Trane PKG-PRC002-EN Generic Building Automation System Module Gbas Option, Gbas Analog Inputs

Page 72

Sequence of

Controls Operation

Generic Building Automation System Module (GBAS) Option

The generic building automation system module (GBAS) provides broad control capabilities for building automation systems other than Trane’s Tracer® system. A field provided potentiometer or a 0-5 vdc signal can be applied to any of the inputs of the GBAS to provide the following inputs and outputs.

• GBAS Analog Inputs

Four analog inputs that can be configured to be any of the following:

(1)Occupied zone cooling

(2)Unoccupied zone cooling

(3)Occupied zone heating

(4)Unoccupied zone heating

(5)SA cooling setpoint

(6)SA heating setpoint

(7)Space static pressure setpoint

(8)SA static pressure setpoint

• GBAS Binary Outputs

Each of the five (5) relay outputs can be mapped to any/all of the available diagnostics.

• Demand Limiting Binary Input

This function is operational on units with a GBAS and is used to reduce electrical consumption at peak load times. There are two types of demand limiting, 50% and 100%. When demand limiting is needed, mechanical cooling and heating operation are either partially (50%), or completely disabled (100%) to save energy.The demand limit definition is user definable at the human interface panel. Demand limit binary input accepts a field supplied switch or contact closure. When the need for demand limiting has been discontinued, the unit’s cooling/ heating functions will again become fully enabled.

Evaporator Coil Frost Protection

FROSTAT

A temperature sensor on the evaporator is used to determine if the coil is getting close to a freezing condition. Mechanical cooling capacity is shed as necessary to prevent icing.

The FROSTATsystem eliminates the need for hot gas bypass and adds a suction line surface temperature sensor mounted near the TXV bulb location to shut off the cooling when coil frosting conditions occur.The supply fan is not

shut off and will de-ice the coil.Timers prevent the compressors from rapid cycling.

Occupied/Unoccupied Switching There are four ways to switch occupied/ unoccupied:

(1)Programmable night setback sensor

(2)Field-supplied contact closure (hardwired binary input to RTM)

(3)Tracer®

(4)Factory-mounted time clock

Field Supplied Occupied/Unoccupied input on the RTM

This input accepts a field supplied switch or contacts closure such as a time clock.

Trane Tracer® System

TheTraneTracer® system can control the occupied/unoccupied status of the self- contained unit.

Factory MountedTime Clock A time clock can control the occupied/unoccupied status of the self-contained unit.

Timed Override Activation - ICS

This function is operational whenever the unit’s RTM module board is used as the zone temperature sensor source, which can be set at the human interface panel. When this function is initiated by the push of the override button on the zone sensor, the unit will switch to the occupied mode. Unit operation (occupied mode) during timed override is terminated by a signal from Tracer®.

Timed Override Activation - Non-ICS This function is active whenever the unit’s RTM module board is selected as the zone temperature source, which can be set at the human interface panel. When this function is initiated by the push of the override button on the zone sensor, the unit will switch to the occupied mode. Automatic cancellation of the timed override mode occurs after three hours of operation.

Low Ambient Compressor Lockout This function will lock out the compressor if the outdoor air temperature is below the low ambient compressor lock-out temperature setpoint when using a field- installed outside air sensor.This setpoint is adjustable at the human interface panel. Compressors will lock out when outdoor air temperature falls below that selected temperature and will start again

when the temperature rises 5 F above the setpoint.

Comparative Enthalpy Control of Airside Economizer Option

An optional comparative enthalpy system is used to control the operation of the economizer and measures the temperature and humidity of both return air and outside air to determine which source has lower enthalpy.This system allows true comparison of outdoor air and return air enthalpy by measurement of outdoor and return air temperatures and humidities.

Note: If comparative enthalpy is not ordered, the standard method compares outdoor air enthalpy with a fixed reference enthalpy, set through the human interface panel.

Compressor Lead/Lag

Compressor lead/lag is a user-selectable feature through the human interface panel available on all units. After each request for compressor operation, the lead refrigeration circuit or compressor switches, thereby causing a more equitable or balanced run time among compressors.

Emergency Stop Input

A binary input is provided on the unit’s RTM module board for installation of a field-provided switch or contacts to immediatly shutdown all unit functions.

Water Flow Control

With compatible piping configurations, the unit can be configured to provide:

1)Constant water flow with basic or intermediate piping or 2) Variable water flow with intermediate piping only.

Constant water flow is for condenser pumping systems that are not capable of unloading the water-pumping system. Variable water flow maximizes energy saving by unloading the water pumping system.

Head Pressure Control

Water-Cooled Condensers

Units that are set up for variable water flow will modulate a water valve to maintain a user-defined condensing temperature setpoint. Condensing temperature will be referenced utilizing factory installed sensors located at each condenser.

