Unconfined Space

A water heater in an unconfined space uses indoor air for combustion and requires at least 50 cubic feet for each 1,000 BTUH of the total input for all gas appliances. The table below shows a few examples of the minimum square footage (area) required for various BTUH inputs.

Table 2

 

 

BTUH

Minimum Square

Typical Room

Feet with

Input

with 8' Ceiling

8' Ceiling

 

 

30,000

188

9 x 21

45,000

281

14 x 20

60,000

375

15 x 25

75,000

469

15 x 31

90,000

563

20 x 28

105,000

657

20 x 33

120,000

750

25 x 30

135,000

844

28 x 30

 

 

 

IMPORTANT:

The area must be open and be able to provide the proper air requirements to the water heater. Areas that are being used for storage or contain large objects may not be suitable for water heater installation.

Water heaters installed in open spaces in buildings with unusually tight construction may still require outdoor air to function properly. In this situation, outside air openings should be sized the same as for a confined space.

Modern home construction usually requires supplying outside air into the water heater area.

Confined Space

For the correct and proper operation of this water heater, ample air must be supplied for the combustion, ventilation, and dilution of flue gases. Small enclosures and confined areas must have two permanent openings so that sufficient fresh air can be drawn from outside of the enclosure. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure as shown in Figure 4.

The size of each opening (free area) is determined by the total BTUH input of all gas utilization equipment (i.e., water heaters, furnaces, clothes dryers, etc.) and the method by which the air is provided. The BTUH input can be found on the water heater data plate. Additional air can be provided by two methods:

1.All air from inside the building.

2.All air from outdoors.

Figure 4

12” maximum

 

 

Opening Locations-

 

 

 

 

 

 

Confined Spaces

 

 

 

 

 

 

 

 

 

Closet

 

 

 

 

 

 

 

 

 

 

Permanent

 

 

 

or

 

 

 

other

openings to

 

 

 

confined

the outside or

 

space

additional

 

 

 

 

rooms within the building

12” maximum

All Air from Inside the Building

When additional air is to be provided to the confined area from additional room(s) within the building, the total volume of the room(s) must be of sufficient size to properly provide the necessary amount of fresh air to the water heater and other gas utilization equipment in the area. If you are unsure that the structure meets this requirement, contact your local gas utility company or other qualified agency for a safety inspection.

Each of the two openings shall have a minimum free area of 1 square inch per 1,000 BTUH of the total input rating of all gas utilization equipment in the confined area, but not less than 100 square inches (Figure 5).

Confined

Space

Permanent

Openings

1 square

inch/1000

BTUH

(minimum

100 sq. In.)

Figure 5

All Air from Inside Building

Confined Space Installation

8

Image 8
Contents Installation Instructions Use & Care Guide Water Heater Safety Table Of ContentsInstalling Your GAS Water Heater Important Information About This Water HeaterConsumer Information Consumer ResponsibilitiesLocation Requirements Site LocationClearances and Accessibility Gas Pressure Testing Gas SupplyGas Requirements Gas PressureCombustion Air Supply and Ventilation Natural Gas Pipe Capacity Table Cu. Ft./HrAll Air from Inside the Building Unconfined SpaceConfined Space All Air from Outdoors Louvers and GrillesDrafthood Installation Vent ConnectorsVent Pipe System Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingTemperature and Pressure Relief Valve Closed System/Thermal ExpansionSolar Installation Special ApplicationsCombination Space Heating/Potable Water SystemInstallation Checklist Important Information About Your Water HeaterOperating Your Water Heater Lighting InstructionsWater Temperature Regulation Checking the DraftBurner Flames StackingOperating the Temperature Control System Water Temperature AdjustmentOperating Modes and Settings Diagnostic Status Light CodeOperational Conditions Draining and Flushing Maintenance of Your Water HeaterRoutine Preventive Maintenance Replacement Parts Removing the Manifold AssemblyRemoving the Burner from the Manifold Assembly Natural Gas Burner Low NoxCleaning the Combustion Chamber and Flame-trap Replacing the Pilot AssemblyExternal Inspection & Cleaning of the Flame-trap Piezoelectric Igniter System Replacing the Manifold AssemblyTesting the Igniter System Flame Lock Safety System Operational Checklist Removing and Replacing the Gas Control Valve/ThermostatSlow HOT Water Pilot Light Troubleshooting Chart Repair Parts Illustration Repair Parts ListListed Parts Kits and Illustrations

W10100870, 89263, SG1J4040T3NOV 5K, BFG1J5040T3NOV 5K, 6510374 specifications

Whirlpool is a leading name in the home appliances industry, known for its innovative technology and user-friendly designs. Among its extensive product range, various models stand out for their unique features and capabilities. Such models include the Whirlpool 6510374, BFG1J5040T3NOV 5K, SG1J4040T3NOV 5K, 89263, and W10100870, each designed to enhance functionality and convenience in kitchen environments and more.

The Whirlpool 6510374 is a versatile appliance often used for its high efficiency and reliable performance. It includes features like adjustable shelves, which provide flexibility in arranging your items to maximize storage space. The smart cooling technology ensures uniform cooling throughout the unit, preserving the freshness of perishables for extended periods.

Next, the BFG1J5040T3NOV 5K offers advanced features tailored for energy efficiency. Its high efficiency compressor not only provides optimal cooling but also helps consumers save on energy bills. Furthermore, it includes a user-friendly digital display that allows for precise temperature control and easy monitoring, catering to the needs of modern families.

The SG1J4040T3NOV 5K model enhances user convenience with features such as a frost-free design, which eliminates the need for manual defrosting, saving both time and effort. This feature, combined with its spacious interior, makes it highly desirable for storing large quantities of food.

Model 89263 focuses on ease of use and maintenance. With its intuitive interface and durable construction, this model stands out in terms of reliability. Its robust design ensures longevity while maintaining performance, making it a dependable choice for families.

Lastly, the W10100870 offers unique characteristics centered around connectivity and technology. Equipped with smart features, it allows users to connect their devices and control settings remotely. This model exemplifies the shift towards smart home technology, creating a seamless integration of appliances into daily life.

In conclusion, the Whirlpool 6510374, BFG1J5040T3NOV 5K, SG1J4040T3NOV 5K, 89263, and W10100870 each present an array of features that enhance functionality, efficiency, and user experience. Whirlpool continues to push boundaries in appliance design, ensuring that each model is a safe, reliable, and smart choice for consumers worldwide. These models reflect the brand’s commitment to quality, innovation, and customer satisfaction, making them an essential part of any modern kitchen.