Trane PKG-PRC002-EN manual Unit Operating Limits

Page 10

Application

Considerations Self-Contained

Recommended Pump Location

Locate pump downstream of the cooling tower and upstream of the self-contained unit. This provides smoother and more stable unit operation.

When the tower and pump are both roof mounted, be sure to provide the necessary net positive suction head pressure to prevent cavitation. Raise the tower or submerge the pump in a sump to provide positive suction.To prevent an on-line pump failure, use a standby pump to avoid a complete system shutdown. Several partial capacity pumps or variable speed pumps may be used. Review the economics of these alternate pumping options.

Strainers and Water Treatment Water strainers are required at the unit inlet to eliminate potential unit damage from dirty water. Specify a water basket- type strainer to avoid an incorrect stream strainer application. Untreated or poorly treated water may result in equipment damage. Consult a water treatment specialist for treatment recommendations.

Isolation Valves

Install isolation valves at each unit before the strainer and after the condenser.This allows periodic servicing of the unit or

strainer while allowing other units in the system to remain in operation.

Pressure Gauges

Install pressure gauges on the inlet and outlet of the self-contained unit. Select the gauge’s scale so that the unit design operating point is approximately mid- scale.

Thermometers

Install thermometers on the condenser water inlet and outlet lines to each unit for system analysis.Trane Company recommends using a thermometer temperature range of 40 to 140 F, using a 2 F temperature increment.

Drains

The unit condensate drain is internally trapped to offset the pressure differential that exists during fan operation. Install a trapped drain in the low point of the mechanical equipment room floor to collect water from cleaning operations.

Condensing Pressure Control (Water-Cooled condensers)

Often cold condensing water applications between 35 F (1.7 C) and 54 F (12.2 C) require a condensing pressure control valve. Any unit with variable-flow waterside valves can modulate water flow to maintain a user defined condensing temperature. However, to

utilize this feature, the building water system must be capable of operating at reduced water flow rates through the self-contained units. It is imperative to install variable volume pumps or an external bypass in the water distribution system.

Waterside Economizer Flow Control Units equipped with waterside economizer control valves can be set up for variable or constant water flow.

Use constant water flow setup on water systems that are not capable of unloading water supply to the unit. The economizer and condenser valves will operate in complement to one another to provide continuous water flow.

Use variable water flow setup with water flow systems that can take advantage of pump unloading for energy savings.

Since non-cooling operation restricts water flow during part load economizing or condensing temperature control, it is imperative to install variable volume pumps or an external bypass in the water distribution system.

Unit Operating Limits

Airflow

The minimum recommended airflow for proper VAV system staging and temperature control is 35 percent of nominal design airflow. AdjustingVAV boxes with the appropriate minimum settings will prevent the self-contained unit from operating in a surge condition at airflows below this point. Continuous operation in a surge condition can cause fan failure. Reference General Data Tables on pages 17-20 for minimum airflow conditions.

Signature Series self-contained units use fixed pitch sheaves. Adjust air balancing by obtaining alternate fixed pitch sheave selections from the localTrane sales office.

Waterflow

Use 3 gpm/ton for optimum unit capacity and efficiency. Use 2.5 or 2 gpm/ton to reduce pump energy, cooling tower and piping costs. However, these reduced waterflows may impact unit capacity and efficiency by one or two percent. Consult General DataTables on pages 17-20 for unit specific waterflow ranges.

