Connect only to a flue or chimney capable of maintaining a negative draft of .05” wc at all times and conditions.

WARNING: If this setting is exceeded it could cause a solid fuel fire to burn out of control.

We recommend that the KERR SCOTSMAN Wood Furnace be connected to its own chimney. However, two or more fuel fired appliances, other than fireplaces or incinerators, may be connected to the same chimney.

The National Standard of Canada, Installation Code for Solid Fuel Burning Appliances and Equipment, CSA-B365-01 clause 5.2.9 states that:

Two or more appliances shall not be connected to the same chimney flue unless:

1)The appliances are located on the same story;

2)A negative pressure is maintained at the flue collar of each appliance;

3)Each appliance is provided with a means to control the rate of flow of air or flue gases through the appliance combustion and heat exchanger chambers. Where limitations on flue pressure (draft) are contained in the manufacturer’s instructions, such means shall be capable of maintaining at the flue collar, the pressure specified by the appliance manufacture; NOTE: For the purpose of this Clause, draft controls include ash pit air control dampers, dampers or draft slides wherever located, over fire and flue key pipe dampers, and check draft controls located on or in the flue pipe.

4)The flue pipes of the appliances are connected to a manifold as close to the chimney as practicable or directly to the chimney in the following order:

(i)If only solid fuel is used, the flue pipe from the smallest appliance shall be on top (downstream);

(ii)If different fuels are used as permitted in Clause 5.2.7, the oil flue pipe shall be on top (downstream); and the solid fuel flue pipe on the bottom (upstream); and

5)The chimney flue is capable of venting the flue gas by natural draft when all appliances not interlocked to prevent simultaneous firing are firing at their maximum rate at the same time.

When installing a wood-burning appliance to an existing chimney carefully inspect entire chimney for the presence of old inlet holes, which may be improperly covered by metal caps or other unacceptable means. Fill any openings with brick and mortar to ensure no hazardous openings exist.

Scotsman

11

Oct-06

Image 12
Contents Scotsman Wood Furnace Table of Contents Specifications Operating Instructions Introduction WOOD-BURNINGStorage of Wood CreosoteCase a Serious Creosote Fire Begins Maintenance Cleaning Fig S101-10Cleaning Procedure Maximum SOLID-FUEL ChargeSafety ServicingControls Disposal of AshesElectrical Power Failure Fig S101-3 Homeowner Checklist Installation Instructions Introduction to InstallersApplicable Standards Uncrating Locating the Furnace Fig S101-1, Fig S101-4Combustion AIR Supply Flue Pipe & ChimneyScotsman Minimum safety clearances to combustibles are Clearances Fig S101-1Warm AIR Duct & Plenum Clearances Disconnecting the circulation fan low speed switch Low Speed Switching Relay This is an optional part Fig S101ADD-ON Fig S101-7, Fig S101-8 Low Speed Switching Relay Installation Instructions Items requiredScotsman Control System Fig S101-5 T822 Room Thermostat Wood FurnaceInstallers Final Checklist Addendum Page Page Page Page Page Page Page Page Page Page Page Page Page Terms and Conditions of Warranty Year Warranty

DB-101 specifications

The Scotsman Ice DB-101 is a state-of-the-art ice maker designed for commercial use, catering to restaurants, bars, hotels, and other hospitality venues that require a reliable supply of high-quality ice. This model is highly regarded for its efficiency, power, and innovative technology, making it an ideal choice for businesses looking to enhance their ice production capabilities.

One of the standout features of the Scotsman Ice DB-101 is its ability to produce a significant amount of ice. This ice machine can produce up to 105 pounds of ice per day, depending on ambient conditions, making it suitable for establishments with high ice demands. The unit is designed to create individual half-dice ice cubes, which not only chill beverages efficiently but also provide a visually appealing presentation.

The technology behind the Scotsman Ice DB-101 is impressive. It employs a powerful self-diagnostic control system that allows for easy monitoring of the machine's performance. This feature minimizes downtime by promptly alerting users to potential issues, ensuring that the ice production remains uninterrupted. Additionally, the unit boasts a compact design that fits seamlessly into various spaces while providing substantial ice-making capacity.

Energy efficiency is another hallmark of the Scotsman Ice DB-101. The machine follows eco-friendly standards, consuming less power compared to other models in its class. This feature not only helps in reducing energy bills but also contributes to sustainability efforts within the hospitality industry.

Other notable characteristics include a durable stainless-steel construction that ensures longevity and resistance to corrosion, making it suitable for busy environments. The user-friendly interface allows for easy operation, and the automatic rinse cycle feature maintains ice purity by preventing mineral buildup and ensuring optimal taste.

The Scotsman Ice DB-101 also offers a versatile water source option, compatible with both filtered and standard water, ensuring users can maintain ice quality as per their requirements.

In summary, the Scotsman Ice DB-101 is a top-tier ice machine that combines efficiency, durability, and advanced technology, making it a valued investment for any commercial establishment that relies on a consistent supply of ice for its operations. Its capacity, energy efficiency, and user-friendly design make it a notable choice for industry professionals.