Lennox Hearth EN04-VDLPM Connection not Directly AT Appliance, Connection Directly AT Appliance

Page 19

TABLE C

H Maximum

V Minimum

 

 

 

 

feet

(meters)

feet

(meters)

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

V + H = 40 feet (12.2 m) Max.

H = 20 ft. (6.096 m) Max.

Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1 (V) to 5

(H)ratio. For every 1 foot of

(V)vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.

*Use Firestop/Spacer SV4.5HF or SF4.5HF when using Secure Vent or Secure Flex respectively. Use Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using Secure Vent or Secure Flex on horizontal vent runs for the MPLDV35/40/45 with a center line lower than 48” (1219 mm) above the fireplace top wrapper surface. In all cases the firestop/spacer provided with the termination may be used with the termination, frame to 5” clearance where applicable.

H

H

V

*Wall

Support Bracket

**Wall

Firestop/Spacer

*When using Secure Flex, use

*Ceiling

 

Firestop/Spacer

 

Firestop/Spacer SF4.5VF

(SV4.5VF)

 

**Use Firestop/Spacer SV4.5HF or SF4.5HF when using

 

Secure Vent or Secure Flex respectively. Use

 

Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using

 

Secure Vent or Secure Flex on horizontal vent runs for

Support

the MPLDV35/40/45 with a center line lower than 48”

Bracket

(1219 mm) above the fireplace top wrapper surface.

 

In all cases the firestop/spacer provided with the

 

termination may be used with the termination, frame

 

to 5” clearance where applicable.

 

Square termination (SV4.5HT-2) shown.

See Table 3 as an aid in venting component selection for a particular range of exterior wall thicknesses.

Figure 30 - Top Vent - ONE 90 DEGREE ELBOW - ELBOW

CONNECTION NOT DIRECTLY AT APPLIANCE

Firestop/Spacer

H = 28 inches (711 mm) Maximum

Square termination (SV4.5HT-2) shown.

Figure 31 - Top Vent - ONE 90 DEGREE ELBOW -

CONNECTION DIRECTLY AT APPLIANCE

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

19

Image 19
Contents MPLDV-35NM-2 OTL Report No -F-47-5Table of Contents Nat Prop Millivolt And Electronic ModelsAll Models Model Orifice sizeTop Vent Application Typical LocationsLocation Model No Shelf Height inches mmHorizontal Vent Termination Clearances Vertical Vent Termination ClearancesAppliance and Vent Clearances Vent Termination ClearancesHorizontal Vent Termination Clearances Typical Installation SequenceDetailed Installation Steps Routing GAS LineInches 30cm Canadian Installation US InstallationMeter/regulator assembly = Clearance to service regulator vent outlet Feet 91cmFraming Model No903 1035 419 965 1030 1162 419 1092Model No These fireplaces must be vented directly to the outside Install the Vent SystemVertical Termination Systems Roof Vent Section Length Chart Vent / 45 Degree Starter Elbow Connection 10 1/2 Min 267 mmConnection 10-1/2 Framing Dimensions for Roof Pitch10-1/2 267 mm 12/12Ceiling Firestop/Spacer SV4.5VF Detail View Vertical Vent FIGURES/TABLESSupport BracketPlan the vent run Horizontal Outside Wall Termination SystemFour incline channels on the collar refer to on Typical Horizontal Vent InstallationInstall firestop/spacer at ceiling Frame exterior wall openingSlide the collars of the termination onto Install Firestop/Spacer at exterior wallInstall the desired termination Mm as shown in FigureExterior Wall Thickness Horizontal Vent FIGURES/TABLESWall Firestop/Spacer Connection not Directly AT ApplianceConnection Directly AT Appliance WallCeiling Firestop/Spacer SV4.5VF WallRoute Flex Vent Install the Outer Flex PipePull and extend the inner flexible vent pipe Pull and extend the outer flexible vent pipeAfter the wiring is complete, replace the cover plate Field WiringMillivolt Wiring See Figure Electronic Wiring See FigureConnecting GAS Line Millivolt Installing the Glass Door and Optional HoodInstalling the Glass Door ING Embers and Volcanic StonesWall Details Burner AdjustmentsBurner Adjustment Finishing RequirementsCold Climate Insulation Installation AccessoriesMantel Clearances Cat. No. Model No. Description CatGAS Conversion Kits .2 Installation CodeMillivolt Appliances Model No Orifice size Natural Pilot Orifice Electronic Appliances Dexen Electronic ValvesPage Page West Taft Avenue Orange, CA 850,043M REV. F 09/2008