Trane PKG-PRC002-EN manual Thermometer to indicate temperature in the zone

Page 77

Zone Sensor

Controls Options

CV

CV

CV

Dual setpoint, manual/automatic changeover sensor, Accessory Model Number Digit 6 = E, BAYSENS008

This zone sensor module is for use with cooling/heating CV applications. It provides the following features and system control functions:

System control switch (Heat/Auto/Off/ Cool): Allows you to select heating mode, cooling mode, automatic selection of heating or cooling as required, or turn the system off.

Fan control switch (Auto/On): Allows you to select automatic fan operation while actively heating or cooling or continuous fan operation.

Dual temperature setpoint levers allow you to set different cooling (blue lever) and heating setpoints (red lever).

Thermometer to indicate temperature in the zone.

Dual setpoint, manual/automatic changeover sensor with system function lights, Accessory Model Number Digit 6 = F, BAYSENS010

This zone sensor is for use with cooling/ heating CV applications. It provides the following features and system control functions:

System control switch to select heating mode (HEAT), cooling mode (COOL), AUTO for automatic selection of heating or cooling as required, or OFF to turn the system off.

Fan control switch to select automatic fan operation while actively heating or cooling (AUTO), or continuous fan operation (ON).

Dual temperature setpoint levers for setting cooling (blue lever) or heating (red lever).

Thermometer to indicate temperatuare in the zone.

Function status indicator lights:

SYS ON glows continuously during normal operation, or blinks if system is in test mode.

COOL glows continuously during cooling cycles or blinks to indicate a cooling system failure.

HEAT glows continuously during heating cycles or blinks to indicate a heating system failure.

SERVICE blinks or glows to indicate a problem. These signals vary depending on the particular equipment used.

Programmable night setback sensor, Accessory Model Number Digit 6 = G, BAYSENS019

The programmable night setback sensor is for use in CV applications. The sensor has a time clock function that provides communication to the self-contained unit through a 2-wire communications link. The desired transition times are programmed at the night setback sensor and communicated to the self-contained unit.

The programmable night setback (unoccupied mode) operates through the time clock provided in the sensors with night setback. When the time clock switches to night setback operation, the outdoor air dampers close and heating/ cooling enables or disables, depending on set-up parameters. As the building load changes, the night setback sensor energizes the self-contained unit’s heating/cooling (if enabled) function and the evaporator fan. The self-contained unit will cycle through the evening as heating/cooling (if enabled) is required in the space. When the time clock switches from night setback to occupied mode, all heating/cooling functions begin normal operation.

