE, Injury or Death Hazard Fire HazardProperty Damage Hazard Location Relative to Cooling EquipmentAIR for Combustion Ventilation Furnace Corrosion HazardCarbon Monoxide Poisoning Hazard Outdoor Combustion Air MethodAir for Combustion, Ventilation and Dilution for Outdoors Installation Upflow InstallationDownflow Installation Horizontal InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportFloor and Plenum Opening Dimensions Roll-Out ProtectionOpening dimensions Furnace Plenum Opening Floor Opening CasingWidth Horizontal Unit Suspension Filter Arrangement Carbon Monoxide Poisoning Hazard AIR DuctsGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsAir Delivery CFM With Filter Speed External Static Pressure IN. WC Size Inlet2380 2285 2200 2085 1970 1835 Air Delivery CFM With Filter* Downflow FurnacesReturn Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Maximum Capacity of Pipe Furnace Damage HazardWiring Electrical Connections Electrical Shock and Fire HazardElectrical Shock Hazard Furnace MAY not Operate HazardElectrical Data BOX RelocationElectrical Connection to J-BOX Power Cord Installation in Furnace J-BOX BX. Cable Installation in Furnace J-BOXElectrical Box on Furnace Casing Side. See Fig Fire or Electrical Shock HazardTwo-Stage Furnace with Two-Speed Air Conditioner See notes 2, 11, and 12 on the page following these figures Accessories VentingGeneral Venting Requirements Masonry Chimney RequirementsChimney Inspection Chart Appliance Application Requirements Vent Height Internal Area of ChimneyUpflow Application-Vent Elbow Up Downflow Application-Vent Elbow Up Horizontal Right Application Vent Elbow Right Furnace Vent Orienta Orientation Tion PUTBTUH/HR Diameter Height FTRounded End of Knockout Burn HazardSTART-UP, ADJUSTMENT, and Safety Check Start-Up ProceduresGeneral Fire and Explosion HazardAdjustments Stage Furnace Setup Switch DescriptionU.S Altitude Derate Multiplier for U.S.ARedundant Automatic Gas Control Valve Gas Rate cu ft/hr Furnace Overheating HazardSeconds Size of Test Dial For Revolution Speed Selection Color Speed AS ShippedCheck Safety Controls Stage Furnace Blower OFF delay Setup SwitchDesired Heating Mode Setup Switch Blower OFF Delay SEC Checklist Altitude Range Specific Gravity of Natural GASBTUH/CU Gravity6001 to Specific Gravity of Natural GAS Altitude Range BTUH/CU FTSpecific Gravity of Natural GAS Altitude Range Heat Value Service and Maintenance Procedures Electrical SHOCK, Fire or Explosion HazardFIRE, Personal Injury and Unit Damage Specific Gravity of Natural GAS Heat Value AT AltitudeCare and Maintenance Electrical Controls and Wiring Electrical Shock HazardIntroduction Unit Operation HazardService Wiring Diagram Cleaning AND/OR Replacing AIR Filter Filter size informationBlower Motor and Wheel Electrical Shock Hazard Furnace Filter Size CasingCleaning Heat Exchanger Unit Damage HazardSequence of Operation Igniter Position Top ViewTwo-Stage Heating Adaptive mode with Single-Stage Thermostat Single-Stage Thermostat and Two-Speed Cooling Adaptive Mode Thermidistat ModeSingle-Speed Cooling Wiring Diagrams TroubleshootingContinuous Blower Mode Troubleshooting Guide 2-Speed Blocked vent shutoff switch used in Chimney Adapter Kit Page Catalog No. II312A---45---8

120 specifications

The Bryant 120 is a remarkable system designed for residential and commercial heating and cooling needs, showcasing an impressive blend of efficiency, reliability, and advanced technology. As a part of Bryant's extensive line of HVAC solutions, the Bryant 120 stands out with its features and performance, making it an ideal choice for those seeking comfort year-round.

One of the main features of the Bryant 120 is its exceptional energy efficiency. It boasts a high Seasonal Energy Efficiency Ratio (SEER) rating, enabling homeowners to save on energy costs while enjoying consistent temperature control. This efficiency is aided by its variable-speed compressor, which allows the system to adjust its output based on current requirements, optimizing both energy consumption and comfort.

In terms of technology, the Bryant 120 incorporates advanced controls that enhance user experience and system performance. The system comes equipped with smart thermostats that allow homeowners to monitor and adjust their environment remotely. These thermostats not only provide convenience but also help in optimizing energy usage by learning the household's heating and cooling patterns.

Another characteristic of the Bryant 120 is its durable construction. The unit is built to withstand various weather conditions, featuring a robust cabinet and components designed for longevity. This durability ensures that homeowners can rely on the system for years without the need for frequent repairs or replacements.

Noise levels are also a critical consideration in HVAC systems, and the Bryant 120 addresses this with its quiet operation. The system is designed to minimize sound output, making it suitable for residential areas where noise can be a concern. This is particularly beneficial for nighttime use, providing a comfortable sleeping environment.

Additionally, the Bryant 120 supports eco-friendly refrigerants that comply with environmental standards, contributing to a reduction in greenhouse gas emissions. This commitment to sustainability reflects Bryant's dedication to creating products that are not only effective but also responsible.

Overall, the Bryant 120 encapsulates a harmonious balance of efficiency, advanced technology, durability, and quiet operation. Whether for a new installation or a replacement, the Bryant 120 presents an ideal solution to meet diverse heating and cooling requirements, enhancing comfort while prioritizing energy savings and environmental responsibility.