Step 3. INSTALL THE VENT SYSTEM

General Information

These instructions should be used as a guide- line and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and - B149.2 in Canada.

These fireplaces are designed, tested and listed for operation and installation with, and only with, Secure VentDirect Vent System Components, Secure Flex

Flexible Vent Components manufactured by Security Chimneys International and Z-FLEXModel GA Venting Systems listed to UL1777 and ULCS635 manufac- tured by Flexmaster Canada Limited. These approved vent system components are labeled for identification. DO NOT use any other manufacturer's vent com- ponents with these appliances.

These fireplaces must be vented directly to the outside.

Determine the venting for the appliance. If the vent run will include at least 8 feet of vertical rise, then install the second restrictor in the appliance collar before connecting any vent (Refer to Figure 12 ). Place the second restric- tor inside the fixed restrictor.

Note: The second restrictor is included within the firebox.

Exhaust Vent

Fixed Restrictor

Second Restrictor (For Vertical Vent Only)

Figure 12

The vent system may not service multiple appliances, and must never be connected to a flue serving a solid fuel burning appliance. The vent pipe is tested to be run inside an enclos- ing wall (such as a chase). There is no require- ment for inspection openings in the enclosing wall at any of the joints in the vent pipe.

Select Venting System - Horizontal or Vertical

With the appliance secured in framing, deter- mine vent routing and identify the exterior termination location. The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Refer to the section relating to your installation. A list of approved venting components is shown in the tables on page 26.

VERTICAL TERMINATION SYSTEMS (ROOF)

Figures 13, 17 and 23 through 25 on pages 12, 14 and 15 and their associated Vertical Vent Tables illustrate the various vertical vent- ing configurations that are possible for use with these appliances. Secure Vent pipe ap- plications are shown in these figures; Secure Flex pipe may also be used.

A Vertical Vent Table summarizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications.

Both these vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls is speci- fied in ANSI Z223.1-(latest edition) (In Canada, the current CAN-1 B149 installation code) by major building codes. Always consult your local codes for specific requirements. A gen- eral guide to follow is the Gas Vent Rule (refer to Figure 4 on page 6 ).

Vertical (Straight) Installation

Determine the number of straight vent sec- tions required. 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 461/2" (1181 mm) net section lengths are available. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Refer to the Vent Section Length Chart.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

SV4.5CGV-1

SV4.5FA OR

Termination

SV4.5FB Flashing

 

 

AND SV4.5SC

 

STORM COLLAR

1" (25.4 mm) Minimum Clearance to Combustibles

*SV4.5VF Firestop/Spacer

40' Max.

 

 

 

SV4.5L6/12/24/36/48

(12.2 M)

 

 

 

 

 

6' Min.

 

 

 

Vent Sections

(1.8 M)

 

 

 

 

 

 

 

 

 

 

 

 

*When using Secure Flex,

 

 

 

 

 

 

 

use Firestop/Spacer

 

 

 

 

 

 

 

 

 

SF4.5VF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 13

Vertical (Offset) Installation

Analyze the vent routing and determine the quantities of vent sections and number of elbows required. Refer to Vertical Vent Fig- ures and Tables on page 14 and 15 to select the type of vertical installation desired. Vent sections are available in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm). Refer to the Vent Section Length Chart on page 11 for an aid in selecting length combinations. Elbows are available in 90° and 45° configurations. Refer to Figure 18 for the SV4.5E45 and SV4.5E90 elbow dimensional specifications.

Image 10
Contents OTL Report No -F-47-5 MPLDV-35NM-2Table of Contents Model Orifice size Millivolt And Electronic ModelsAll Models Nat PropModel No Shelf Height inches mm Typical LocationsLocation Top Vent ApplicationVent Termination Clearances Vertical Vent Termination ClearancesAppliance and Vent Clearances Horizontal Vent Termination ClearancesRouting GAS Line Typical Installation SequenceDetailed Installation Steps Horizontal Vent Termination Clearances= Clearance to service regulator vent outlet Feet 91cm Canadian Installation US InstallationMeter/regulator assembly Inches 30cm1030 1162 419 1092 Model No903 1035 419 965 FramingModel No These fireplaces must be vented directly to the outside Install the Vent SystemVertical Termination Systems Roof Vent Section Length Chart Vent / 45 Degree Starter Elbow Connection 10 1/2 Min 267 mmConnection 12/12 Framing Dimensions for Roof Pitch10-1/2 267 mm 10-1/2Bracket Vertical Vent FIGURES/TABLESSupport Ceiling Firestop/Spacer SV4.5VF Detail ViewHorizontal Outside Wall Termination System Plan the vent runFrame exterior wall opening Typical Horizontal Vent InstallationInstall firestop/spacer at ceiling Four incline channels on the collar refer to onMm as shown in Figure Install Firestop/Spacer at exterior wallInstall the desired termination Slide the collars of the termination ontoHorizontal Vent FIGURES/TABLES Exterior Wall ThicknessWall Connection not Directly AT ApplianceConnection Directly AT Appliance Wall Firestop/SpacerWall Ceiling Firestop/Spacer SV4.5VFPull and extend the outer flexible vent pipe Install the Outer Flex PipePull and extend the inner flexible vent pipe Route Flex VentElectronic Wiring See Figure Field WiringMillivolt Wiring See Figure After the wiring is complete, replace the cover plateConnecting GAS Line ING Embers and Volcanic Stones Installing the Glass Door and Optional HoodInstalling the Glass Door MillivoltFinishing Requirements Burner AdjustmentsBurner Adjustment Wall DetailsCold Climate Insulation Installation AccessoriesMantel Clearances Cat Cat. No. Model No. DescriptionGAS Conversion Kits .2 Installation CodeMillivolt Appliances Pilot Orifice Electronic Appliances Dexen Electronic Valves Model No Orifice size NaturalPage Page 850,043M REV. F 09/2008 West Taft Avenue Orange, CA