Bryant 120 Air Delivery CFM With Filter, Downflow Furnaces, Return Air Connections

Page 18

312A

Table 5 - Air Delivery - CFM (With Filter)* (Cont.)

FURNACE

RETURN---AIR

SPEED

 

 

EXTERNAL STATIC PRESSURE (IN. WC)

 

 

SIZE

INLET

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

 

135--- 16 /

Bottom

High

2090

2010

1930

1835

1710

1590

1470

1335

1025

835

Med--- High

1790

1755

1705

1640

1550

1465

1360

1210

945

785

or

048135

Med--- Low

1545

1525

1500

1450

1380

1315

1215

1005

855

670

Side(s)

 

Low

1325

1320

1295

1265

1210

1150

995

865

745

540

 

 

 

Bottom

High

2485

2400

2310

2215

2110

2000

1880

1725

1535

1355

 

Med--- High

2195

2150

2090

2000

1920

1825

1720

1565

1405

1255

 

Only

Med--- Low

1880

1850

1820

1780

1715

1635

1540

1415

1290

1160

 

 

Low

1640

1635

1615

1585

1530

1465

1370

1255

1150

1040

135--- 22 /

Bottom Sides

High

--- ---

--- ---

2385

2305

2195

2085

1960

1825

1670

1465

Med--- High

2180

2145

2060

2010

1945

1865

1765

1660

1515

1325

or

066135

Med--- Low

1880

1850

1820

1780

1715

1635

1540

1415

1290

1160

1 Side & Bottom

 

Low

1640

1635

1615

1585

1530

1465

1370

1255

1150

1040

 

 

 

 

High

2320

2250

2155

2055

1970

1855

1725

1600

1450

1280

 

1 Side Only

Med--- High

2125

2065

1995

1910

1815

1710

1610

1490

1340

1175

 

Med--- Low

1845

1825

1765

1710

1650

1570

1475

1370

1240

1100

 

 

 

 

Low

1640

1620

1580

1540

1485

1410

1330

1220

1080

960

 

 

High

2465

2430

2375

2305

2230

2110

2000

1865

1725

1545

 

Bottom Only

Med--- High

2115

2105

2075

2030

1980

1910

1830

1725

1590

1425

 

Med--- Low

1800

1790

1770

1735

1695

1640

1570

1465

1345

1225

 

 

155--- 20 /

 

Low

1570

1565

1550

1525

1495

1445

1370

1270

1175

1070

060155

Both Sides Or 1

High

--- ---

--- ---

2375

2285

2200

2105

1995

1870

1730

1570

 

Side & Bottom

Med--- High

2155

2135

2095

2040

1975

1895

1790

1685

1550

1400

 

1 Side Only

High

--- ---

--- ---

2260

2180

2085

1975

1865

1740

1605

1455

 

Med--- High

2140

2095

2040

1975

1890

1810

1705

1595

1480

1325

 

 

*A filter is required for each return ---air inlet. Airflow performance included 1---in. washable filter media such as contained in factory ---authorized accessory filter

rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.

 

 

 

--- --- Indicates unstable operating conditions.

 

 

 

 

 

 

 

 

 

 

NOTE: For horizontal applications, the top-most flange may be bent past 90_ to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the coil are performed.

Downflow Furnaces

Connect supply-air duct to supply-air outlet on furnace. Bend flange inward past 90_ with wide duct pliers. (See Fig. 14.) The supply-air duct must be connected to ONLY the furnace supplyoutlet or air conditioning coil casing (when used). When installed on combustible material, supply-air duct must be connected to ONLY the accessory subbase, KGASB0201ALL, or a factory approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace casing.

Return Air Connections

!WARNING

FIRE HAZARD

Failure to follow this warning could cause personal injury, death and/or property damage.

Never connect return-air ducts to the back of the furnace. Follow instructions below.

Downflow Furnaces

The return-air duct must be connected to return-air opening (bottom inlet) as shown in Fig. 1. DO NOT cut into casing sides (left or right). Side opening is permitted for only upflow and most horizontal furnaces. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace. (See Fig. 19.) Upflow and Horizontal Furnaces The return-air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing as shown in Fig. 1. Bypass humidifier may be attached into unused return air side of the furnace casing. (See Fig. 18 and 20.) Not all

horizontal furnaces are approved for side return air connections. (See Fig. 20.)

GAS PIPING

!WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury, death, and/or property damage.

Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.

!WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury, death, and/or property damage.

Use proper length of pipe to avoid stress on gas control manifold and a gas leak.

!WARNING

FIRE OR EXPLOSION HAZARD

Failure to protect gas valve inlet from water and debris could result in death, personal injury and/or property damage.

Gas valve inlet and/or inlet pipe must remain capped until gas supply line is permanently installed to protect the valve from moisture and debris. Also, install a sediment trap in the gas supply piping at the inlet to the gas valve.

