Trane PKG-PRC002-EN manual Electrical Data, Selection Procedures

Page 79

Electrical Data

Selection Procedures

RLA = Rated Load Amps

Compressor LRA = Locked Rotor Amps

Fan Motor LRA = Locked Rotor Amps,

N.E.C.Table 430 - 150

FLA = Full Load Amps, N.E.C.

Table 430 - 150

Voltage utilization range is ±10 percent

Determination of minimum circuit ampacity (MCA).

MCA = 1.25 x largest motor amps/VFD amps (FLA or RLA) + the sum of the remaining motor amps.

Determination of maximum fuse size (MFS) and maximum circuit breaker size (MCB)

MFS and MCB = 2.25 x largest motor amps (FLA or RLA) + the sum of the remaining motor amps.

Units with the dual power option require separate MFS and MCB calculations for each electrical circuit:

1) fans and 2) compressors.

If the rating value calulation does not equal a standard over current protective device rating, use the next lower standard rating as the maximum.

Table ED-1. Number of Compressors per Unit

SCRF/SIRF

20

25 - 29

30

- 35

40

50

 

60

SCWF/SIWF 20 - 25

29 - 32

35

- 38

42 - 46

52 - 58

65 - 72

80

10

2

1

 

3

2

-

1

-

15

-

1

 

-

1

3

3

4

Table ED-2. SCWF/SIWF Compressor Electrical Data

 

 

200V

 

460V

 

575V

HP

RLA

LRA

RLA

LRA

RLA

LRA

10

33

269

14.5

117

11.5

94

15

46

409

20.5

178

16.5

143

Table ED-3. SCRF/SIRF Compressor Electrical Data

 

 

200V

 

460V

 

575V

HP

RLA

LRA

RLA

LRA

RLA

LRA

10

36.8

269

16.3

117

13.2

94

15

61.1

409

26

178

21.5

143

Table ED-4. Fan Without VFD Electrical Data

 

 

200V

 

460V

 

575V

HP

FLA

LRA

FLA

LRA

FLA

LRA

5

16.1

105

6.7

46

5.4

37

7.5

25.0

152

10.8

66

8.2

54

10

32.9

193

14.2

84

11.4

66

15

44.8

290

20.3

126

16.2

102

20

61.0

373

25.0

162

20.0

132

25

74.0

469

31.0

204

24.2

162

30

87.0

552

36.0

240

28.6

192

40

113.0

718

47.8

312

38.0

246

50

NA

NA

62.0

390

49.2

312

Table ED-5. Fan with VFD Electrical Data

 

 

200V

 

460V

HP

FLA

LRA

FLA

LRA

7.5

29.0

152

14.3

66

10

38.3

193

18.1

84

15

42.7

290

25.8

126

20

55.2

373

32.4

162

25

67.8

469

38.9

204

30

82.0

552

39.0

240

40

108.6

718

51.0

312

50

NA

NA

61.5

390

Note: Values are at the maximum VFD input rating and not the reduced motor values.

