Trane PKG-PRC002-EN manual Comparative Enthalpy Control, Standard Two-Position Damper Interface

Page 98

Mechanical Specifications Options

Airside Economizer

Units with the airside economizer option are equipped with the necessary control sequences to use outside air for the first stage of cooling, in occupied or unoccupied mode and when ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to suppress the setpoint below the normal unit setpoint. This allows the building to improve comfort levels when possible, and at the same time, optimize building mechanical cooling operation for peak operating efficiency. An outside air temperature and relative humidity sensor are provided to allow monitoring of reference enthalpy and are field installed. Economizer operation enables when the outside air enthalpy is less than 25 BTU’s/ lb. default (adjustable 19-28 BTU’s/lb.). During occupied mode, the outside air damper opens to 15% (adjustable 0- 100%) for ventilation purposes. Also, the ability to alter the outside air damper position to compensate forVAV supply air modulation is inherent in the unit controls, and can be enabled by the operator.

The mixing box fabrication is 16-gauge galvanized steel. Opposed low leak damper blades are fabricated from 16- gauge galvanized steel and rotate on rustproof nylon bushings. A factory installed 24V modulating spring return actuator controls both damper positions.

• Comparative Enthalpy Control

Units with comparative enthalpy control are equipped with the necessary control sequences to allow using outside air for the first stage of cooling, in occupied or unoccupied mode and when ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to suppress the setpoint below the normal unit setpoint. This allows the building to improve comfort levels when possible, and at the same time, optimize building mechanical cooling operation for peak operating efficiency. A factory-installed control board, with field-installed outside and return air temperature and relative humidity sensors, allows monitoring of outside and return air. Economizer operation enables when the outside air enthalpy is 3 BTU’s/lb. less than the return air enthalpy. During occupied mode, the outside air damper opens to 15% (adjustable 0-100%) for ventilation

purposes. Also, the ability to alter the outside air damper position to compensate forVAV supply air modulation is inherent in the unit controls, and can be enabled by the operator.

The mixing box fabrication is 16-gauge galvanized steel. Opposed low leak damper blades are fabricated from 16- gauge galvanized steel and rotate on rustproof nylon bushings. A factory installed 24V modulating spring return actuator controls both damper positions.

•Standard Two-Position Damper Interface

Units with the two-position damper interface are provided with a 0-10 VDC control output suitable for controlling a field-provided modulating actuator. In occupied mode, the output drives to the maximum position.

• Airside Economizer Interface

Units with airside economizer interface are equipped with the necessary control sequences to allow using outside air for the first stage of cooling, in occupied or unoccupied mode and when ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to suppress the setpoint below the normal unit setpoint. This allows the building to improve comfort levels when possible, and at the same time, optimize building mechanical cooling operation for peak operating efficiency. An outside air temperature and relative humidity sensor are provided for field installation to monitor reference enthalpy. Economizer operation enables when the outside air enthalpy is less than 25 BTU’s/lb. (adjustable 19-28 BTU’s/lb). During occupied mode, the outside air damper opens to 15% (adjustable 0-100%) for ventilation purposes. Also, the ability to alter the outside air damper position to compensate forVAV supply air modulation is inherent in the unit controls, and can be enabled by the operator. An analog 2-10 VDC output (adjustable (0-10 VDC) is provided to modulate the field- provided 30 second damper actuators (adjustable 1-255 seconds).

Airside Economizer Interface with Comparative Enthalpy

Units with airside economizer interface and comparative enthalpy are equipped with the necessary control sequences to

allow using outside air for the first stage of cooling, in occupied or unoccupied mode and when ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to suppress the setpoint below the normal unit setpoint. This allows the building to improve comfort levels when possible, and at the same time, optimize building mechanical cooling operation for peak operating efficiency. A factory-installed control board, with outside and return air temperature and relative humidity sensors, are provided for monitoring outside and return air.The sensors are field installed. Economizer operation enables when the outside air enthalpy is 3 BTU’s/lb. less than the return air enthalpy. During occupied mode, the outside air damper opens to 15% (adjustable 0-100%) for ventilation purposes. Also, the ability to alter the outside air damper position to compensate forVAV supply air modulation is inherent in the unit controls, and can be enabled by the operator. An analog 2-10 VDC output (adjustable (0-10 VDC) is provided to modulate the field-provided 30-second damper actuators (adjustable 1-255 seconds).

Basic Water Piping

This option is available on units without a waterside economizer and with condenser water applications above 54 F (12.2 C) that do not require condensing pressure control. Left hand water connections and piping are extended to the unit exterior. Manifold piping is factory installed.

Intermediate Water Piping This option provides condensing temperature control when the unit is configured (user defined at the HI) for variable water flow with or without a waterside economizer. A two-way modulating control valve is wired and installed in the unit to maintain a specific range of water temperature rise through the condenser when entering fluid temperature is less than 58 F (15 C). This option allows the compressor to operate with entering fluid temperature down to 35 F (2 C). The minimum valve position to maintain minimum condenser flow rates is user-defined at the human interface. This valve drives closed if the unit shuts down or if a power failure occurs.

