Trane TCONT802AS32DA Troubleshooting see Table, Troubleshooting Symptom Possible Cause Action

Page 19

TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

TROUBLESHOOTING (SEE TABLE 6)

Table 6. Troubleshooting.

 

 

 

Symptom

Possible Cause

Action

 

 

 

 

 

 

Display does not come on.

Comfort control is not being

Check for 24 Vac between B and Rc.

 

powered.

 

 

 

 

Temperature settings do not

The upper or lower temperature

Check temperature setpoints.

change.

limits were reached.

Check Installer Setup Numbers 0600 and

 

 

0610; modify as needed.

 

 

 

 

The keypad is fully locked.

Check Installer Setup Number 0670 to

 

 

change keypad locked options.

 

 

 

Heating or cooling does not come

Comfort control minimum off-

Wait up to five minutes for the system to

on.

time is activated.

respond.

 

 

 

 

System selection is not set to

Set system Selection to correct position.

 

Heat or Cool.

 

 

 

 

 

System type Selection is

Check Installer Setup Number 0170 and

 

incorrect.

make sure correct System type is

 

 

chosen.

 

 

 

Comfort control is calling for Heat

Heating or cooling equipment is

Check wiring.

(Heat on) or Cool (Cool on) but no

not operating.

Check Installer Setup Number 0170 and

heating or cooling is running.

 

make sure correct system type is chosen.

 

 

Verify operation of equipment in System

 

 

Test mode.

 

 

 

Comfort control does not respond

The keypad is locked.

Check Installer Setup Number 0670 to

when touch areas are pressed.

 

change keypad locked options.

 

 

 

 

Pub. No. 18-HD25D19-3

19

69-1790—3

Image 19
Contents Application When Installing this ProductSelecting Location Disconnect power before wiring Installing WallplatePub. No -HD25D19-3 Heat Pump PM-A Variable Speed AIR Handler Heat Pump Variable M24202 Vac Common Power Recommended Powering the Comfort ControlBattery Power Optional Mounting the Comfort Control Adjusting Real-Time ClockUsing the Comfort Control Setting Calendar and TimeOperation System and Fan SettingsLED Indication Requires 24 Vac Common Connection Installer Setup Installer Setup Menu Factory Setting Other Choices Cycles per 0240 Heat Stage 1 cycles Deadband 0310 Adaptive 0530 Adaptive Intelligent Conventional recovery Overshoot System Checkout Installer System TestDehumidification Droop Control Advanced FeaturesOutdoor or Indoor Temperature Sensor Special Heat Pump FeaturesTroubleshooting Symptom Possible Cause Action Troubleshooting see TableRegistered Trademark