Note: Secure Flex vent must be attached to Secure Flex terminations only. DO NOT substitute Secure Vent terminations or the Secure Vent adapter for Secure Flex compo- nents. The collars of Secure Flex termina- tions and adapters have a different circum- ference than that used with the Secure Vent pipe. Additionally, Secure Flex components have an extended length center tube for use in attaching the flexible vent.
Step 4. FIELD WIRING
Caution: Label all wires prior to disconnec- tion when servicing controls. Wiring errors can cause improper and dangerous opera- tion. Verify proper operation after servicing.
Refer to Section A for millivolt appliances and Section B for electronic appliances. The gas valve is set in place and
A. Millivolt Wiring (See Figure 36 ) –
1.
2. If
4.If an optional control switch is installed, turn the
B. Electronic Wiring (See Figure 37 ) –
Note: The electronic appliance must be con- nected to the main power supply.
1. Route a
2. Remove the electrical inlet cover plate from the side of the unit by removing the plate's securing screws. See Figure 11 on page 9.
3. Remove the cover plate's knockout and then feed the power supply wire through the knock- out opening and into the unit junction box.
4. Connect the black power supply wire to the lower outlet's red pigtail lead and the white power supply wire to the common terminal of the outlet as shown in Figure 37.
5. Connect the ground supply wire to the pigtail lead attached to outlet's green ground screw.
6.
Optional
7. If
8. If an optional control is to be used, wire it in the low voltage circuit as shown in Figure 37.
Note: The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the bottom com- partment.
9. If an optional control switch is installed, turn the
10. After the wiring is complete, replace the cover plate.
Note: No batteries to be installed in the battery holder until a power outage, or if the appliance is to be operated solely with two
(2) "D" batteries.
22
tion on a wall near the fireplace.
3. Wire the control switch within the millivolt control circuit using the 15 feet of 2 conductor wire supplied with the unit.
Note: The supplied 15 feet of 2 conductor wire has one end of each conductor con- nected to the gas valve circuit and the other end of each conductor placed loose inside the bottom compartment.
Caution: Do Not connect the optional wall switch to a 120V power supply.
WIRING DIAGRAM MILLIVOLT GAS VALVES | ||
|
| THERMOPILE |
APPLIANCE- MOUNTED |
| |
ON/OFF SWITCH |
|
|
|
| |
|
| TP |
|
| TH |
BK/W(1) | BK/W(1) | GAS VALVE |
THERMOSTAT (OPTIONAL) |
| |
Figure 36 |
|
|
120 VAC | INTERMITTENT ELECTRONIC WIRING DIAGRAM | SPARK TO PILOT IGNITOR |
| |
BK W GR |
|
| ||
|
|
|
| |
| GR |
|
|
|
| W |
|
|
|
| BK |
|
|
|
| IGNITOR MODULE |
|
|
|
JUNCTION BOX | 3V |
|
|
|
| BLACK (IGNITOR) |
|
| |
|
|
|
| |
TRANSFORMER 3V |
| BLACK (SENSOR) |
|
|
| BLACK |
|
|
|
TO WALL |
|
|
|
|
SWITCH OR | ORANGE (THTP) |
|
| |
THERMOSTAT |
|
| ||
| BATTERY |
| IN |
|
| BLACK (TP) |
|
|
|
|
| LO | HI | PILOT |
| RED |
| OUT | IN |
| GREEN (TH) |
| ||
|
|
|
| |
|
|
| VENT |
|
| BROWN |
|
|
|
| BROWN |
|
|
|
Figure 37 |
|
|
|
|
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.