98

PKG-PRC002-EN

Image 98
Contents Commercial Self-Contained DecemberIntroduction Signature Series Self-Contained UnitsContents Features and Benefits Standard Features Optional FeaturesIntegrated Self-Contained Systems Integrated Comfort System ICSLow Torque Variation Proven DesignThroughTesting and ResearchTrane 3-DScroll Compressor Supply Air Ductwork Application Considerations Self-ContainedReturn Air Ductwork Equipment Room Location and OrientationIsolation Recommendations Condenser Water PipingUnit Operating Limits Considerations ApplicationAir Cooled CondenserUnit Capacities Procedure Self-ContainedSelection Waterside Economizer CapacitySelection Example Design Conditions Unit SelectionDescription ProcedureModel Number Self-Contained Model Number DescriptionSelf-Contained Accessory Model Number Description Remote Air-Cooled Condenser Model Number Description General Data TonsTable GD-3. SCWF/SIWF Water-Cooled Self-Contained, 42-80Tons SCRF/SIRF Table GD-4. SCRF/SIRF Air-Cooled Self-ContainedGeneral Data CCRC/CIRCHeating Coil Table GD-7. Self-Contained Heating CoilDrops Data Chart PD-5. Airside Pressure DropPerformance DropsAirside Pressure Heating CoilsDischarge Plenum 20 to 38 Ton Unit 42 to 80 Ton UnitAirside Pressure Airside Economizer with Standard Damper Airside Economizer with Traq Damper Pressure Drop Chart PD-21. Waterside Pressure Drop SCWF/SIWF 35Waterside SCWF/SIWF Performance Water-Cooled Data Table PD-1. CFM Capacity Correction TableTable PD-2. SCWF/SIWF 20 Economizer Full Capacity 8,000 cfm Water-Cooled20 Ton Table PD-3. SCWF/SIWF 20 Economizer Low Capacity 8,000 cfmEntering WaterTemp Entering Air 75 F 85 F 95 F Table PD-6. SCWF/SIWF 22 Economizer Low Capacity 8,800 cfm 22 TonTable PD-5. SCWF/SIWF 22 Economizer Full Capacity 8,800 cfm EnteringWaterTemp Entering Air 75 F 85 F 95 F 25 Ton Table PD-9. SCWF/SIWF 25 Economizer Low Capacity 10,000 cfmEntering Water Temp Entering Air 75 F 85 F 95 F 29 Ton Table PD-12. SCWF/SIWF 29 Economizer Low Capacity 11,600 cfm84.2 32 Ton Table PD-15. SCWF/SIWF 32 Economizer Low Capacity 12,800 cfm94.5 35 Ton Table PD-18. SCWF/SIWF 35 Economizer Low Capacity 14,000 cfm401 320 38 Ton Table PD-21. SCWF/SIWF 38 Economizer Low Capacity 15,200 cfm434 373 42 Ton Table PD-24. SCWF/SIWF 42 Economizer Low Capacity 16,800 cfm403 84.1 46 Ton Table PD-27. SCWF/SIWF 46 Economizer Low Capacity 18,400 cfm83.8 52 Ton Table PD-30. SCWF/SIWF 52 Economizer Low Capacity 20,800 cfm596 471 58 Ton Table PD-33. Scwfsiwf 58 Economizer Low Capacity 23,200 cfm663 571 65 Ton Table PD-36. SCWF/SIWF 65 Economizer Low Capacity 26,000 cfmEntering Water Temp Entering Air 72 Ton Table PD-39. SCWF/SIWF 72 Economizer Low Capacity 28,000 cfm83.7 80 Ton Table PD-42. SCWF/SIWF 80 Economizer Low Capacity 29,800 cfm891 761 Air-Cooled Table PD-45. SCRF/SIRF 25 Gross Cooling Capacity 11,600 cfm Table PD-46. SCRF/SIRF 29 Gross Cooling Capacity 12,800 cfm 30 Ton Table PD-47. SCRF/SIRF 30 Gross Cooling Capacity 14,000 cfmTable PD-48. SCRF/SIRF 35 Gross Cooling Capacity 15,200 cfm 40 Ton Table PD-49. SCRF/SIRF 40 Gross Cooling Capacity 18,400 cfm50 Ton Table PD-50. SCRF/SIRF 50 Gross Cooling Capacity 23,200 cfmTable PD-51. SCRF/SIRF 60 Gross Cooling Capacity 29,800 cfm Performance Air-CooledData60-Ton Table PD-52. HotWater Heating Capacity Self-ContainedHeating Coils Table PD-53. Steam Heating CapacityControls Available Input and Output PointsHuman Interface Panel HI Standard IntelliPak Unit Control FeaturesIntelliPak Unit Features Main menus of the human interface panels areControl Sequences Operation SequenceControls Operation Gbas Binary Outputs Generic Building Automation System Module Gbas OptionGbas Analog Inputs Demand Limiting Binary InputWater Purge Airside OptionsAir-Cooled Condensers Inlet GuideVane ControlHeating Electric Occupied ZoneTemperature ControlUnoccupied ZoneTemperature Control Cooling and Heating Heating Hot Water or SteamSupply Air Tempering Hot Water and Steam Units Only Supply Air Temperature Control Unit Sequence OperationSupply Air Setpoint Reset Standard On All Units Zone SensorControls Options Model Number Digit 6 = A, BAYSENS017Thermometer to indicate temperature in the zone Setpoint thumbwheel for local setpoint adjustment Selection Procedures Electrical DataTable ED-7. CCRC/CIRC Condenser Electrical Data Electrical Data SCWF/SCRFTable ED-6. Single Stage Electric Heat Electrical Data Dimensions Self-Contained Weights Tons Ton Self-ContainedDimensions Self-Contained Weights 40-80 Ton Discharge Dimensions Metric mm Detail B Discharge DimensionsDischarge Dimensions English inches Detail a Electrical ConnectionsDimensions Air-Cooled Weights Condenser Ccrc Unit DimensionsRefrigerant and Electrical Connections DimensionsWeights Front View Looking at Control PanelHot Water Coil Steam CoilPlenum Dimensions Metric mm DimensionsPlenum Dimensions English inches Flexible Horizontal Discharge PlenumAirside Economizer AirsideEconomizer Airside Economizer Dimensions English inches Airside Economizer Dimensions Metric mmZone Sensors Field-InstalledAdjustment Dual Setpoint, Manual/AutomaticProgrammable Night-Setback Sensor Zone Temperature Sensor OnlyFunction Lights Clearances ServiceService/Code Clearance Requirements Self-Contained ModelsTop View CCRC/CIRC 50 Top View CCRC/CIRC 20Top View CCRC/CIRC 35 Table W-2. Unit Weights CCRC/CIRC Dimensions WeightsTable W-1. Unit Weights SCWF/SCRF/SIWF/SIRF Table W-3. Variable Frequency Drive WeightsMechanical Specifications Self-Contained Signature Series Self Contained UnitsMechanical Air-CooledSpecifications Condenser Supply Air Temperature Control with Inlet GuideVanes Mechanical Specifications OptionsAir Volume/Temperature Control Zone Temperature Control Self-Contained OptionsAirside Economizer Interface Comparative Enthalpy ControlStandard Two-Position Damper Interface Airside Economizer Interface with Comparative EnthalpyLow Entering Air Temperature Protection Device Water Flow SwitchService Valves Non-fused Disconnect SwitchCupro-Nickel Condenser Protective Coating CabinetCoils Stainless Steel Drain PanLiterature Order Number