18

Image 18
Contents Ama Safety Considerations Furnace Reliability HazardCUT Hazard Width Bottom Flue Cabinet DimensionsIntroduction SizeInstallation Electrostatic Discharge ESD Precautions Procedure Codes and StandardsLocation GeneralCarbon Monoxide Poisoning and Unit Damage Hazard Property Damage Hazard FIRE, Injury or Death HazardFire Hazard Location Relative to Cooling EquipmentCarbon Monoxide Poisoning Hazard AIR for Combustion VentilationFurnace Corrosion Hazard Outdoor Combustion Air MethodAir for Combustion, Ventilation and Dilution for Outdoors Installation Upflow InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Downflow InstallationHorizontal Installation Suspended Furnace SupportFloor and Plenum Opening Dimensions Roll-Out ProtectionOpening dimensions Furnace Plenum Opening Floor Opening CasingWidth Horizontal Unit Suspension General Requirements Filter Arrangement Carbon Monoxide Poisoning HazardAIR Ducts Ductwork Acoustical Treatment Supply Air ConnectionsAir Delivery CFM With Filter Speed External Static Pressure IN. WC Size Inlet2380 2285 2200 2085 1970 1835 Return Air Connections Air Delivery CFM With Filter*Downflow Furnaces GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Maximum Capacity of Pipe Furnace Damage HazardElectrical Shock Hazard WiringElectrical Connections Electrical Shock and Fire Hazard Furnace MAY not Operate HazardElectrical Data BOX RelocationElectrical Connection to J-BOX Electrical Box on Furnace Casing Side. See Fig Power Cord Installation in Furnace J-BOXBX. Cable Installation in Furnace J-BOX Fire or Electrical Shock HazardTwo-Stage Furnace with Two-Speed Air Conditioner See notes 2, 11, and 12 on the page following these figures Accessories VentingGeneral Venting Requirements Masonry Chimney RequirementsChimney Inspection Chart Appliance Application Requirements Vent Height Internal Area of ChimneyUpflow Application-Vent Elbow Up Downflow Application-Vent Elbow Up Horizontal Right Application Vent Elbow Right Furnace Vent Orienta Orientation Tion PUTBTUH/HR Diameter Height FTRounded End of Knockout Burn HazardGeneral START-UP, ADJUSTMENT, and Safety CheckStart-Up Procedures Fire and Explosion HazardU.S AdjustmentsStage Furnace Setup Switch Description Altitude Derate Multiplier for U.S.ARedundant Automatic Gas Control Valve Gas Rate cu ft/hr Furnace Overheating HazardSeconds Size of Test Dial For Revolution Speed Selection Color Speed AS ShippedCheck Safety Controls Stage Furnace Blower OFF delay Setup SwitchDesired Heating Mode Setup Switch Blower OFF Delay SEC Checklist BTUH/CU Altitude RangeSpecific Gravity of Natural GAS Gravity6001 to Specific Gravity of Natural GAS Altitude Range BTUH/CU FTSpecific Gravity of Natural GAS Altitude Range Heat Value FIRE, Personal Injury and Unit Damage Service and Maintenance ProceduresElectrical SHOCK, Fire or Explosion Hazard Specific Gravity of Natural GAS Heat Value AT AltitudeIntroduction Care and MaintenanceElectrical Controls and Wiring Electrical Shock Hazard Unit Operation HazardService Wiring Diagram Blower Motor and Wheel Electrical Shock Hazard Cleaning AND/OR Replacing AIR FilterFilter size information Furnace Filter Size CasingCleaning Heat Exchanger Unit Damage HazardSequence of Operation Igniter Position Top ViewTwo-Stage Heating Adaptive mode with Single-Stage Thermostat Single-Stage Thermostat and Two-Speed Cooling Adaptive Mode Thermidistat ModeSingle-Speed Cooling Wiring Diagrams TroubleshootingContinuous Blower Mode Troubleshooting Guide 2-Speed Blocked vent shutoff switch used in Chimney Adapter Kit Page Catalog No. II312A---45---8

120 specifications

The Bryant 120 is a remarkable system designed for residential and commercial heating and cooling needs, showcasing an impressive blend of efficiency, reliability, and advanced technology. As a part of Bryant's extensive line of HVAC solutions, the Bryant 120 stands out with its features and performance, making it an ideal choice for those seeking comfort year-round.

One of the main features of the Bryant 120 is its exceptional energy efficiency. It boasts a high Seasonal Energy Efficiency Ratio (SEER) rating, enabling homeowners to save on energy costs while enjoying consistent temperature control. This efficiency is aided by its variable-speed compressor, which allows the system to adjust its output based on current requirements, optimizing both energy consumption and comfort.

In terms of technology, the Bryant 120 incorporates advanced controls that enhance user experience and system performance. The system comes equipped with smart thermostats that allow homeowners to monitor and adjust their environment remotely. These thermostats not only provide convenience but also help in optimizing energy usage by learning the household's heating and cooling patterns.

Another characteristic of the Bryant 120 is its durable construction. The unit is built to withstand various weather conditions, featuring a robust cabinet and components designed for longevity. This durability ensures that homeowners can rely on the system for years without the need for frequent repairs or replacements.

Noise levels are also a critical consideration in HVAC systems, and the Bryant 120 addresses this with its quiet operation. The system is designed to minimize sound output, making it suitable for residential areas where noise can be a concern. This is particularly beneficial for nighttime use, providing a comfortable sleeping environment.

Additionally, the Bryant 120 supports eco-friendly refrigerants that comply with environmental standards, contributing to a reduction in greenhouse gas emissions. This commitment to sustainability reflects Bryant's dedication to creating products that are not only effective but also responsible.

Overall, the Bryant 120 encapsulates a harmonious balance of efficiency, advanced technology, durability, and quiet operation. Whether for a new installation or a replacement, the Bryant 120 presents an ideal solution to meet diverse heating and cooling requirements, enhancing comfort while prioritizing energy savings and environmental responsibility.