Waterside Economizer Piping

10

PKG-PRC002-EN

Image 10
Contents Commercial Self-Contained DecemberIntroduction Signature Series Self-Contained UnitsContents Features and Benefits Standard Features Optional FeaturesIntegrated Self-Contained Systems Integrated Comfort System ICSTrane 3-DScroll Compressor Proven DesignThroughTesting and ResearchLow Torque Variation Supply Air Ductwork Application Considerations Self-ContainedReturn Air Ductwork Equipment Room Location and OrientationIsolation Recommendations Condenser Water PipingUnit Operating Limits Considerations ApplicationAir Cooled CondenserUnit Capacities Procedure Self-ContainedSelection Waterside Economizer CapacitySelection Example Design Conditions Unit SelectionDescription ProcedureModel Number Self-Contained Model Number DescriptionSelf-Contained Accessory Model Number Description Remote Air-Cooled Condenser Model Number Description General Data TonsTable GD-3. SCWF/SIWF Water-Cooled Self-Contained, 42-80Tons SCRF/SIRF Table GD-4. SCRF/SIRF Air-Cooled Self-ContainedGeneral Data CCRC/CIRCHeating Coil Table GD-7. Self-Contained Heating CoilDrops Data Chart PD-5. Airside Pressure DropPerformance DropsAirside Pressure Heating CoilsDischarge Plenum 20 to 38 Ton Unit 42 to 80 Ton UnitAirside Pressure Airside Economizer with Standard Damper Airside Economizer with Traq Damper Waterside Chart PD-21. Waterside Pressure Drop SCWF/SIWF 35Pressure Drop SCWF/SIWF Performance Water-Cooled Data Table PD-1. CFM Capacity Correction TableTable PD-2. SCWF/SIWF 20 Economizer Full Capacity 8,000 cfm Water-Cooled20 Ton Table PD-3. SCWF/SIWF 20 Economizer Low Capacity 8,000 cfmEntering WaterTemp Entering Air 75 F 85 F 95 F Table PD-5. SCWF/SIWF 22 Economizer Full Capacity 8,800 cfm 22 TonTable PD-6. SCWF/SIWF 22 Economizer Low Capacity 8,800 cfm EnteringWaterTemp Entering Air 75 F 85 F 95 F 25 Ton Table PD-9. SCWF/SIWF 25 Economizer Low Capacity 10,000 cfmEntering Water Temp Entering Air 75 F 85 F 95 F 29 Ton Table PD-12. SCWF/SIWF 29 Economizer Low Capacity 11,600 cfm84.2 32 Ton Table PD-15. SCWF/SIWF 32 Economizer Low Capacity 12,800 cfm94.5 35 Ton Table PD-18. SCWF/SIWF 35 Economizer Low Capacity 14,000 cfm401 320 38 Ton Table PD-21. SCWF/SIWF 38 Economizer Low Capacity 15,200 cfm434 373 42 Ton Table PD-24. SCWF/SIWF 42 Economizer Low Capacity 16,800 cfm403 84.1 46 Ton Table PD-27. SCWF/SIWF 46 Economizer Low Capacity 18,400 cfm83.8 52 Ton Table PD-30. SCWF/SIWF 52 Economizer Low Capacity 20,800 cfm596 471 58 Ton Table PD-33. Scwfsiwf 58 Economizer Low Capacity 23,200 cfm663 571 65 Ton Table PD-36. SCWF/SIWF 65 Economizer Low Capacity 26,000 cfmEntering Water Temp Entering Air 72 Ton Table PD-39. SCWF/SIWF 72 Economizer Low Capacity 28,000 cfm83.7 80 Ton Table PD-42. SCWF/SIWF 80 Economizer Low Capacity 29,800 cfm891 761 Air-Cooled Table PD-45. SCRF/SIRF 25 Gross Cooling Capacity 11,600 cfm Table PD-46. SCRF/SIRF 29 Gross Cooling Capacity 12,800 cfm 30 Ton Table PD-47. SCRF/SIRF 30 Gross Cooling Capacity 14,000 cfmTable PD-48. SCRF/SIRF 35 Gross Cooling Capacity 15,200 cfm 40 Ton Table PD-49. SCRF/SIRF 40 Gross Cooling Capacity 18,400 cfm50 Ton Table PD-50. SCRF/SIRF 50 Gross Cooling Capacity 23,200 cfmData60-Ton Performance Air-CooledTable PD-51. SCRF/SIRF 60 Gross Cooling Capacity 29,800 cfm Table PD-52. HotWater Heating Capacity Self-ContainedHeating Coils Table PD-53. Steam Heating CapacityControls Available Input and Output PointsHuman Interface Panel HI Standard IntelliPak Unit Control FeaturesIntelliPak Unit Features Main menus of the human interface panels areControls Operation SequenceControl Sequences Operation Gbas Binary Outputs Generic Building Automation System Module Gbas OptionGbas Analog Inputs Demand Limiting Binary InputWater Purge Airside OptionsAir-Cooled Condensers Inlet GuideVane ControlHeating Electric Occupied ZoneTemperature ControlUnoccupied ZoneTemperature Control Cooling and Heating Heating Hot Water or SteamSupply Air Setpoint Reset Supply Air Temperature Control Unit Sequence OperationSupply Air Tempering Hot Water and Steam Units Only Standard On All Units Zone SensorControls Options Model Number Digit 6 = A, BAYSENS017Thermometer to indicate temperature in the zone Setpoint thumbwheel for local setpoint adjustment Selection Procedures Electrical DataTable ED-6. Single Stage Electric Heat Electrical Data Electrical Data SCWF/SCRFTable ED-7. CCRC/CIRC Condenser Electrical Data Dimensions Self-Contained Weights Tons Ton Self-ContainedDimensions Self-Contained Weights 40-80 Ton Discharge Dimensions Metric mm Detail B Discharge DimensionsDischarge Dimensions English inches Detail a Electrical ConnectionsDimensions Air-Cooled Weights Condenser Ccrc Unit DimensionsRefrigerant and Electrical Connections DimensionsWeights Front View Looking at Control PanelHot Water Coil Steam CoilPlenum Dimensions Metric mm DimensionsPlenum Dimensions English inches Flexible Horizontal Discharge PlenumEconomizer AirsideAirside Economizer Airside Economizer Dimensions English inches Airside Economizer Dimensions Metric mmZone Sensors Field-InstalledAdjustment Dual Setpoint, Manual/AutomaticFunction Lights Zone Temperature Sensor OnlyProgrammable Night-Setback Sensor Clearances ServiceService/Code Clearance Requirements Self-Contained ModelsTop View CCRC/CIRC 35 Top View CCRC/CIRC 20Top View CCRC/CIRC 50 Table W-2. Unit Weights CCRC/CIRC Dimensions WeightsTable W-1. Unit Weights SCWF/SCRF/SIWF/SIRF Table W-3. Variable Frequency Drive WeightsMechanical Specifications Self-Contained Signature Series Self Contained UnitsMechanical Air-CooledSpecifications Condenser Supply Air Temperature Control with Inlet GuideVanes Mechanical Specifications OptionsAir Volume/Temperature Control Zone Temperature Control Self-Contained OptionsAirside Economizer Interface Comparative Enthalpy ControlStandard Two-Position Damper Interface Airside Economizer Interface with Comparative EnthalpyLow Entering Air Temperature Protection Device Water Flow SwitchService Valves Non-fused Disconnect SwitchCupro-Nickel Condenser Protective Coating CabinetCoils Stainless Steel Drain PanLiterature Order Number