72

PKG-PRC002-EN

Image 72
Contents Commercial Self-Contained DecemberIntroduction Signature Series Self-Contained UnitsContents Features and Benefits Standard Features Optional FeaturesIntegrated Self-Contained Systems Integrated Comfort System ICSProven DesignThroughTesting and Research Trane 3-DScroll CompressorLow Torque Variation Application Considerations Self-Contained Return Air DuctworkSupply Air Ductwork Equipment Room Location and OrientationIsolation Recommendations Condenser Water PipingUnit Operating Limits Application Air CooledConsiderations CondenserProcedure Self-Contained SelectionUnit Capacities Waterside Economizer CapacitySelection Example Design Conditions Unit SelectionProcedure Model NumberDescription Self-Contained Model Number DescriptionSelf-Contained Accessory Model Number Description Remote Air-Cooled Condenser Model Number Description General Data TonsTable GD-3. SCWF/SIWF Water-Cooled Self-Contained, 42-80Tons SCRF/SIRF Table GD-4. SCRF/SIRF Air-Cooled Self-ContainedGeneral Data CCRC/CIRCHeating Coil Table GD-7. Self-Contained Heating CoilDrops Chart PD-5. Airside Pressure Drop PerformanceData DropsAirside Pressure Heating CoilsDischarge Plenum 20 to 38 Ton Unit 42 to 80 Ton UnitAirside Pressure Airside Economizer with Standard Damper Airside Economizer with Traq Damper Chart PD-21. Waterside Pressure Drop SCWF/SIWF 35 WatersidePressure Drop SCWF/SIWF Performance Water-Cooled Data Table PD-1. CFM Capacity Correction TableWater-Cooled 20 TonTable PD-2. SCWF/SIWF 20 Economizer Full Capacity 8,000 cfm Table PD-3. SCWF/SIWF 20 Economizer Low Capacity 8,000 cfmEntering WaterTemp Entering Air 75 F 85 F 95 F 22 Ton Table PD-5. SCWF/SIWF 22 Economizer Full Capacity 8,800 cfmTable PD-6. SCWF/SIWF 22 Economizer Low Capacity 8,800 cfm EnteringWaterTemp Entering Air 75 F 85 F 95 F 25 Ton Table PD-9. SCWF/SIWF 25 Economizer Low Capacity 10,000 cfmEntering Water Temp Entering Air 75 F 85 F 95 F 29 Ton Table PD-12. SCWF/SIWF 29 Economizer Low Capacity 11,600 cfm84.2 32 Ton Table PD-15. SCWF/SIWF 32 Economizer Low Capacity 12,800 cfm94.5 35 Ton Table PD-18. SCWF/SIWF 35 Economizer Low Capacity 14,000 cfm401 320 38 Ton Table PD-21. SCWF/SIWF 38 Economizer Low Capacity 15,200 cfm434 373 42 Ton Table PD-24. SCWF/SIWF 42 Economizer Low Capacity 16,800 cfm403 84.1 46 Ton Table PD-27. SCWF/SIWF 46 Economizer Low Capacity 18,400 cfm83.8 52 Ton Table PD-30. SCWF/SIWF 52 Economizer Low Capacity 20,800 cfm596 471 58 Ton Table PD-33. Scwfsiwf 58 Economizer Low Capacity 23,200 cfm663 571 65 Ton Table PD-36. SCWF/SIWF 65 Economizer Low Capacity 26,000 cfmEntering Water Temp Entering Air 72 Ton Table PD-39. SCWF/SIWF 72 Economizer Low Capacity 28,000 cfm83.7 80 Ton Table PD-42. SCWF/SIWF 80 Economizer Low Capacity 29,800 cfm891 761 Air-Cooled Table PD-45. SCRF/SIRF 25 Gross Cooling Capacity 11,600 cfm Table PD-46. SCRF/SIRF 29 Gross Cooling Capacity 12,800 cfm 30 Ton Table PD-47. SCRF/SIRF 30 Gross Cooling Capacity 14,000 cfmTable PD-48. SCRF/SIRF 35 Gross Cooling Capacity 15,200 cfm 40 Ton Table PD-49. SCRF/SIRF 40 Gross Cooling Capacity 18,400 cfm50 Ton Table PD-50. SCRF/SIRF 50 Gross Cooling Capacity 23,200 cfmPerformance Air-Cooled Data60-TonTable PD-51. SCRF/SIRF 60 Gross Cooling Capacity 29,800 cfm Self-Contained Heating CoilsTable PD-52. HotWater Heating Capacity Table PD-53. Steam Heating CapacityControls Available Input and Output PointsStandard IntelliPak Unit Control Features IntelliPak Unit FeaturesHuman Interface Panel HI Main menus of the human interface panels areSequence Controls OperationControl Sequences Operation Generic Building Automation System Module Gbas Option Gbas Analog InputsGbas Binary Outputs Demand Limiting Binary InputAirside Options Air-Cooled CondensersWater Purge Inlet GuideVane ControlOccupied ZoneTemperature Control Unoccupied ZoneTemperature Control Cooling and HeatingHeating Electric Heating Hot Water or SteamSupply Air Temperature Control Unit Sequence Operation Supply Air Setpoint ResetSupply Air Tempering Hot Water and Steam Units Only Zone Sensor Controls OptionsStandard On All Units Model Number Digit 6 = A, BAYSENS017Thermometer to indicate temperature in the zone Setpoint thumbwheel for local setpoint adjustment Selection Procedures Electrical DataElectrical Data SCWF/SCRF Table ED-6. Single Stage Electric Heat Electrical DataTable ED-7. CCRC/CIRC Condenser Electrical Data Dimensions Self-Contained Weights Tons Ton Self-ContainedDimensions Self-Contained Weights 40-80 Ton Detail B Discharge Dimensions Discharge Dimensions English inchesDischarge Dimensions Metric mm Detail a Electrical ConnectionsDimensions Air-Cooled Weights Condenser Ccrc Unit DimensionsDimensions WeightsRefrigerant and Electrical Connections Front View Looking at Control PanelHot Water Coil Steam CoilDimensions Plenum Dimensions English inchesPlenum Dimensions Metric mm Flexible Horizontal Discharge PlenumAirside EconomizerAirside Economizer Airside Economizer Dimensions English inches Airside Economizer Dimensions Metric mmField-Installed AdjustmentZone Sensors Dual Setpoint, Manual/AutomaticZone Temperature Sensor Only Function LightsProgrammable Night-Setback Sensor Service Service/Code Clearance RequirementsClearances Self-Contained ModelsTop View CCRC/CIRC 20 Top View CCRC/CIRC 35Top View CCRC/CIRC 50 Dimensions Weights Table W-1. Unit Weights SCWF/SCRF/SIWF/SIRFTable W-2. Unit Weights CCRC/CIRC Table W-3. Variable Frequency Drive WeightsMechanical Specifications Self-Contained Signature Series Self Contained UnitsMechanical Air-CooledSpecifications Condenser Mechanical Specifications Options Air Volume/Temperature Control Zone Temperature ControlSupply Air Temperature Control with Inlet GuideVanes Self-Contained OptionsComparative Enthalpy Control Standard Two-Position Damper InterfaceAirside Economizer Interface Airside Economizer Interface with Comparative EnthalpyWater Flow Switch Service ValvesLow Entering Air Temperature Protection Device Non-fused Disconnect SwitchProtective Coating Cabinet CoilsCupro-Nickel Condenser Stainless Steel Drain PanLiterature Order Number