PKG-PRC002-EN

77

Image 77
Contents December Commercial Self-ContainedSignature Series Self-Contained Units IntroductionContents Features and Benefits Optional Features Standard FeaturesIntegrated Comfort System ICS Integrated Self-Contained SystemsLow Torque Variation Proven DesignThroughTesting and ResearchTrane 3-DScroll Compressor Return Air Ductwork Application Considerations Self-ContainedSupply Air Ductwork Equipment Room Location and OrientationCondenser Water Piping Isolation RecommendationsUnit Operating Limits Air Cooled ApplicationConsiderations CondenserSelection Procedure Self-ContainedUnit Capacities Waterside Economizer CapacityUnit Selection Selection Example Design ConditionsModel Number ProcedureDescription Self-Contained Model Number DescriptionSelf-Contained Accessory Model Number Description Remote Air-Cooled Condenser Model Number Description Tons General DataTable GD-3. SCWF/SIWF Water-Cooled Self-Contained, 42-80Tons Table GD-4. SCRF/SIRF Air-Cooled Self-Contained SCRF/SIRFCCRC/CIRC General DataTable GD-7. Self-Contained Heating Coil Heating CoilDrops Performance Chart PD-5. Airside Pressure DropData DropsHeating Coils Airside Pressure20 to 38 Ton Unit 42 to 80 Ton Unit Discharge PlenumAirside Pressure Airside Economizer with Standard Damper Airside Economizer with Traq Damper Pressure Drop Chart PD-21. Waterside Pressure Drop SCWF/SIWF 35Waterside SCWF/SIWF Table PD-1. CFM Capacity Correction Table Performance Water-Cooled Data20 Ton Water-CooledTable PD-2. SCWF/SIWF 20 Economizer Full Capacity 8,000 cfm Table PD-3. SCWF/SIWF 20 Economizer Low Capacity 8,000 cfmEntering WaterTemp Entering Air 75 F 85 F 95 F Table PD-6. SCWF/SIWF 22 Economizer Low Capacity 8,800 cfm 22 TonTable PD-5. SCWF/SIWF 22 Economizer Full Capacity 8,800 cfm EnteringWaterTemp Entering Air 75 F 85 F 95 F Table PD-9. SCWF/SIWF 25 Economizer Low Capacity 10,000 cfm 25 TonEntering Water Temp Entering Air 75 F 85 F 95 F Table PD-12. SCWF/SIWF 29 Economizer Low Capacity 11,600 cfm 29 Ton84.2 Table PD-15. SCWF/SIWF 32 Economizer Low Capacity 12,800 cfm 32 Ton94.5 Table PD-18. SCWF/SIWF 35 Economizer Low Capacity 14,000 cfm 35 Ton401 320 Table PD-21. SCWF/SIWF 38 Economizer Low Capacity 15,200 cfm 38 Ton434 373 Table PD-24. SCWF/SIWF 42 Economizer Low Capacity 16,800 cfm 42 Ton403 84.1 Table PD-27. SCWF/SIWF 46 Economizer Low Capacity 18,400 cfm 46 Ton83.8 Table PD-30. SCWF/SIWF 52 Economizer Low Capacity 20,800 cfm 52 Ton596 471 Table PD-33. Scwfsiwf 58 Economizer Low Capacity 23,200 cfm 58 Ton663 571 Table PD-36. SCWF/SIWF 65 Economizer Low Capacity 26,000 cfm 65 TonEntering Water Temp Entering Air Table PD-39. SCWF/SIWF 72 Economizer Low Capacity 28,000 cfm 72 Ton83.7 Table PD-42. SCWF/SIWF 80 Economizer Low Capacity 29,800 cfm 80 Ton891 761 Air-Cooled Table PD-45. SCRF/SIRF 25 Gross Cooling Capacity 11,600 cfm Table PD-46. SCRF/SIRF 29 Gross Cooling Capacity 12,800 cfm Table PD-47. SCRF/SIRF 30 Gross Cooling Capacity 14,000 cfm 30 TonTable PD-48. SCRF/SIRF 35 Gross Cooling Capacity 15,200 cfm Table PD-49. SCRF/SIRF 40 Gross Cooling Capacity 18,400 cfm 40 TonTable PD-50. SCRF/SIRF 50 Gross Cooling Capacity 23,200 cfm 50 TonTable PD-51. SCRF/SIRF 60 Gross Cooling Capacity 29,800 cfm Performance Air-CooledData60-Ton Heating Coils Self-ContainedTable PD-52. HotWater Heating Capacity Table PD-53. Steam Heating CapacityAvailable Input and Output Points ControlsIntelliPak Unit Features Standard IntelliPak Unit Control FeaturesHuman Interface Panel HI Main menus of the human interface panels areControl Sequences Operation SequenceControls Operation Gbas Analog Inputs Generic Building Automation System Module Gbas OptionGbas Binary Outputs Demand Limiting Binary InputAir-Cooled Condensers Airside OptionsWater Purge Inlet GuideVane ControlUnoccupied ZoneTemperature Control Cooling and Heating Occupied ZoneTemperature ControlHeating Electric Heating Hot Water or SteamSupply Air Tempering Hot Water and Steam Units Only Supply Air Temperature Control Unit Sequence OperationSupply Air Setpoint Reset Controls Options Zone SensorStandard On All Units Model Number Digit 6 = A, BAYSENS017Thermometer to indicate temperature in the zone Setpoint thumbwheel for local setpoint adjustment Electrical Data Selection ProceduresTable ED-7. CCRC/CIRC Condenser Electrical Data Electrical Data SCWF/SCRFTable ED-6. Single Stage Electric Heat Electrical Data Ton Self-Contained Dimensions Self-Contained Weights TonsDimensions Self-Contained Weights 40-80 Ton Discharge Dimensions English inches Detail B Discharge DimensionsDischarge Dimensions Metric mm Detail a Electrical ConnectionsCcrc Unit Dimensions Dimensions Air-Cooled Weights CondenserWeights DimensionsRefrigerant and Electrical Connections Front View Looking at Control PanelSteam Coil Hot Water CoilPlenum Dimensions English inches DimensionsPlenum Dimensions Metric mm Flexible Horizontal Discharge PlenumAirside Economizer AirsideEconomizer Airside Economizer Dimensions Metric mm Airside Economizer Dimensions English inchesAdjustment Field-InstalledZone Sensors Dual Setpoint, Manual/AutomaticProgrammable Night-Setback Sensor Zone Temperature Sensor OnlyFunction Lights Service/Code Clearance Requirements ServiceClearances Self-Contained ModelsTop View CCRC/CIRC 50 Top View CCRC/CIRC 20Top View CCRC/CIRC 35 Table W-1. Unit Weights SCWF/SCRF/SIWF/SIRF Dimensions WeightsTable W-2. Unit Weights CCRC/CIRC Table W-3. Variable Frequency Drive WeightsSignature Series Self Contained Units Mechanical Specifications Self-ContainedMechanical Air-CooledSpecifications Condenser Air Volume/Temperature Control Zone Temperature Control Mechanical Specifications OptionsSupply Air Temperature Control with Inlet GuideVanes Self-Contained OptionsStandard Two-Position Damper Interface Comparative Enthalpy ControlAirside Economizer Interface Airside Economizer Interface with Comparative EnthalpyService Valves Water Flow SwitchLow Entering Air Temperature Protection Device Non-fused Disconnect SwitchCoils Protective Coating CabinetCupro-Nickel Condenser Stainless Steel Drain PanLiterature Order Number

