INSTALLATION

Built-In Fireplace Installation (Cont.) Installing Gas Piping to Fireplace Location

11

INSTALLATION

Continued

NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.

Installation Items Needed

Before installing fireplace, make sure you have the items listed below.

• external regulator for propane/LP unit only (supplied by installer)

• piping (check local codes)

sealant (resistant to propane/LP gas)

equipment shutoff valve *

Note:

All Vertical mea- surements are from top of fireplace opening to bottom of mantel shelf.

Minimum Non-

Combustible

Material

10"

8"

6"

2 1/2"

13"

16"

Mantel

Shelf

19"

 

21"

 

 

 

 

• test gauge connection *

sediment trap (optional)

tee joint

pipe wrench

• approved flexible gas line with gas connector (if allowed by lo-

 

cal codes) (not provided)

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, pages 28 through 30.

For propane/LP units, the installer must supply an external regula- tor. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent point- ing down as shown in Figure 17. Pointing the vent down protects it from freezing rain or sleet.

Figure 16 - Minimum Mantel Clearances for Built-In Installation

INSTALLING GAS PIPING TO FIREPLACE LOCATION

WARNING: This appliance requires a 1/2" NPT (National Pipe Thread) inlet connection to the pres- sure regulator.

WARNING: A qualified service person must con- nect fireplace to gas supply. Follow all local codes.

CAUTION: Never connect propane/LP fireplace directly to the propane/LP supply. This fireplace requires an external regulator (not supplied). Install the external regulator between the fireplace and pro- pane/LP supply.

WARNING: Never connect natural gas fireplace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diam- eter or greater to allow proper gas volume to fireplace. If pipe is too small, undue loss of volume will occur.

External

Propane/LP

Supply Tank

Regulator

 

Vent

Pointing

Down

Figure 17 - External Regulator on Propane/LP Supply Tank with Vent Pointing Down

For morevisit www..com

107172-01J

Image 11
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualSafety Information Table of ContentsProduct Identification Log Base Assembly VSGF33NRA ShownAIR for Combustion and Ventilation Product FeaturesLocal Codes UnpackingConfined and Unconfined Space Providing Adequate VentilationDetermining FRESH-AIR Flow for Heater Location Unusually Tight ConstructionVentilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Electrical Hookup InstallationInstalling Hood Check GAS TypeAssembling and Attaching Optional Brass Trim Installation ClearancesConventional Fireplace Installation Included with Mantel AccessoryPlacing Hearth Base Accessory Against Wall Mantel Clearances for Built-In Installation BUILT-IN Fireplace InstallationInstallation Items Needed Installing GAS Piping to Fireplace LocationGas Connection Connecting Fireplace to GAS SupplyChecking GAS Connections Pressure Testing gas Supply Piping systemPressure Testing Fireplace Gas Connections Place front log on top of the grate. Make sure the notches Installing Fireplace Screen Lighting Instructions For Your Safety Read Before LightingOperating Fireplace ON/OFF Series Models Ghrcb and Cghrcb Manual Lighting ProcedureTo Turn OFF GAS To Appliance Optional HAND-HELD Remote OperationPilot Flame Pattern Inspecting BurnersOptional Blower Operation Front Burner Flame Pattern Cleaning MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Main BurnerModels EFS33NR, EFS33NRA, VSGF33NR, and VSGF33NRA Wiring DiagramSpecifications LogsObserved Problem Possible Cause Remedy TroubleshootingMaintenance, For more Visit www Com Illustrated Parts Breakdown Not a field replaceable part Parts ListModels EFS33NR, EFS33NRA, VSGF33NR, VSGF33NRA KEY Part Number Description QTY Accessories Laminate Trim for Hearth or Mantel Cabinet Mantel and Full Hearth BaseCorner Hearth Base Hardwood Hearth BaseTechnical Service Replacement PartsService Hints Owners Registration Form Tape 107172-01J Warranty Information