Trane TCONT802AS32DA, TCONT803AS32DA System Checkout, Installer System Test

Page 17

TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

SYSTEM CHECKOUT

Installer System Test

The Installer System Test mode is used to test the HVAC system(s). See Table 5. While in System Test mode, minimum off-time for compressors is bypassed.

The Installer Test is part of the Installer Setup options. Enter Installer Setup screen and press the Down arrow key to bring up test selection(s) quickly.

CAUTION

Equipment Damage Hazard.

Minimum compressor off-time is bypassed during Installer System Test.

Avoid cycling compressor quickly.

Table 5. System Test(s).

 

 

 

 

 

 

 

 

Installer

Factory Setting

 

Other Choices

 

Select

Setup

 

 

 

 

 

Number

Options

Description

Options

Description

Comments

 

 

 

 

 

 

 

Installer

Test 1

0

Cool is off

1,2

0—cool off

System selection

Test Cool

 

 

 

 

1—cool stage 1 turns on

determines which

 

 

 

 

 

2—cool stages 1 and 2 on

tests are available

 

 

 

 

 

 

and the number of

 

 

 

 

 

 

stages shown.

 

 

 

 

 

 

 

Installer

Test 2

0

Fan is off

1

0—fan off

Test Fan

 

 

 

 

1—fan turns on

 

 

 

 

 

 

 

 

Installer

Test 3

0

Heat is off

1-3

0—heat off

Test Heat

 

 

 

 

1—stage 1 heat on

 

 

 

 

 

 

2—stages 1 and 2 heat on

 

 

 

 

 

 

3—stages 1, 2 and 3 (Aux

 

 

 

 

 

 

Ht) on

 

 

 

 

 

 

 

 

Installer

Test 4

0

Emergency

1

0—emergency heat off

Available only if

Test Em

 

 

heat is off

 

1—emergency heat on

heat pump with

Ht

 

 

 

 

2—emergency heat and

auxiliary heat is

 

 

 

 

 

auxiliary heat turn on

selected.

 

 

 

 

 

 

 

 

Pub. No. 18-HD25D19-3

17

69-1790—3

Image 17
Contents Selecting Location When Installing this ProductApplication Disconnect power before wiring Installing WallplatePub. No -HD25D19-3 Heat Pump PM-A Variable Speed AIR Handler Heat Pump Variable M24202 Battery Power Optional Powering the Comfort ControlVac Common Power Recommended Using the Comfort Control Adjusting Real-Time ClockSetting Calendar and Time Mounting the Comfort ControlLED Indication Requires 24 Vac Common Connection System and Fan SettingsOperation Installer Setup Installer Setup Menu Factory Setting Other Choices Cycles per 0240 Heat Stage 1 cycles Deadband 0310 Adaptive 0530 Adaptive Intelligent Conventional recovery Overshoot System Checkout Installer System TestOutdoor or Indoor Temperature Sensor Advanced FeaturesSpecial Heat Pump Features Dehumidification Droop ControlTroubleshooting Symptom Possible Cause Action Troubleshooting see TableRegistered Trademark