AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow For Heater Location Ventilation Air

AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 3168 cu. ft. (volume of space) x 20 = 63,360 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 7.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

 

Gas water heater

40,000

_____________ Btu/Hr

Vent-free heater

33,000

+ _____________ Btu/Hr

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills Into Adjoining Room,

Total

73,000

= _____________ Btu/Hr

Room,

Or

Option 2

Option 1

Remove

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 63,360 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

Door into Adjoining Room, Option 3

12"

Figure 3 - Ventilation Air from Inside Building (EFP33PR Shown)

For..com

108117-01G

Image 6
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASTable of Contents Safety InformationFireplace Floor Assembly EFP33PR Shown Product IdentificationProduct Features Local CodesUnpacking Unusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined Space and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Heater LocationVentilation AIR Ventilation Air From Inside BuildingInstallation Ventilation Air From OutdoorsRemoving Fireplace Screen and Floor Assembly Installation ClearancesInstallation Sequence Check GAS TypeElectrical Connections for Power Cord Relocating Wall SwitchRelocating Switch and Wall Plate Installing Variable Speed Blower Accessory Ing from inside mantel see FigureAttaching Speed Control to Firebox VTGF33NR/ VTGF33PR Shown Installing Thermostatic Blower Accessory Operating the BlowerAttaching Speed Control VTGF33NR/VTGF33PR Shown Installing GAS Piping to Fireplace Location Installation Items Needed Pressure Testing Gas Supply Piping System Connecting Fireplace to GAS SupplyInstallation Items Needed Checking GAS ConnectionsConventional Fireplace Installation Pressure Testing Fireplace Gas ConnectionsBUILT-IN Fireplace Installation Installing Cabinet MantelMantel Clearances for Built-In Installation Assembling and Attaching Optional Brass TrimInstalling Logs VTGF33NR/VTGF33PR Installing HoodInstalling Logs CGEFP33PR/CGEFP33NR InstallingInstalling Logs EFP33PR/EFP33NR Installing Screen Installing Battery Into RemoteFor Your Safety Read Before Lighting Operating FireplaceNormal Lighting Instructions To Turn OFF GAS to ApplianceManual Lighting Instructions for Electrical Power Outage Shutting Off Heater When Manually LitOptional Blower Operation Front Burner Flame Pattern VTGF33 Series only Inspecting BurnersPilot Flame Pattern Main BurnerCleaning Pilot AIR Inlet Hole Cleaning MaintenanceCleaning Burner Injector Holder LogsTroubleshooting Observed Problem Possible Cause RemedyFor Com Gas leak. See Warning statement Technical Service SpecificationsService Hints Replacement PartsWiring Diagram EFP33NR/EFP33PR and CGEFP33NR/CGEFP33PR VTGF33NR/VTGF33PRIllustrated Parts Breakdown Parts List KEY Part Number EFP33 CGEFP33 Description QTYFirebox EFP33PR/NR CGEFP33PR/NR7 Firebox EFP33PR/NR CGEFP33PR/NR KEY Part Number Description QTYRemote Control LOG Base Assembly VTGF33PR and VTGF33NR Shown 101004-08 Front Burner Injector Natural 101004-02 Firebox VTGF33NR VTGF33PR Firebox VTGF33NR and VTGF33PR Accessories Slim Hearth Base Laminate Trim for Hearth or MantelCorner Hearth Base Firebox Brick Liner G8001 SeriesFor . .com Templates Diameter HolesThis page Intentionally Left Blank Owners Registration Form Postage Required 108117-01G Not a UPC