PKG-PRC002-EN specifications

The Trane PKG-PRC002-EN is a groundbreaking packaged rooftop unit designed to meet the diverse needs of commercial and industrial spaces. This model showcases Trane’s commitment to innovation, energy efficiency, and reliability, making it a preferred choice for HVAC professionals and building owners alike.

One of the main features of the PKG-PRC002-EN is its high-efficiency design. This unit leverages advanced technologies to minimize energy consumption while ensuring optimal cooling and heating performance. Its efficient compressor, coupled with enhanced heat exchangers, significantly reduces operating costs and energy bills, aligning with today’s sustainability goals.

The PKG-PRC002-EN features a robust and durable construction, which translates to enhanced longevity and reduced maintenance requirements. Designed for ease of installation, the unit is compact and lightweight, facilitating seamless retrofitting and integration into existing systems. Furthermore, its accessible service panels allow for straightforward maintenance and repairs, thus minimizing downtime and service disruptions.

Equipped with Trane's advanced control technology, the PKG-PRC002-EN offers precise temperature management, ensuring consistent comfort across different zones within a building. The intuitive controls enable users to program schedules and adjust settings based on their specific needs, enhancing comfort while maximizing efficiency.

The model also incorporates advanced filtration options, improving indoor air quality by effectively reducing pollutants and allergens. This focus on health and safety is essential, especially in commercial settings where air quality can significantly impact occupant well-being and productivity.

Another notable characteristic of the PKG-PRC002-EN is its low noise levels during operation, which is essential for maintaining a conducive indoor environment in workplaces, retail spaces, or educational institutions. The unit's design minimizes sound transmission, creating a more pleasant atmosphere for occupants.

In summary, the Trane PKG-PRC002-EN is a highly efficient, reliable, and user-friendly rooftop unit that combines advanced technology with robust construction. Its energy-saving features, superior air quality options, and focus on quiet performance make it an excellent choice for modern commercial HVAC applications, ultimately contributing to sustainable building practices and enhanced occupant comfort.