•Do not apply insulation to the top of the water heater, as this will interfere with safe operation of the draft hood.
•Do not cover the outer door, thermostat or temperature & pressure relief valve.
•Do not allow insulation to come within 2” (50.8 mm) of the floor to prevent blockage of combustion air fl ow to the burner.
•Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.
•Do obtain new warning and instruction labels from Sears for placement on the blanket directly over the existing labels.
•Do inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air fl ow.
Combustion Air and Ventilation for Appliances Located in Unconfined Spaces
UNCONFINED SPACE is space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfi ned space.
In unconfi ned spaces in buildings, infi ltration may be adequate to provide air for combustion, ventilation and dilution of fl ue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in Combustion Air and Ventilation for Appliances Located in Confi ned Spaces.
Combustion Air and Ventilation for Appliances Located in Confined Spaces
CONFINED SPACE is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kW) of the aggregate input rating of all appliances installed in that space.
A.ALL AIR FROM INSIDE BUILDINGS:
(See Figure 9 on page 9 and Figure 10 below)
The confi ned space shall be provided with two permanent openings communicating directly with an additional room(s) of suffi cient volume so that the combined volume of all spaces meets the criteria for an unconfi ned space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of one square inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization equipment in the confi ned space, but not less than 100 square inches (645 cm2). One opening shall commence
within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) of the bottom of the enclosures.
FIGURE 10.
B. ALL AIR FROM OUTDOORS: (See Figures 9, 11,12 and 13)
The confi ned space shall be provided with two permanent openings, one commencing within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
FIGURE 11.
•When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure. See Figure 12.
•When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure. See Figure 12.
11