Desa EFS33PRA installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 6

6

AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow for Heater Location (Cont.) Ventilation Air

AIR FOR COMBUSTION AND VENTILATION

Continued

The space in the example on page 5 is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the

extra space provides an unconfined space, remove door to adjoining

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills

Into Adjoining Room,

room or add ventilation grills between rooms. See Ventilation Air From

Room,

Or

Option 2

Inside Building.

Option 1

Remove

B.

Vent room directly to the outdoors. See Ventilation Air From Outdoors.

C.

Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Door into Adjoining Room, Option 3

12"

Figure 3 - Ventilation Air from Inside Building

 

 

Outlet

 

Ventilated

 

 

 

Attic

 

 

Air

 

 

 

 

 

 

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To Attic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

;;;;QQQQ¢¢¢¢

To

 

 

 

Crawl

Inlet

 

 

Space

 

 

 

 

Inlet Air

Ventilated

 

 

Crawl Space

 

 

 

 

Figure 4 - Ventilation Air from Outdoors

 

Forvisit..com

107172-01J

Image 6
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASTable of Contents Safety InformationLog Base Assembly VSGF33NRA Shown Product IdentificationUnpacking Product FeaturesLocal Codes AIR for Combustion and VentilationUnusually Tight Construction Providing Adequate VentilationDetermining FRESH-AIR Flow for Heater Location Confined and Unconfined SpaceVentilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Check GAS Type InstallationInstalling Hood Electrical HookupIncluded with Mantel Accessory Installation ClearancesConventional Fireplace Installation Assembling and Attaching Optional Brass TrimPlacing Hearth Base Accessory Against Wall BUILT-IN Fireplace Installation Mantel Clearances for Built-In InstallationInstalling GAS Piping to Fireplace Location Installation Items NeededConnecting Fireplace to GAS Supply Gas ConnectionPressure Testing gas Supply Piping system Pressure Testing Fireplace Gas ConnectionsChecking GAS Connections Place front log on top of the grate. Make sure the notches Installing Fireplace Screen For Your Safety Read Before Lighting Operating FireplaceLighting Instructions Optional HAND-HELD Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance ON/OFF Series Models Ghrcb and CghrcbInspecting Burners Optional Blower OperationPilot Flame Pattern Main Burner Cleaning MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Front Burner Flame PatternLogs Wiring DiagramSpecifications Models EFS33NR, EFS33NRA, VSGF33NR, and VSGF33NRATroubleshooting Observed Problem Possible Cause RemedyMaintenance, For more Visit www Com Illustrated Parts Breakdown Parts List Not a field replaceable partModels EFS33NR, EFS33NRA, VSGF33NR, VSGF33NRA KEY Part Number Description QTY Accessories Hardwood Hearth Base Cabinet Mantel and Full Hearth BaseCorner Hearth Base Laminate Trim for Hearth or MantelReplacement Parts Service HintsTechnical Service Owners Registration Form Tape 107172-01J Warranty Information