Trane UH-PRC001-EN manual Model S, Model P, Selection Procedure

Page 14
Model S

Selection Procedure

Model S

Maximum mounting heights for Model S Unit Heaters are given inTable SP-1. When equipped with standard Louver Fin Diffusers the distance of throw may be increased as much as 25% by “toeing- in” the vertical blades. Distance of throw decreases in proportion to the amount of deflection given the airstream to either side of the heater.

Mounting the unit at or below maximum mounting height will insure that heated air reaches the living zone.

Model P

Maximum mounting heights for Model P Unit Heaters are given inTable SP-10, page 19.These distances are figured from the floor line to the bottom plate of the unit heater.

Where ceilings are unusually low, a nearly horizontal flow of air can be obtained by equipping these units with Louver Cone Diffusers.The individually adjustable blades of the Louver Cone permit an infinite variety of adjustments to meet any on-the-job problems. By setting the blades vertically to straighten the airstream, as much as 45% increase in throw can be obtained.

Table SP-2 – Factors for Determining Steam Capacity of Model S Horizontal Unit Heaters atVarious Pressures andTemperatures

Table Based on 2 PSIG and 60 F Entering Air

Steam

 

 

 

 

 

Temperature of Entering Air (F)

 

 

 

 

 

Pressure PSIG

-10

0

10

20

30

40

50

60

70

80

90

100

 

0

1.54

1.45

1.37

1.27

1.19

1.11

1.03

0.96

0.88

0.81

0.74

0.67

 

2

1.59

1.50

1.41

1.32

1.24

1.16

1.08

1.00

0.93

0.85

0.78

0.71

 

5

1.64

1.55

1.46

1.37

1.29

1.21

1.13

1.05

0.97

0.90

0.83

0.76

Blow-

10

1.73

1.64

1.55

1.46

1.38

1.29

1.21

1.13

1.06

0.98

0.91

0.84

Through

15

1.80

1.71

1.61

1.53

1.44

1.34

1.28

1.19

1.12

1.04

0.97

0.90

Type

20

1.86

1.77

1.68

1.58

1.50

1.42

1.33

1.25

1.17

1.10

1.02

0.95

 

30

1.97

1.87

1.78

1.68

1.60

1.51

1.43

1.35

1.27

1.19

1.12

1.04

 

40

2.06

1.96

1.86

1.77

1.68

1.60

1.51

1.43

1.35

1.27

1.19

1.12

 

50

2.13

2.04

1.94

1.85

1.76

1.67

1.58

1.50

1.42

1.34

1.26

1.19

 

60

2.20

2.09

2.00

1.90

1.81

1.73

1.64

1.56

1.47

1.39

1.31

1.24

 

70

2.26

2.16

2.06

1.96

1.87

1.78

1.70

1.61

1.53

1.45

1.37

1.29

 

75

2.28

2.18

2.09

1 .99

1.90

1.81

1.72

1.64

1.55

1.47

1.40

1.32

Notes:

To determine the Btu per hour capacity of a Model S Horizontal Unit Heater at any steam pressure and entering air temperature multiply rated capacity at 2 psig steam 60 F entering air (Table SP-3) by factor from above table. Factors in italics: Units should not be operated when entering air is below freezing at steam pressures below 10 psig.

14

UH-PRC001-EN

Image 14
Contents 17.4 to 705.6 MBh UH-PRC001-ENPropeller Unit Heaters/Unitary OctoberIntroduction The Industrial Designed Model P Unit HeaterSelection Procedure ContentsFeatures and Benefits Electric PowerFeatures and Benefits Put HeatWhere It’s NeededCompact Design The Model S CoilThe Model P Motor Rectangular Draw-ThruCoilsFeatures and Benefits Model PModel S External Couplings Features and BenefitsTypical Factory Application ConsiderationsGeneral Rules Application Considerations HotWater System - Using Circulating PumpGeneral Notes Application Considerations Vapor orVacuum SystemHotWater System with Circulating Pump Figure AC-4 Figure AC-5 Figure AC-6BTU Requirements Selection ProcedureTrane Propeller Unit Heaters Type of BuildingUseful Data FormulaDetermining Special Steam Capacities Equivalent Direct RadiationSelection Procedure Model S NomenclatureD BE Selection Procedure Model SModel P Table Based on 2 PSIG and 60 F Entering AirSelection Procedure 2 Lbs. Steam 60 F Entering AirTempSelection Procedure 2 Lbs. Steam 60 F Entering AirTempSelection Procedure Table SP-6- Maximum Spread FtMotor and Fan Speeds Additional Selection DataModel P Nomenclature Selection ProcedureSelection Procedure Selection ProcedureHotWater Selection Example StepPropylene Correction Factors for Propylene Glycol/WaterPropylene Glycol GlycolMotors Model Number DescriptionMODEL P UNIT HEATER Motors D B EModel Number Description Performance Data Performance Data WaterPerformance Data WaterPerformance Data WaterPerformance Data Entering WaterTemperaturePerformance Data Entering WaterTemperaturePerformance Data 117.6Performance Data Entering WaterTemperaturePerformance Data Entering WaterTemperaturePerformance Data WaterPerformance Data WaterPerformance Data WaterPerformance Data 115.1Performance Data WaterPerformance Data WaterPerformance Data Entering WaterTemperaturePerformance Data Entering WaterTemperaturePerformance Data Entering WaterTemperaturePerformance Data 100.1Performance Data Entering WaterTemperaturePerformance Data Entering WaterTemperatureElectric Power Electric Power AccessoryElectric Power ModelMotor MountType-1 Dimensions and WeightsFigure DW-1 Motor MountType-2Dimensions and Weights Figure DW-2Figure DW-3 Dimensions and WeightsIn Dimensions Figure DW-4 Table DW-4- Louver Cone Diffuser RoughingCasing Mechanical SpecificationsModel P General Model S GeneralPage NRTL/C TheTrane Company