PKG-PRC002-EN

79

Image 79
Contents December Commercial Self-ContainedSignature Series Self-Contained Units IntroductionContents Features and Benefits Optional Features Standard FeaturesIntegrated Comfort System ICS Integrated Self-Contained SystemsTrane 3-DScroll Compressor Proven DesignThroughTesting and ResearchLow Torque Variation Equipment Room Location and Orientation Application Considerations Self-ContainedReturn Air Ductwork Supply Air DuctworkCondenser Water Piping Isolation RecommendationsUnit Operating Limits Condenser ApplicationAir Cooled ConsiderationsWaterside Economizer Capacity Procedure Self-ContainedSelection Unit CapacitiesUnit Selection Selection Example Design ConditionsSelf-Contained Model Number Description ProcedureModel Number DescriptionSelf-Contained Accessory Model Number Description Remote Air-Cooled Condenser Model Number Description Tons General DataTable GD-3. SCWF/SIWF Water-Cooled Self-Contained, 42-80Tons Table GD-4. SCRF/SIRF Air-Cooled Self-Contained SCRF/SIRFCCRC/CIRC General DataTable GD-7. Self-Contained Heating Coil Heating CoilDrops Drops Chart PD-5. Airside Pressure DropPerformance DataHeating Coils Airside Pressure20 to 38 Ton Unit 42 to 80 Ton Unit Discharge PlenumAirside Pressure Airside Economizer with Standard Damper Airside Economizer with Traq Damper Waterside Chart PD-21. Waterside Pressure Drop SCWF/SIWF 35Pressure Drop SCWF/SIWF Table PD-1. CFM Capacity Correction Table Performance Water-Cooled DataTable PD-3. SCWF/SIWF 20 Economizer Low Capacity 8,000 cfm Water-Cooled20 Ton Table PD-2. SCWF/SIWF 20 Economizer Full Capacity 8,000 cfmEntering WaterTemp Entering Air 75 F 85 F 95 F Table PD-5. SCWF/SIWF 22 Economizer Full Capacity 8,800 cfm 22 TonTable PD-6. SCWF/SIWF 22 Economizer Low Capacity 8,800 cfm EnteringWaterTemp Entering Air 75 F 85 F 95 F Table PD-9. SCWF/SIWF 25 Economizer Low Capacity 10,000 cfm 25 TonEntering Water Temp Entering Air 75 F 85 F 95 F Table PD-12. SCWF/SIWF 29 Economizer Low Capacity 11,600 cfm 29 Ton84.2 Table PD-15. SCWF/SIWF 32 Economizer Low Capacity 12,800 cfm 32 Ton94.5 Table PD-18. SCWF/SIWF 35 Economizer Low Capacity 14,000 cfm 35 Ton401 320 Table PD-21. SCWF/SIWF 38 Economizer Low Capacity 15,200 cfm 38 Ton434 373 Table PD-24. SCWF/SIWF 42 Economizer Low Capacity 16,800 cfm 42 Ton403 84.1 Table PD-27. SCWF/SIWF 46 Economizer Low Capacity 18,400 cfm 46 Ton83.8 Table PD-30. SCWF/SIWF 52 Economizer Low Capacity 20,800 cfm 52 Ton596 471 Table PD-33. Scwfsiwf 58 Economizer Low Capacity 23,200 cfm 58 Ton663 571 Table PD-36. SCWF/SIWF 65 Economizer Low Capacity 26,000 cfm 65 TonEntering Water Temp Entering Air Table PD-39. SCWF/SIWF 72 Economizer Low Capacity 28,000 cfm 72 Ton83.7 Table PD-42. SCWF/SIWF 80 Economizer Low Capacity 29,800 cfm 80 Ton891 761 Air-Cooled Table PD-45. SCRF/SIRF 25 Gross Cooling Capacity 11,600 cfm Table PD-46. SCRF/SIRF 29 Gross Cooling Capacity 12,800 cfm Table PD-47. SCRF/SIRF 30 Gross Cooling Capacity 14,000 cfm 30 TonTable PD-48. SCRF/SIRF 35 Gross Cooling Capacity 15,200 cfm Table PD-49. SCRF/SIRF 40 Gross Cooling Capacity 18,400 cfm 40 TonTable PD-50. SCRF/SIRF 50 Gross Cooling Capacity 23,200 cfm 50 TonData60-Ton Performance Air-CooledTable PD-51. SCRF/SIRF 60 Gross Cooling Capacity 29,800 cfm Table PD-53. Steam Heating Capacity Self-ContainedHeating Coils Table PD-52. HotWater Heating CapacityAvailable Input and Output Points ControlsMain menus of the human interface panels are Standard IntelliPak Unit Control FeaturesIntelliPak Unit Features Human Interface Panel HIControls Operation SequenceControl Sequences Operation Demand Limiting Binary Input Generic Building Automation System Module Gbas OptionGbas Analog Inputs Gbas Binary OutputsInlet GuideVane Control Airside OptionsAir-Cooled Condensers Water PurgeHeating Hot Water or Steam Occupied ZoneTemperature ControlUnoccupied ZoneTemperature Control Cooling and Heating Heating ElectricSupply Air Setpoint Reset Supply Air Temperature Control Unit Sequence OperationSupply Air Tempering Hot Water and Steam Units Only Model Number Digit 6 = A, BAYSENS017 Zone SensorControls Options Standard On All UnitsThermometer to indicate temperature in the zone Setpoint thumbwheel for local setpoint adjustment Electrical Data Selection ProceduresTable ED-6. Single Stage Electric Heat Electrical Data Electrical Data SCWF/SCRFTable ED-7. CCRC/CIRC Condenser Electrical Data Ton Self-Contained Dimensions Self-Contained Weights TonsDimensions Self-Contained Weights 40-80 Ton Detail a Electrical Connections Detail B Discharge DimensionsDischarge Dimensions English inches Discharge Dimensions Metric mmCcrc Unit Dimensions Dimensions Air-Cooled Weights CondenserFront View Looking at Control Panel DimensionsWeights Refrigerant and Electrical ConnectionsSteam Coil Hot Water CoilFlexible Horizontal Discharge Plenum DimensionsPlenum Dimensions English inches Plenum Dimensions Metric mmEconomizer AirsideAirside Economizer Airside Economizer Dimensions Metric mm Airside Economizer Dimensions English inchesDual Setpoint, Manual/Automatic Field-InstalledAdjustment Zone SensorsFunction Lights Zone Temperature Sensor OnlyProgrammable Night-Setback Sensor Self-Contained Models ServiceService/Code Clearance Requirements ClearancesTop View CCRC/CIRC 35 Top View CCRC/CIRC 20Top View CCRC/CIRC 50 Table W-3. Variable Frequency Drive Weights Dimensions WeightsTable W-1. Unit Weights SCWF/SCRF/SIWF/SIRF Table W-2. Unit Weights CCRC/CIRCSignature Series Self Contained Units Mechanical Specifications Self-ContainedMechanical Air-CooledSpecifications Condenser Self-Contained Options Mechanical Specifications OptionsAir Volume/Temperature Control Zone Temperature Control Supply Air Temperature Control with Inlet GuideVanesAirside Economizer Interface with Comparative Enthalpy Comparative Enthalpy ControlStandard Two-Position Damper Interface Airside Economizer InterfaceNon-fused Disconnect Switch Water Flow SwitchService Valves Low Entering Air Temperature Protection DeviceStainless Steel Drain Pan Protective Coating CabinetCoils Cupro-Nickel CondenserLiterature Order Number

