Selection
Procedure
Table
2 Lbs. Steam 60 F Entering AirTemperature
Size | Motor | Motor | BTU | EDR | Condensate | Final | CFM 70 F | CFM at | Outlet | Oper. | |
HP | RPM | Per Hour | Lbs Per Hr | Temp. | Air Basis | FinalTemp. | Velocity | Weight Lbs. | |||
|
|
|
|
| Standard Models |
|
|
|
|
| |
1/25 | 1550 | 41,300 | 172 | 43 | 124 | 595 | 660 | 877 | 30 | ||
|
| 1150 | 33,600 | 140 | 35 | 131 | 436 | 495 | 658 |
|
|
1/20 | 1550 | 65,500 | 273 | 68 | 121 | 989 | 1085 | 1005 | 35 | ||
|
| 1150 | 52,800 | 220 | 55 | 129 | 706 | 785 | 727 |
|
|
1/20 | 1550 | 80,600 | 336 | 83 | 122 | 1200 | 1320 | 1220 | 40 | ||
|
| 1150 | 65,100 | 271 | 67 | 130 | 858 | 954 | 894 |
|
|
1/8 | 1070 | 101,800 | 424 | 106 | 123 | 1490 | 1635 | 980 | 55 | ||
|
| 850 | 87,900 | 366 | 91 | 129 | 1180 | 1315 | 783 |
|
|
1/6 | 1070 | 124,400 | 518 | 129 | 124 | 1790 | 1970 | 1170 | 55 | ||
1/6 | 1070 | 152,000 | 633 | 157 | 123 | 2220 | 2440 | 1045 | 80 | ||
1/6 | 1070 | 173,000 | 720 | 179 | 121 | 2620 | 2870 | 1230 | 80 | ||
1/4 | 1070 | 210,200 | 838 | 208 | 118 | 3200 | 3490 | 1495 | 85 | ||
1/4 | 1070 | 249,800 | 1040 | 260 | 115 | 4180 | 4550 | 1205 | 135 | ||
1/2 | 1070 | 283,800 | 1180 | 294 | 119 | 4430 | 4840 | 1275 | 135 | ||
3/4 | 1120 | 333,400 | 1390 | 345 | 119 | 5210 | 5690 | 1500 | 135 | ||
3/4 | 1120 | 386,000 | 1610 | 400 | 118 | 6140 | 6700 | 1770 | 175 | ||
1120 | 496,000 | 2070 | 514 | 117 | 8020 | 8750 | 1640 | 250 | |||
1120 | 585,000 | 2440 | 605 | 117 | 9450 | 10,300 | 1930 | 260 | |||
3 | 1120 | 705,000 | 2940 | 729 | 119 | 11,000 | 12,020 | 2250 | 325 | ||
|
|
| Low FinalTemperature Models - Standard Model P Units With All Air Ports Open |
|
|
| |||||
1/25 | 1150 | 34,800 | 145 | 36 | 108 | 668 | 716 | 950 | 30 | ||
|
| 1150 | 26,000 | 108 | 27 | 111 | 470 | 506 | 672 |
|
|
1/20 | 1550 | 57,200 | 238 | 59 | 104 | 1200 | 1280 | 1190 | 35 | ||
|
| 1150 | 45,800 | 191 | 48 | 109 | 862 | 925 | 858 |
|
|
1/20 | 1550 | 68,000 | 283 | 71 | 106 | 1360 | 1455 | 1350 | 40 | ||
|
| 1150 | 55,000 | 229 | 57 | 111 | 995 | 1070 | 992 |
|
|
1/8 | 1070 | 85,400 | 356 | 89 | 108 | 1640 | 1760 | 1050 | 55 | ||
|
| 850 | 71,200 | 296 | 74 | 111 | 1290 | 1390 | 827 |
|
|
1070 | 111,000 | 462 | 115 | 107 | 2180 | 2330 | 1390 | 55 | |||
1/6 | 1070 | 125,800 | 524 | 130 | 109 | 2360 | 2530 | 1080 | 80 | ||
1070 | 149,000 | 620 | 154 | 107 | 2920 | 3130 | 1340 | 80 | |||
1070 | 176,800 | 736 | 183 | 108 | 3390 | 3640 | 1560 | 85 | |||
1070 | 214,900 | 895 | 224 | 104 | 4500 | 4800 | 1270 | 135 | |||
1070 | 251,800 | 1050 | 260 | 106 | 5040 | 5380 | 1420 | 135 | |||
1120 | 291,000 | 1210 | 302 | 107 | 5700 | 6100 | 1610 | 135 | |||
1120 | 344,000 | 1430 | 356 | 108 | 6600 | 7080 | 1870 | 175 | |||
1120 | 428,000 | 1785 | 446 | 102 | 9380 | 9940 | 1860 | 250 | |||
1120 | 515,000 | 2140 | 533 | 106 | 10,300 | 11,000 | 2060 | 260 | |||
3 | 1120 | 620,000 | 2580 | 642 | 108 | 11,900 | 12,750 | 2380 | 325 | ||
Notes: |
|
|
|
|
|
|
|
|
|
|
|
Constant speed units are rated at capacities shown in regular type; capacities in italic faced type apply only to units with
To determine BTU per hour capacities at various steam pressures and entering air temperatures, use conversion factors from Table
Table SP-6 – Maximum Spread (Ft.)
Unit No. | 42P | 64P | 80P | 102P | 122P | 146P | 166P | 202P | 252P | 280P | 336P | 384P | 500P | 600P | 720P |
Spread (Ft.) | 15 | 17 | 20 | 24 | 26 | 27 | 28 | 32 | 35 | 37 | 45 | 50 | 54 | 57 | 60 |
Note:
The “spread” is the diameter of the comfort zone at floor level, projected by the Model P unit without the louver cone diffuser, based on two pounds steam pressure and 60 F entering air.
17 |