PKG-PRC002-EN specifications

The Trane PKG-PRC002-EN is a groundbreaking packaged rooftop unit designed to meet the diverse needs of commercial and industrial spaces. This model showcases Trane’s commitment to innovation, energy efficiency, and reliability, making it a preferred choice for HVAC professionals and building owners alike.

One of the main features of the PKG-PRC002-EN is its high-efficiency design. This unit leverages advanced technologies to minimize energy consumption while ensuring optimal cooling and heating performance. Its efficient compressor, coupled with enhanced heat exchangers, significantly reduces operating costs and energy bills, aligning with today’s sustainability goals.

The PKG-PRC002-EN features a robust and durable construction, which translates to enhanced longevity and reduced maintenance requirements. Designed for ease of installation, the unit is compact and lightweight, facilitating seamless retrofitting and integration into existing systems. Furthermore, its accessible service panels allow for straightforward maintenance and repairs, thus minimizing downtime and service disruptions.

Equipped with Trane's advanced control technology, the PKG-PRC002-EN offers precise temperature management, ensuring consistent comfort across different zones within a building. The intuitive controls enable users to program schedules and adjust settings based on their specific needs, enhancing comfort while maximizing efficiency.

The model also incorporates advanced filtration options, improving indoor air quality by effectively reducing pollutants and allergens. This focus on health and safety is essential, especially in commercial settings where air quality can significantly impact occupant well-being and productivity.

Another notable characteristic of the PKG-PRC002-EN is its low noise levels during operation, which is essential for maintaining a conducive indoor environment in workplaces, retail spaces, or educational institutions. The unit's design minimizes sound transmission, creating a more pleasant atmosphere for occupants.

In summary, the Trane PKG-PRC002-EN is a highly efficient, reliable, and user-friendly rooftop unit that combines advanced technology with robust construction. Its energy-saving features, superior air quality options, and focus on quiet performance make it an excellent choice for modern commercial HVAC applications, ultimately contributing to sustainable building practices and enhanced occupant comfort.