The following conditions apply for an RS-485 bus system:

A bus system consists of a bus line and/or one or more branch lines.

Cable lengths exceeding 100m or 300ft must be installed as bus lines.

Branch lines are branching connections from a bus line.

Peripheral devices are AMC2 4W which are connected to the host computer.

Maximum cable length of a bus line must not exceed 1200m or 4000ft.

The cable length of branch lines must not exceed 100m or 300ft.

Any bus line conductor connects up to eight AMC2 4W. The maximum number of devices must not be exceeded.

For longer bus lines connect the AMC2 4W to multiple AMC-MUX (-EXT) with the host.

NOTE!

Up to seven AMC-MUX-EXT can be connected to an AMC-MUX.

i Every module subjects the conditions above. Using the exten- sions you can’t connect more than eight AMC2 4W.

To get more information about the AMC-MUX and the extension see the manual of these devices (F.01U.012.855).

To use RS-485 mode at the AMC2 4W, connect the data cables to the pluggable screw connector of the RS-485 host interface. Set the connection mode of the RS-485 using the DIL switch of the AMC-MUX. Then set the RS-485 address via DIL switch or software and activate the RS-485 two-wire or four-wire mode via jumper settings on the AMC - see Figure 5.10 and

Figure 5.12.

Bosch Security Systems

Installation manual

F.01U.024.965 V.4 2006.09

Image 31
Contents AMC2 4W Page Remarks Table of Contents Appendix OperatingIndex AMC2 4W Please read carefully Explanation of Used SymbolsInternet Important Safety Notes Safety InstructionsSafety Instructions en FCC & Ices Information Health and Safety Safety PrecautionsRead instructions Unpacking Description of the AMC2 4W IntroductionAMC2 4W in a four door safety lock Upper circuit board with display top side Equipment ConfigurationOverview Interfaces Jumper at the bottom side Performance Characteristics System overview System OverviewRTC Technical DataAMC 5VA Mounting InstallingDemounting Opening the AMC2 4W Case Cabling Conductor data for connection to power supplyGrounding and Shielding Location of ground jumper RS-485 host interface Grounding and Shielding the Host InterfaceAMC2 4W Grounding and Shielding the Extension Interface Connecting Power SupplyLocation of the power supply connector RS-485 Host Interface AMC2 4W RS-485 host interface 1 RS-485 Two Wire Connection10 Settings for RS-485 two wire connections 2 RS-485 Four Wire Connection12 Settings for RS-485 four wire connection DIL Switch Address SelectorAMC2 4W Mode DIL Switches Address DIL SwitchesRS-232 Host Interface 14 Location of the RS-232 serial interface Ethernet InterfaceIpconfig /flushdns Wiegand Interface for Card Readers RS-485 Extension Module Bus17 Location of the Wiegand interfaces for external devices 18 Location of the relay output connectors Connecting Relay Outputs19 Wet mode and dry mode of the AMC2 4W relay outputs Keep in mind the following specificationsRisk of Damage 20 Schema of the using of the recovery diode21 Location of relay output jumpers bottom side Connecting Analog Input DevicesComplete connection diagram of the analog input devices is Tamper Protection AMC2 4W Status Display of the AMC2 4W OperatingDig. IO Push Display Example DescriptionDig Resetting the AMC2 4W Configuring the Ethernet InterfaceResetting the Software Restarting the AMC2 4W with the provided screw driver Resetting the Network ConfigurationsAMC2 4W Appendix Connecting DiagramsConnecting diagram of the RS-232 serial interface AMC2 4W Power supply Twisted pair connection Transmitter Receiver I L O P IndexPage Bosch Security Systems