PKG-PRC002-EN specifications

The Trane PKG-PRC002-EN is a groundbreaking packaged rooftop unit designed to meet the diverse needs of commercial and industrial spaces. This model showcases Trane’s commitment to innovation, energy efficiency, and reliability, making it a preferred choice for HVAC professionals and building owners alike.

One of the main features of the PKG-PRC002-EN is its high-efficiency design. This unit leverages advanced technologies to minimize energy consumption while ensuring optimal cooling and heating performance. Its efficient compressor, coupled with enhanced heat exchangers, significantly reduces operating costs and energy bills, aligning with today’s sustainability goals.

The PKG-PRC002-EN features a robust and durable construction, which translates to enhanced longevity and reduced maintenance requirements. Designed for ease of installation, the unit is compact and lightweight, facilitating seamless retrofitting and integration into existing systems. Furthermore, its accessible service panels allow for straightforward maintenance and repairs, thus minimizing downtime and service disruptions.

Equipped with Trane's advanced control technology, the PKG-PRC002-EN offers precise temperature management, ensuring consistent comfort across different zones within a building. The intuitive controls enable users to program schedules and adjust settings based on their specific needs, enhancing comfort while maximizing efficiency.

The model also incorporates advanced filtration options, improving indoor air quality by effectively reducing pollutants and allergens. This focus on health and safety is essential, especially in commercial settings where air quality can significantly impact occupant well-being and productivity.

Another notable characteristic of the PKG-PRC002-EN is its low noise levels during operation, which is essential for maintaining a conducive indoor environment in workplaces, retail spaces, or educational institutions. The unit's design minimizes sound transmission, creating a more pleasant atmosphere for occupants.

In summary, the Trane PKG-PRC002-EN is a highly efficient, reliable, and user-friendly rooftop unit that combines advanced technology with robust construction. Its energy-saving features, superior air quality options, and focus on quiet performance make it an excellent choice for modern commercial HVAC applications, ultimately contributing to sustainable building practices and enhanced occupant comfort.