PKG-PRC002-EN specifications

The Trane PKG-PRC002-EN is a groundbreaking packaged rooftop unit designed to meet the diverse needs of commercial and industrial spaces. This model showcases Trane’s commitment to innovation, energy efficiency, and reliability, making it a preferred choice for HVAC professionals and building owners alike.

One of the main features of the PKG-PRC002-EN is its high-efficiency design. This unit leverages advanced technologies to minimize energy consumption while ensuring optimal cooling and heating performance. Its efficient compressor, coupled with enhanced heat exchangers, significantly reduces operating costs and energy bills, aligning with today’s sustainability goals.

The PKG-PRC002-EN features a robust and durable construction, which translates to enhanced longevity and reduced maintenance requirements. Designed for ease of installation, the unit is compact and lightweight, facilitating seamless retrofitting and integration into existing systems. Furthermore, its accessible service panels allow for straightforward maintenance and repairs, thus minimizing downtime and service disruptions.

Equipped with Trane's advanced control technology, the PKG-PRC002-EN offers precise temperature management, ensuring consistent comfort across different zones within a building. The intuitive controls enable users to program schedules and adjust settings based on their specific needs, enhancing comfort while maximizing efficiency.

The model also incorporates advanced filtration options, improving indoor air quality by effectively reducing pollutants and allergens. This focus on health and safety is essential, especially in commercial settings where air quality can significantly impact occupant well-being and productivity.

Another notable characteristic of the PKG-PRC002-EN is its low noise levels during operation, which is essential for maintaining a conducive indoor environment in workplaces, retail spaces, or educational institutions. The unit's design minimizes sound transmission, creating a more pleasant atmosphere for occupants.

In summary, the Trane PKG-PRC002-EN is a highly efficient, reliable, and user-friendly rooftop unit that combines advanced technology with robust construction. Its energy-saving features, superior air quality options, and focus on quiet performance make it an excellent choice for modern commercial HVAC applications, ultimately contributing to sustainable building practices and enhanced occupant comfort.