PKG-PRC002-EN specifications

The Trane PKG-PRC002-EN is a groundbreaking packaged rooftop unit designed to meet the diverse needs of commercial and industrial spaces. This model showcases Trane’s commitment to innovation, energy efficiency, and reliability, making it a preferred choice for HVAC professionals and building owners alike.

One of the main features of the PKG-PRC002-EN is its high-efficiency design. This unit leverages advanced technologies to minimize energy consumption while ensuring optimal cooling and heating performance. Its efficient compressor, coupled with enhanced heat exchangers, significantly reduces operating costs and energy bills, aligning with today’s sustainability goals.

The PKG-PRC002-EN features a robust and durable construction, which translates to enhanced longevity and reduced maintenance requirements. Designed for ease of installation, the unit is compact and lightweight, facilitating seamless retrofitting and integration into existing systems. Furthermore, its accessible service panels allow for straightforward maintenance and repairs, thus minimizing downtime and service disruptions.

Equipped with Trane's advanced control technology, the PKG-PRC002-EN offers precise temperature management, ensuring consistent comfort across different zones within a building. The intuitive controls enable users to program schedules and adjust settings based on their specific needs, enhancing comfort while maximizing efficiency.

The model also incorporates advanced filtration options, improving indoor air quality by effectively reducing pollutants and allergens. This focus on health and safety is essential, especially in commercial settings where air quality can significantly impact occupant well-being and productivity.

Another notable characteristic of the PKG-PRC002-EN is its low noise levels during operation, which is essential for maintaining a conducive indoor environment in workplaces, retail spaces, or educational institutions. The unit's design minimizes sound transmission, creating a more pleasant atmosphere for occupants.

In summary, the Trane PKG-PRC002-EN is a highly efficient, reliable, and user-friendly rooftop unit that combines advanced technology with robust construction. Its energy-saving features, superior air quality options, and focus on quiet performance make it an excellent choice for modern commercial HVAC applications, ultimately contributing to sustainable building practices and enhanced occupant comfort.